background image

__________________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)20 8743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)20 8740 4200 
Document No. IS 2457-P   Issue E       12-03-10                                     Sheet 3 of 4 

9) 

 Cable Selection 

 

When selecting the cable size consideration must be given to 
the  input  current  that  each  unit  draws (see  table  above),  and 

the length of the cable runs.  
 
SAFETY WARNING: If the high output BExDTS110D units are 
used  at  high  ambient  temperatures,  i.e. over  +40ºC,  then  the 
cable  entry  temperature  may  exceed  +70ºC  and  therefore 

suitable  heat  resisting  cables  must  be  used,  with  a  rated 
service temperature of at least 110ºC. 

 

10) 

  Earthing

 

 

The  Sontel units  must  be connected  to  a good  quality earth. 
The  units  are  provided  with  internal  and  external  earthing 
terminals  which  are  both  located  on  the  terminal  chamber 
section of the unit (see figures 2 and 3).  

 

 
When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel  M4  flat  washer  is between the incoming earth 

wire and the enclosure. 
 

When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel  M4  flat  washer  is between the incoming earth 

wire and the enclosure. 
 
When using the external earth terminal a cable crimp lug must 

be used.  The cable lug should be located between the two M5 
stainless steel flat washers. The M5 stainless steel spring 

washer must be fixed between the outer flat washer and the 
M5 stainless steel nut to ensure that the cable lug is secured 

against loosening and twisting.  
 

The  internal  earth  bonding  wire  ensures  that  a  good  quality 
earth  is  maintained between the flameproof chamber  casting 
and the flameproof cover casting. 

 

11) 

 Cable Glands

 

 

The  BExDTS110D  Sontels  have  dual  cable  gland  entries 
which  have  an  M20  x  1.5  as  standard.  Only  cable  glands 
approved for Ex  ‘d’ applications can  be  used, which  must be 
suitable  for  the  type  of  cable  being  used  and  also  meet  the 
requirements  of  the  Ex  ‘d’  flameproof  installation  standard  

EN60079-14:2008 / IEC60079-14:2007. 
 

When  only  one  cable  entry  is  used  the  other  one  must  be 
closed with an Ex ‘d’ flameproof blanking plug, which must be 
suitably approved for the installation requirements.  

 
For combustible dust applications, the cable entry device and 

blanking  elements  shall  be  in  type  of  explosion  protection 
increased safety "e" or flameproof enclosure "d" and shall have 
an IP 6X rating according to EN 60529. 
 
SAFETY WARNING: If the BExDTS110D Sontels are used at 
high  ambient  temperatures,  i.e.  over  +40ºC,  then  the  cable 
entry  temperature  may  exceed  +70ºC  and  therefore  suitable 

heat resisting cable glands must be used, with a rated service 
temperature of at least 110ºC. 
 

12) 

 Cable Connections 

 

The  cable connections  are  made  into  the terminal blocks  on 

the Sontel pcb assembly located in the flameproof enclosure. 
See  section  7  of  this  manual  for  access  to  the  flameproof 

enclosure.  The printed circuit  board  has  two  terminal  blocks; 
one  for  the  power  supply  input  voltage  and  one  for  the 

telephone signal input cable (see figures 4 and 5). The power 
input  cable  should  enter  the  enclosure  via  one  of  the  M20 
cable entries and be connected to the supply terminals (L and 

N) AC units (+ve and –ve) DC units and the telephone signal 
cable should enter the enclosure via the other M20 entry and 

be connected to the telephone terminal. 
 

A single wire with a cross sectional area of up to 4mm² can be 
connected to each terminal way. When connecting wires to the 
terminals great care should be taken to dress the wire so that 

when the cover is inserted into the chamber the wires do not 
exert  excess  pressure  on  the  terminal  blocks.  This  is 

particularly  important  when  using  cables  with  large  cross 
sectional areas such as 2.5mm² and above. 
 
 

 

 

 

 
 
 
 

 
 
 
 
 
 

Figure 4 

BExDTS110D  AC Sontels 

DIP Switch 

Volume Control 

Telephone Signal 
Input Terminals 

Mains Supply  

Input Terminals 
L and N 

Pulse Tone 
Header Pin 

2 off M20  

Cable Entries 

Internal Earth Terminal 

Figure 3 

Internal Bonding 

Wire Terminal 

Reviews: