Area Classification Dust:

Zone 21

Explosive dust air mixture likely to occur in
normal operation.

Zone 22

Explosive dust air mixture not likely to occur, and
if it does, it will only exist for a short time.

IP Rating:

IP67

T100ºC Ta < +55ºC
T85ºC Ta < +40ºC

Equipment Category:

2G/D

Ambient Temperature Range:

-50

°

C to +55

°

C

(T6 = +40ºC)

6)

Beacon Location and Mounting

The location of the beacons should be made with due regard
to the area over which the warning signal must be visible.
They should only be fixed to services that can carry the
weight of the unit.

The beacons should be securely bolted to a suitable surface
using the 7mm diameter boltholes in the stainless steel U
shaped mounting bracket (see figure 1). The required angle
can be achieved by loosening the two large bracket screws in
the side of the unit, which allow adjustment of the beacon in
steps of 18

°

. On completion of the installation the two large

bracket adjustment screws on the side of the unit must be
fully tightened to ensure that the unit cannot move in service.

SAFETY WARNING:

The flashdome guard must not be removed from the unit
at any time.

7)

Access to the Flameproof Enclosure

In order to connect the electrical supply cables to the beacon
it is necessary to remove the flameproof cover to gain access
to the flameproof chamber. To achieve this remove the four
M6 hexagon socket head screws (see figure 2) and withdraw
the flameproof cover taking extreme care not to damage the
flameproof joints in the process.

Note the four

M6 screws are Class A4-80 stainless steel

and only screws of this category can be used on the

beacons.

It is therefore important that these screws and their

spring washers are kept in a safe place during installation.

On completion of the cable wiring installation the flameproof
joints should be inspected to ensure that they are clean and
that they have not been damaged during installation. Also
check that the earth bonding wire between the two casting
sections is secure and the ‘O’ ring seal is in place. When
replacing the flameproof cover casting ensure that it is square
with the flameproof

chamber casting before inserting.

Carefully push the cover in place allowing time for the air to
be expelled. Only after the cover is fully in place should the
four M6 Stainless Steel A4-80 cover bolts and their spring
washer be inserted and tightened down. If the cover jams
while it is being inserted, carefully remove it and try again.
Never use the cover bolts to force the cover into position.

8)

Power Supply Selection

It is important that a suitable power supply is used to run the
beacons. The power supply selected must have the
necessary capacity to provide the input current to all of the
beacons

The following table shows the input current taken by the
various beacons:-

Unit Type

Nominal I/P

Input

Max.

Voltage

Current

I/P

Volts

BExBG05D

12V DC

750mA

15V

BExBG05D

24V DC

300mA

30V

BExBG05D

48V DC

180mA

58V

BExBG05D

230V AC

55mA

253V

BExBG05D

115V AC

140mA

126V

The input current will vary according to the voltage input
level. The current levels shown above are for nominal input
voltage. The 12V, 24V and 48V DC units have a converter
circuit and therefore the input current level will decrease
slightly as the input voltage in increased and will increase
slightly as the input voltage is reduced.

The above table also shows the maximum voltages at which
the beacons can be operated.

Flashdome
Guard

Flameproof
Chamber

Flameproof
Cover

S/S Bracket

Figure 1

4 off M6 Cover Screws

External Earth
Terminal

Figure 2