3.  Marking & Rating Information 

The BExS110E, BExS110E-R & BExS120E Alarm Horns comply with 
the following standards for hazardous locations:  
  

3.1 ATEX / IECEx & UKEx Ratings

 

 

Standards

EN60079-0:2018/IEC60079-0:2017 

(ed.7): 

Explosive 

Atmospheres - Equipment General Requirements. 
EN60079-1:2014/IEC60079-1:2014 

(ed.7): 

Explosive 

Atmospheres - Equipment Protection by Flameproof Enclosures 
“d”. 
EN60079-31:2014/IEC60079-31:2013 

(ed.2): 

Explosive 

Atmospheres - Equipment Dust Ignition Protection by enclosure 
“t”. 

Model No: 

Rating 

BExS110D 

BExS110D-R 

Ex db IIC T4 Gb Ta. -50°C to +55°C  
Ex db IIB T4 Gb Ta. -50°C to +70°C 
Ex tb IIIC T100°C Db Ta. -50°C to +55°C 
Ex tb IIIC T115°C Db Ta. -50°C to +70°C 

See Product table for electrical ratings of each unit model 

 

Certificate No.    

KEMA  99ATEX6312X  
IECEx KEM 10.0003X 
UL22UKEX2638X          

Epsilon x 
Equipment Group 
and Category: 

 

II 2G 
II 2D

 

CE Marking and 
Notified Body No. 

2813 

UKCA Marking and 
Approval Body No. 
 

 

0518 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.  Zones, Gas Group, Category and 

Temperature Classification 

The units can be installed in locations with the following conditions: 
 

Area Classification Gas 

Zone 1 

Explosive gas air mixture likely to occur in normal 
operation.

Zone 2 

Explosive gas air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Gas Groupings 

Group IIA

Propane

Group IIB

Ethylene

Group IIC

Hydrogen and Acetylene (up to 55°C ambient)

Temperature Classification for Gas Applications

T1

450

o

T2

300

o

C

T3

200

o

C

T4

135

o

C

Area Classification Dust 

Zone 21 

Explosive dust air mixture likely to occur in normal 
operation.

Zone 22 

Explosive dust air mixture not likely to occur in 
normal operation, and if it does, it will only exist for 
a short time. 

Dust Groupings 

Group IIIA

Combustible Dusts 

Group IIIB

Non-Conductive Dusts 

Group IIIC

Conductive Dusts 

Equipment Category 

2G, 2D

Equipment Protection Level 

Gb, Db,

Maximum Surface Temperature for Dust Applications

100°C at +55°C 

115°C at +70°C  

Ambient Temperature Range

-50°C to +55°C Gas Groups IIA, IIB and IIC 

-50°C to +70°C Gas Groups IIA and IIB 

-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

IP Rating 

IP66/67 to EN/IEC60529 and

IP6X to EN/IEC60079-0, EN/IEC60079-31 

The sounder must only be installed by suitably qualified personnel in 
accordance with the latest issues of the relevant standards: 
  
EN60079-14  /  IEC60079-14:  Explosive  atmospheres  -  Electrical 
installations design, selection and erection 
EN60079-10-1  /  IEC60079-10-1:  Explosive  atmospheres  - 
Classification of areas. Explosive gas atmospheres 
EN60079-10-2  /  IEC60079-10-2:  Explosive  atmospheres  - 
Classification of areas. Explosive dust atmospheres 
 
The  installation  of  the  sounder  must  also  be  in  accordance  with  any 
local  codes  that  may  apply  and  should  only  be  carried  out  by  a 
competent electrical engineer who has the necessary training.

 

 

 

Summary of Contents for BExL15D

Page 1: ...o the type of loudspeaker being used Loudspeakers with a 70V or 100V line matching transformer fitted must be connected to a power amplifier with a 70V or 100V line output Low impedance 8 ohm or 16 oh...

Page 2: ...operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C ambient Temperature Classification for Gas A...

Page 3: ...ghtened to ensure that the unit cannot move in service Fig 1a Fixing Location for BExL15D Sounder Fig 1b Fixing Location for BExL25D Sounder 7 Access to the Flameproof Enclosure To access the Ex d cha...

Page 4: ...the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing conne...

Page 5: ...st have a minimum resistance value of 4k7 ohms and a minimum wattage of 2 5 watts On low impedance units the end of line resistor used must have a minimum resistance value of 2k ohms and a minimum wat...

Page 6: ...HEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D210 06 101 R S RAIT R N POTTS R N POTTS 05 08 2022 OF BExL15 BExL...

Page 7: ...LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS STANDARDS MOD No REASON INITIAL DATE ISSUE DATE APPROVED CHECKED DATE DATE DRAWN WEIGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TIT...

Page 8: ...nds B V Utrechtseweg 310 6812 AR Arnhem Netherlands Quality Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 2G Ex db IIB or IIC T4 Gb II 2G Ex db eb IIB or I...

Page 9: ...are in accordance with the restriction of the use of hazardous substances in electrical and electronic equipment including amendment by Directive 2015 863 EU Regulation EC 1907 2006 Registration Evalu...

Page 10: ...duction process Module D Sira Certification Service Notified Body No 0518 Rake Lane Eccleston Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the eq...

Page 11: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the...

Page 12: ...Page left Intentionally blank...

Reviews: