11.  AC Wiring 

 

A 4-way terminal block is provided on the AC chamber beacon 
for power. There are 2-off Live and 2-off Neutral terminals in 
total.  A  4-way  terminal  block  is  provided  on  the  AC  cover 
beacon  for  power.  There  are  2-off  Live  and  2-off  Neutral 
terminals in total.  

 

 

 

Fig. 5 AC Terminals 

 

 

12.  DC Wiring 

 

A 4-way terminal block is provided on the DC chamber beacon 
for power. There are 2-off +ve and 2-off -ve terminals in total. 
A 4-way terminal block is provided on the AC cover beacon for 
power. There are 2-off +ve and 2-off -ve terminals in total.  

 

 

 

Fig. 6 DC Terminals 

 

 

 

12.1 

Line Monitoring 

 

On BExCBGL2-L2D DC units, dc reverse line monitoring can 
be  used  if  required.  All  DC  sounders  have  a  blocking  diode 
fitted in their supply input lines. An end of line monitoring diode 
or an end of line monitoring resistor can be connected across 
the +ve and –ve terminals. If an end of line resistor is used it 
must  have  a  minimum  resistance  value  of  3k3Ω  and  a 
minimum power rating of 0.5 watts or a minimum resistance 
value of 500Ω and a minimum power rating of 2 watts. 

 

The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor 
leads should be kept as short as possible.  

 

 

Fig. 7 End of Line Resistor Placement 

 

13.  Flash Rate Settings 

 

 

The BExB2L2D beacons can produce different flash patterns 
as  shown  in  Table  1.  The  flash  patterns  are  selected  by 
operation of the flash setting DIP switch on the PCB, Fig 9.   

 

 

Fig. 8: DIP Switch Location 

 

Table 1: Switch Positions for Flash Patterns 

 

 

 

Switch 

Setting

S1 Mode 

S2 Mode 

S3 Mode 

(123456) 

(DC & AC) 

(DC Only) 

(DC Only) 

000000 

Steady High 

Power 

Flashing 1Hz 

Flashing Triple 

Strike 

000001 

Steady Low 

Power 

Flashing 1Hz 

Flashing Triple 

Strike 

100000 

Flashing 1Hz 

Flashing 

Double Strike 

Flashing Triple 

Strike

101000 

Flashing 

1.5Hz 

Flashing 2Hz

 

Flashing 

Double Strike 

010000 

Flashing 2Hz 

Flashing Triple 

Strike 

Flashing Triple 

Strike 

110000 

Flashing 

Double Strike

Steady High 

Power 

Flashing Triple 

Strike

001000 

Flashing 

Triple Strike

Flashing 2Hz 

Flashing 

Double Strike

Warning – high-intensity light source. Avoid 
looking directly at the light source for 
extended periods of time. 

End of Line 
Resistor

 

L

 

 

N

 

 

N

 

 

E

 

 

E

 

 

+

 

 

-

 

 

-

 

 

S2

 

 

S3

 

Summary of Contents for BExCBL2-L2D-P

Page 1: ...ent taken by the various units Nominal current at nominal voltage Table 1 Electrical Ratings It is important that a suitable power supply is used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all of the units The above table shows the input current taken by the various units and shows the maximum voltage at which they can be operate...

Page 2: ...ccur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen Acetylene Temperature Classification for Gas Applications T1 450o C T2 300o C T3 200o C T4 135o C T5 100ºC T6 85ºC up to 55ºC ambient Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust a...

Page 3: ...d to ensure that the unit cannot move in service Fig 1 Fixing Location for Combined Beacon Beacon 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexagon socket head screws and withdraw the flameproof cover taking extreme care not to damage the flameproof joints in the process M6 cover screws are Class A4 80 stainless steel and only screws of this category can be...

Page 4: ...n using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing connections should be made to the Internal Earth terminal in the base of the housing using a ring crimp terminal to secure the earth conductor under the earth clamp The earth conductor should be at least equal in size and rating to the incoming p...

Page 5: ...mum resistance value of 3k3Ω and a minimum power rating of 0 5 watts or a minimum resistance value of 500Ω and a minimum power rating of 2 watts The resistor must be connected directly across the ve and ve terminals as shown in the following drawing The resistor leads should be kept as short as possible Fig 7 End of Line Resistor Placement 13 Flash Rate Settings The BExB2L2D beacons can produce di...

Page 6: ... Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance The acoustic horn is made out of ABS plastic ther...

Page 7: ...5W MIN MINIMUM VALUES R1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 3 to ve 24 03 2022 24 03 2022 24 03 2022 BExBGL2D BExC...

Page 8: ...NTS 1 1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 2 to ve Stage 3 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Connect Stage 3 to ve 24 03 2022 24 03 2022 24 03 2022 BExBGL2D BExCBL2 L2D DC LED LE...

Page 9: ...uality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G Ex db IIB T6 to T4 Gb II 2D Ex tb IIIC T65 C to T130 CDb IP6X Dust Protectionto EN60079 0 EN60079 31 Standards applied EN 60079 0 2012 A11 2013 EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protectionto EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive ...

Page 10: ...er Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthemarket theequipment conforms with alltechnical andregulatory requirements oftheabovelisteddirectives regulations and standards This Declaration is issued under thesole responsibility ofthemanufacturer...

Page 11: ... Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIB T6 T4 Gb II 2D Ex tb IIIC T65 C T130 Db IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2...

Page 12: ... and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the market the equipment conforms with all technical and regulatory requirements of the above listed directives regulations and standards This Declaration is issued under the sole responsibility of the ma...

Reviews: