13) 

 Tone Selection 

 

 

The BExDTS110D Sontels have 32 different tones that can be 
selected by the DIP switches on the sounder pcb (see figures 
4  and  5).  The  tone  table  on  page  four  shows  the  switch 

positions for the 32 tones.  
 

14) 

 Pulse Tone Operation 

 
The  BExDTS110D  Sontel  has  two  modes  of  operation 

continuous  tone  operation  and  pulsed  tone  operation.  To 
select  continuous  tone  operation  the  pulse  tone  header  pins 
should not be shorted (see figures 4 and 5). In this mode the 
output tone will be as per the tone table. To select pulse tone 
operation  the  pulse tone  header pins should  be shorted  (see 
figures 4  and  5). In this mode  of operation  the  selected  tone 
pattern  will  pulse  on  and  off  following  the  telephone  input 

signal. Note if pulsed tone operation is selected it is advisable 
not to select any of the intermittent tones, such as tone 11. 

 

15) 

 Volume Control

 

 
T

he  BExDTS110D  Sontel  has  a  volume  control  to adjust  the 

output  level.  To  set  the  required  output  level,  adjust  the 

potentiometer on the sontel pcb (see figure 4). For maximum 
output  level  the  potentiometer  should  be  set  to  the  fully 

clockwise position. 
 

  
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

 

TONE SELECTION TABLE  
 

Note Switch No. 6 is not used 

 

 

Tone Selection 

DIP Switch                                    

Settings 

Stage 1 

Frequency Description 

1    2   3   4   5 

 

Continuous  1000Hz  

Toxic gas alarm 

0    0   0   0   0 

Alternating  800/1000Hz  at  0.25s 

intervals 

1    0   0   0   0 

Slow  Whoop  500/1200Hz  at  0.3Hz 

with 0.5s gap repeated 

0    1   0   0   0 

Sweeping 800/1000 at 1Hz 

1    1   0   0   0 

Continuous at 2400Hz 

0    0   1   0   0 

Sweeping 2400/2900Hz at 7Hz 

1    0   1   0   0 

Sweeping 2400/2900Hz at 1Hz 

0    1   1   0   0 

Siren 500/1200/500Hz at 0.3Hz 

1    1   1   0   0 

Sawtooth 1200/500Hz at 1Hz 

0    0   0   1   0 

10 

Alternating 2400/2900Hz at 2Hz 

1    0   0   1   0 

11 

Intermittent  1000Hz  at  0.5Hz 

General alarm

 

0    1   0   1   0 

12 

Alternating 800/1000Hz at 0.875Hz 

1    1   0   1   0 

13 

Intermittent 2400Hz at 1Hz 

0    0   1   1   0 

14 

Intermittent 800Hz 0.25s on 1s off 

1    0   1   1   0 

15 

Continuous at 800Hz 

0    1   1   1   0 

16 

Intermittent  660Hz  150mS  on, 

150mS off 

1    1   1   1   0 

17 

Alternating 544Hz  

(100mS)/440Hz(400mS) 

0    0   0   0   1 

18 

Intermittent 660Hz 1.8s on, 1.8s off 

1    0   0   0   1 

19 

1400Hz  to  1600Hz  sweep  up over 

1s - 1600Hz to 1400Hz sweep down  

over 0.5s 

0    1   0   0   1 

20 

Continuous 660Hz  

1    1   0   0   1 

21 

Alternating 554/440Hz at 1Hz 

0    0   1   0   1 

22 

Intermittent 554Hz at 0.875Hz 

1    0   1   0   1 

23 

800Hz pulsing at 2Hz 

0    1   1   0   1 

24 

Sweeping 800/1000Hz at 50Hz 

1    1   1   0   1 

25 

Sweeping 2400/2900Hz at 50Hz 

0    0   0   1   1 

26 

Simulated bell sound 

1    0   0   1   1 

27 

Continuous 554Hz 

0    1   0   1   1 

28 

Continuous 440Hz 

1    1   0   1   1 

29 

Sweeping 800/1000Hz at 7Hz 

0    0   1   1   1 

30 

420Hz repeating 0.625s on, 0.625s 

off  

Australian alert signal

 

1    0   1   1   1 

31 

1200/500Hz at 1 Hz  

Prepare to abandon platform 

0    1   1   1   1 

32 

Sweeping 500/1200Hz 3.75s on, 

0.25s off 15Hz 

1    1   1   1   1 

BExDTS110D  DC Sontels 

DC Power Supply  

Input Terminals 
+ve and -ve 

Telephone Signal 
Input Terminals 

Terminal block 
not used 

DIP Switch 

Volume Control 

Pulse Tone 

Header Pin 

Figure 5 