INSTRUCTION & SERVICE MANUAL 

D1xS1 & D1xS2 RADIAL ALARM HORNS 

For Use In Hazardous Locations - Gas 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1) 

Introduction 

 
The  D1xS1  &  D1xS2  range  are  UL  Classified  alarm  horns 
which  produce  a  loud  warning  signal  in  a  hazardous  area. 
Sixty-Four first stage alarm sounds can be selected by internal 
switches and each one can be externally changed to a second, 
third or fourth stage alarm sound. The alarm horn may be used 
for Gas applications in Class I Division 1 & 2 as well as Class  
I  Zone  1  &  2.  The  D1xS1  variants  are  also  ATEx  /  IECEx 
certified and can be used for gas applications in Zones 1 & 2. 
D1xC1  &  D1xC2  combined  alarm  horn  &  strobe  units  and 
D1xL1  &  D1xL2  Loudspeakers  are  also  available  as  well  as 
variants for Explosive Dust Atmospheres. 

 

2)  Cautions and Warnings 

 

CAUTION 
TO REDUCE THE RISK OF IGNITION OF HAZARDOUS 
ATMOSPHERES: 
DISCONNECT FROM SUPPLY BEFORE OPENING. 
KEEP TIGHTLY CLOSED WHEN IN OPERATION. 
WARNING 
FIT SEALING FITTING IN CONDUIT RUNS WITHIN 18 
INCHES FROM ENCLOSURE. 
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS 
PRESENT 

 

DO NOT OPEN WHEN ENERGISED  
POTENTIAL ELECTROSTATIC CHARGING HAZARD - 
CLEAN ONLY WITH A DAMP CLOTH  
 
ATTENTION 

P

OUR REDUIRE LE RISQUE D’INFLAMMATION  DES 

ATMOSPHÈRES DANGEREUSES: 
COUPER L 'ALIMENTATION AVANT OUVERTURE. 
CONSERVER FERMÉ PENDANT LE FONCIONNEMENT. 
AVERTISSEMENT 
CONDUITS DOIVENT ÊTRE SCELLÉS EN MOINS DE 18 
POUCES. 
NE PAS OUVRIR UN PRESENCE D’ATMOSPHERE 
EXPLOSIVE  
NE PAS OUVRIR ENERGIE  
DANGER POTENTIEL CHARGE ÉLECTROSTATIQUE - 
NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE  
 
 
 

 

3)  Ratings and Markings 

 
The D1xS1 and D1xS2 Alarm Horns comply with the following 
standards for hazardous locations:  
 
UL 1203 
CSA C22.2 NO. 30-M1986 
 
The  D1xS1  and  D1xS2  Alarm  Horns  also  comply  with  the 
following standards for signaling equipment:  
UL464 
CSA C22.2 NO. 205-12 

3.1 Class / Division Ratings for US & Canada 

 
Class I Div 1 

ABCD 

T6 

Ta -40°C to +70°C 

 

 

Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 
 

3.2 Class / Zone ratings US & Canada

 

 
Class I Zone 1 

IIC 

T6 

Ta -40°C to +70°C 

 
Installation must be carried out in compliance with the National 
Electric Code / Canadian Electric Code 

 
3.3 Fire Alarm Rating 

 
The  following  models  are  approved  for  use  as  audible  signal 
appliances  for  fire  alarm  use 

–  public  mode  and  produce  a 

sound pressure level above 75dB(A) at 10 feet: 
 
D1xS1-DC024 / D1xS2-DC024  
 
For  public  mode  fire  alarm  use  the  temporal  pattern  tone  No. 
12 as per the tone table provided in these instructions must be 
selected. For Fire Alarm use, units must be supplied 18-30Vdc. 
 

3.4 Ambient Temperature Range: 

 
D1xS1-DC024 / D1xS2-DC024 / D1xS2-AC230: 
-40ºC to +70ºC  
D1xS1-AC230: 
-40ºC to +70ºC for 110-120Vac 50/60Hz 
-40ºC to +55ºC for 120-240Vac 50/60Hz  
 

3.5 Ingress Protection Ratings 

 
The product is rated for ingress protection as follows: 
 

IP rating per EN60529: 

 

IP66 

 

Type rating per UL50E / NEMA250: 

4 / 4X / 3R / 13  

  
3.6 Electrical Ratings per UL Listing 

 

Model No. 

Nom. 
Voltage 

Nom. rms 
current

2

 

Voltage  
Range 

Max. rms 
current

3

 

D1xS1-DC024  24Vdc 

217mA 

10-30Vdc

1

 

270mA @ 
18Vdc 

D1xS1-AC230  115Vac 60Hz 

230Vac 50Hz 

77mA 
53mA 

110-240Vac 
50/60Hz 

82mA @ 
110Vac 60Hz 

D1xS2-DC024  24Vdc 

924mA 

10-30Vdc

1

 

1217mA @ 
18Vdc 

D1xS2-AC230  115Vac 60Hz 

230Vac 50Hz 

268mA 
159mA 

110-240Vac 
50/60Hz 

293mA @ 
110Vac 60Hz 

 

The D1xS1 & D1xS2 alarm horns are 

classified by UL as Audible Signaling 

Appliances for General Signaling and 

Public Mode Fire Alarm use in Hazardous 

Locations 

Summary of Contents for D1xS1 Series

Page 1: ...ENTIEL CHARGE LECTROSTATIQUE NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE 3 Ratings and Markings The D1xS1 and D1xS2 Alarm Horns comply with the following standards for hazardous locations UL 1203 CSA C...

Page 2: ...rical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres 4 Installation 4 1 Safe Installation Requirements T...

Page 3: ...y to remove the explosionproof cover to gain access to the explosionproof chamber This can be achieved by unscrewing the explosionproof cover counter clockwise taking extreme care not to damage the ex...

Page 4: ...Simplified Block Diagram negative switching Fig 7b DC Simplified Block Diagram positive switching 10 2 Units First Stage Tones Stage one S1 operation Simply connect the supply voltage to the and suppl...

Page 5: ...f 0 82mm2 18AWG in size 12 End Of Line Monitoring DC Units Only On D1xS1DC D1xS2DC units dc reverse line monitoring can be used if required All DC alarm horns have a blocking diode fitted in their sup...

Page 6: ...9 34 1 10 1000Hz 1s on 1s off x7 7s on 1s off IMO Code 1a 1 0 0 1 0 0 10 34 1 11 420Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 11 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO...

Page 7: ...0 1 48 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 49 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 50 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 51 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0...