background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No. IS 2441-P      Issue G          19-03-10                                

Sheet 4 of 6 

two  neutral  terminals  for  the  input  and  output  wiring  on  AC 
units. On the DC units there are two +ve terminals and two -

ve terminals for the input and output wiring. 
Wires  having  a  cross  sectional  area  of  up  to  4mm²  can  be 

connected  to  each  terminal  way.  When  connecting  wires  to 
the terminals great care should be taken to dress the wires so 

that  wires  do  not  exert  excess  pressure  on  the  terminal 
blocks. This is particularly important when using cables with 
large cross sectional areas such as 2.5mm² and above. 

 

 

 
 

 

 

 
 

 

14) 

Tone Selection and 2nd and 3rd Stage Alarms

 

 

The  BExCS110-05D sounder  section  has  32  different  tones 

that can be selected for the first stage alarm. The sounders 
can then be switched to sound second and third stage alarm 

tones. The tones are selected by operation of a DIP switch on 
the sounder pcb for both DC and AC units. The tone table on 

page  five  shows  the  switch  positions  for  the  32  tones  and 
which tones are available for the second and third stages. To 
operate the sounder on stage one simply connect the supply 

voltage to the normal supply terminals (+ve and –ve for DC 
units,  L and N for AC units).  

 
The operation of the second and third stages is different for 

DC and AC units. 
 

DC Units Second and Third Stage Tone Selection 
 

The  BExCS110-05D  DC  sounder  section  has  the  facility  to 
use  either  +ve  or  –ve  switching  to  change  the  tone  to  the 

second and third stages. For –ve switching connect the two 
headers on the pcb to the left-hand (marked –ve) and centre 

pins. For +ve switching connect the headers to the right hand 
(ve) and the centre pins. To change to the second 

stage tone, connect either a -ve or +ve supply line to terminal 
S2, depending on which switching mode is being used while 
maintaining  the  dc  supply  to  the  +ve  and  –ve  terminals. 

Similarly for the third stage tone, connect a -ve or +ve supply 
line  to  terminal  S3.  The  supply  to  the  S3  terminal  will 

automatically override a supply to the S2 terminal. 
 

AC Units Second and Third Stage Tone Selection 
 
To  select  the  second  and  third  stage  tones  on  the 

BExCS110-05D  AC  sounder  section,  the  Common  (C) 
terminal  on  the  three  way  terminal  block  on  the  pcb  is 

connected to the S2 terminal for the second stage tone and 
the S3 terminal for the third stage tone. 

 

 

 

 

 

 

 

15) 

Volume Control

 

 

The  BExCS110-05D  sounder  section,  with  the  exception  of 
12V DC units, has a volume control to adjust the output level. 

To set the required output level, adjust the potentiometer on 
the pcb. For maximum output level the potentiometer should 

be set to the fully clockwise position. 
 

Figure 7 

Figure 6 

BExCS110-05D  DC Sounder Section 

BExCS110-05D  AC Sounder Section 

Volume Control 

DIP Switch 

DIP Switch 

Volume Control 

DC Input 
Terminals 

Stage Headers 

Stage Terminals 

AC Input 

Terminals 

 
S2 
S3

 


+

 

       S2 
       S3 
        C 
 
 
        N 
        L

 




N

 

Figure 4 

AC Input 

Terminals 

Interconnecting Terminals to 

sounder pcb (simultaneous 
mode of operation) 

BExCS110-05D  AC Beacon Section 

Flip / Flop 

Pin Header 

DC Input 

Terminals 

Figure 5 




+

 

Flip / Flop 

Pin Header 

BExCS110-05D  DC Beacon Section 

Interconnecting Terminals to 
sounder pcb (simultaneous 

mode of operation) 

Reviews: