European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e-2-s.com              Fax: +44 (0)208 740 4200 
Document No. D210-00-011-IS 

Issue 5        20-04-2020                         Sheet 1 of 8

 

                                                                                              

  

INSTRUCTION MANUAL (ATEX / IECEx) 

BExS120D and BExS120D-R Flameproof Sounders

 

For use in Flammable Gas and Dust Atmospheres

 

 

 

 

 

 

 

 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGIZED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD 

– CLEAN ONLY WITH A DAMP 

CLOTH 

 COVER BOLTS CLASS A4-80 

 USE HEAT RESISTING CABLES AND CABLE 

GLANDS (RATED 110°C) AT AMB. 
TEMPERATURES OVER 40°C 

 

2)  Rating & Marking Information 

 

All  units  have  a  rating  label,  which  carries  the  following 
important information: - 

 

Model No.:

  

BExS120D or BExS120D-R 

 

Input Voltage:

     DC Units    12V or 24V or 48V 

              AC Units    115V or 230V 

 

BExS120D or BExS120D-R Codes:  

Ex db IIC T4 Gb Ta. -50°C to +55°C  
Ex db IIB T4 Gb Ta. -50°C to +70°C 
Ex tb IIIC T100°C Db Ta. -50°C to +55°C 
Ex tb IIIC T115°C Db Ta. -50°C to +70°C  

 

Certificate No.

     KEMA 99ATEX6312X 

 

 

IECEx KEM 10.0003X  

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

The units can be installed in locations with the following 
conditions: 

 

Area Classification Gas: 

Zone 1 

Explosive  gas  air  mixture  likely  to  occur  in 
normal operation. 

Zone 2 

Explosive  gas  atmosphere  not  likely  to 
occur  in  normal  operation  but  may  be 
present for short periods. 

 

Gas Groupings: 

Group IIA 

Propane 

Group IIB 

Ethylene 

Group IIC 

Hydrogen and Acetylene (up to 55°C 
ambient)   

 

Temperature Classification: 

T1 

450ºC  

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

 

Area Classification Dust: 

Zone 21 

Explosive dust air mixture likely to occur in 
normal operation. 

Zone 22 

Explosive  dust  air  mixture  not  likely  to 
occur in normal operation, and if it does, it 
will only exist for a short time. 

 

Dust Groupings: 

Group IIIA 

Combustible Dusts 

Group IIIB 

Non-Conductive Dust 

Group IIIC 

Conductive Dust 

 

Maximum Surface Temperature for Dust Applications: 

100ºC at +55 ºC ambient 
115 ºC at +70 ºC ambient 

 

IP Rating:  

IP66/67 to EN/IEC60529 and IP6X to 
EN/IEC60079-0, EN/IEC60079-31 

 

Equipment Category:

 

2G / 2D 

 

Equipment Protection Level:

 

Gb / Db 

 

Ambient Temperature Range:

 

-50°C to +55°C Gas Groups IIA, IIB and IIC 
-50°C to +70°C Gas Groups IIA and IIB 
-50°C to +70°C Dust Groups IIIA, IIIB and IIIC 

2813 

II 2G 
II 2D 

Epsilon x 
Equipment Group and 
Category: 

CE Marking 
Notified Body No. 

BExS120D 

BExS120D-R 

Summary of Contents for BE S120D Series

Page 1: ...C Certificate No KEMA 99ATEX6312X IECEx KEM 10 0003X The units can be installed in locations with the following conditions Area Classification Gas Zone 1 Explosive gas air mixture likely to occur in...

Page 2: ...and Mounting The location of the sounder should be made with due regard to the area over which the warning signal must be visible They should only be fixed to services that can carry the weight of the...

Page 3: ...o NPT M20 to M25 It is important to note that stopping plugs cannot be fitted onto adapters only directly onto the M20 entries Any other adapters used must be suitably rated and ATEX IECEx certified a...

Page 4: ...eration Simply connect the supply voltage to the L and N supply terminals see fig 4 12 2 2 AC Units Second Third Stage Tone Selection To select the second third and fourth stage tones on the BExS110 A...

Page 5: ...ve the facility to use either ve or ve switching to change the tone to the second and third stages Negative switching is the default setting For ve switching connect the two headers on the pcb to the...

Page 6: ...e set by adjusting the volume control potentiometer see Fig 9 For maximum output set the potentiometer fully clockwise BExS120D AC BExS120D DC Fig 9 Location of Volume Control Potentiometer 15 Mainten...

Page 7: ...1 0 Tone 31 Tone 1 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 Tone 4 Tone 5 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 Tone 15 Tone 5 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 Tone 4 Tone 5 15...

Page 8: ...7 112 8 113 1 116 7 119 2 119 8 112 9 112 3 3 500 1200Hz 0 3Hz 0 5 Sec Slow Whoop 114 5 115 9 119 8 119 9 114 8 113 5 113 9 115 7 119 5 119 7 114 7 113 1 9 1200 500Hz 1Hz DIN PFEER P T A P 114 5 115...

Reviews: