E2S BExL15D Instruction Manual Download Page 4

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-101-IS

 

Issue 6

 

12-09-2022

Sheet 4 of 5

 

8.  Selection of Cable. Cable Glands, Blanking 

Elements & Adapters 

 

When selecting the cable size, consideration must be given to 
the input current that each unit draws (see table above), the 
number  of  sounders  on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 
capacity  to  provide  the  input  current  to  all  of  the  sounders 
connected to the line.  

 

For  ambient  temperatures  over  +40ºC  the  cable  entry 
temperature  may  exceed  +70ºC  and  therefore  suitable  heat 
resisting cables and cable glands must be used, with a rated 
service temperature of at least 110ºC 

 

The dual cable gland entries have an M20 x 1.5 entry thread. 
To  maintain  the  ingress  protection  rating  and  mode  of 
protection, the cable entries must be fitted with suitably rated 
ATEX / IECEx or UKEx certified cable glands and/or suitably 
rated ATEX / IECEx or UKEx certified blanking devices during 
installation according to EN / IEC60079-14. 

 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs.  

 

For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 

 

The  BEx  sounder  range  can  be  supplied  with  the  following 
types of adapters: 

 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 
It is important to note that stopping plugs cannot be fitted onto 
adapters, only directly onto the M20 entries. 
 
Any other adapters used must be suitably rated and ATEX / 
IECEx or UKEx certified adapters. 

 

9.  Earthing 

 

Both AC and DC sounder units must be connected to an earth. 
The  units  are  provided  with  internal  and  external  earth 
terminals  which  are  both  located  on  the  terminal  chamber 
section of the unit. 

 

Fig. 3 Internal View of Cover 

 

When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure.  

 

Internal earthing connections should be made to the Internal 
Earth terminal in the base of the housing using a ring crimp 

terminal to secure the earth conductor under the earth clamp. 
The earth conductor should be at least equal in size and rating 
to the incoming power conductors. Tighten M4 Earth screw to 
1Nm. 

 

External earthing connections should be made to the M5 earth 
stud, using a ring crimp terminal to secure the earth conductor 
to the earth stud. The external earth conductor should be at 
least 4mm² in size.

 

Tighten the Earth nut to 3Nm. Please firmly 

tighten the external grounding terminal so that the stud does 
not  become  loose  and  lay  the  ground  wire  so  that  it  is  not 
caught by twisting and sagging. 
 

10.  70V & 100V Line In Wiring 

 

The cable connections are made into the terminal blocks on 
the PCB assembly located in the explosion proof enclosure. 
See section 7 of this manual for access to the explosion proof 
enclosure. The 70V & 100V Line loudspeakers are fitted with 
a five way terminal block. Terminal A is common and one of 
the other terminals B, C, D or E should be selected 
depending on what output level is required (see table below). 

 

Terminals  BExL25D (25W)  BExL15D (15W) 

A – B 

25W 

15W 

A – C 

12.5W 

7.5W 

A – D 

6W 

3W 

A – E 

2W 

1W 

 

A single wire with a cross sectional area of up to 4mm² can be 
connected to each terminal way or if an input and output wire 
is  required  two  2.5mm²  wires  can  be  connected  to  each 
terminal  way.  When  connecting  wires  to  the  terminals  great 
care should be taken to dress the wire so that when the cover 
is  inserted  into  the  chamber  the  wires  do  not  exert  excess 
pressure on the terminal blocks. This is particularly important 
when  using  cables  with  large  cross  sectional  areas  such  as 
2.5mm² and above. 

 

A

B

C

D

E

 

Fig. 4 Line In Terminals 

External Earthing 

Internal 
Earthing 

Internal 
Bonding 
Wire 
Terminal 

2-off M20 
Cable 
Entries 

 

D

 

 

C

 

 

B

 

 

A

 

Summary of Contents for BExL15D

Page 1: ...o the type of loudspeaker being used Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 100V line output Low impedance 8 ohm or 16 oh...

Page 2: ...operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C ambient Temperature Classification for Gas A...

Page 3: ...ghtened to ensure that the unit cannot move in service Fig 1a Fixing Location for BExL15D Sounder Fig 1b Fixing Location for BExL25D Sounder 7 Access to the Flameproof Enclosure To access the Ex d cha...

Page 4: ...the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing conne...

Page 5: ...st have a minimum resistance value of 4k7 ohms and a minimum wattage of 2 5 watts On low impedance units the end of line resistor used must have a minimum resistance value of 2k ohms and a minimum wat...

Page 6: ...HEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 101 R S RAIT R N POTTS R N POTTS 05 08 2022 OF BExL15 BExL...

Page 7: ...LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TIT...

Page 8: ...nds B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T4 Gb II 2G Ex db eb IIB or I...

Page 9: ...are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evalu...

Page 10: ...duction process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the eq...

Page 11: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 12: ...Page left Intentionally blank...

Reviews: