background image

 

 

 

European Safety Systems Ltd.

  

Impress House, Mansell Road, Acton, London W3 7QH    

 

 

[email protected]

     Tel: +44 (0)208 743 8880 

                                                                                                                                                        

www.e2s.com

    Fax: +44 (0)208 740 4200 

Document No. D165-00-001-IS_Issue_4    16-11-22 
 

Sheet 2 of 10 

Always de-energize unit before removing cover. 
The  installation  of  the  units  must  be  in 
accordance  with  any  local  codes  that  may  apply 
and  should  only  be  carried  out  by  a  competent 
trained electrical engineer. 
The  power  terminals  on  the  control  unit  are 
clearly  marked  and  will  accept  up  to  1.5mm

2

 

cable.

 

 
 

 

 

 

DC Terminals  
On main PCB. 

 

 

 

++ = Positive 

 

 

 

- -  = Negative 

 
 
 

AC Terminals 
On Sub PCB 
L = Live 
N = Neutral 
E = Earth 

 

The  AL105N  units  will  have  the  beacon  already 
prewired to the unit so no extra wiring is required. 
 
 

4)  Beacon Set-up 

The beacon unit may need to be configured 
dependant on the type of flash required. 
 
The xenon beacon has a 1Hz flash rate only. 
 
The LED beacon is set as standard to the 2Hz 
flash mode but it can be set to a steady on mode 
also. To alter the settings, change the position of 
the header pin as shown. 

 

Remove header for steady mode. 

 

Keep header in standard position for 
2Hz flashing mode 

 

 
 
 

5)  Unit Set-up and Recording 

The unit will need to be configured to suit the end 
user. 
If recording either via the onboard microphone or 
the in-line connector the unit will need to be 
supplied with power.  
DC units can be powered when completing 
recording and set-up. 

Warning! : During set-up AC units must be 
temporarily powered from either a 12V battery 
or a separate 10-30VDC isolated power supply, 
connected directly to the DC terminals on the 
main appello PCB. This is because  the AC 
units power supply is not isolated and there 
may be a risk of electric shock. 
 

See section 7) Appello Setup Guide overleaf for 
Set-up instructions and functions. 

 
 

6)  Tone Selection Table 

The  Appello  unit  has  45  different  tones  (See 
Table  1)  that  can  be  selected  for  the  first  stage 
alarm.  The  systems  can  then  be  switched  to 
sound second, third and fourth stage alarm tones. 
The  tones  are  selected  by  operation  of  a  DIP 
switch S4 on the main PCB. 
 
The  tone  table  (Table  1)  shows  the  switch 
positions  for  the  45  tones  and  which  tones  are 
available for the second third and fourth stages. 
 
 

Example 
 
S4 Dip Switch -  
Shown Set for Tone 1  

(All switches OFF) 
 
 
 
To  sound  stage  one  simply  connect  the  supply 
voltage  (+ve  and 

–ve)  for  DC  units  and  (L,  N,  E) 

for  AC  units,  to  the  supply  input  terminals  on  the 
correct PCB shown. 
 
 

 

 

E

 

S2 

S3 

S4

 

Summary of Contents for APPELLO A105NAX

Page 1: ...The Beacon functions are either Xenon Strobe 1Hz flash rate LED Either Steady or 2Hz blink rate 2 Operating and Marking All units have the following operating requirements and limitations Unit Type No...

Page 2: ...mode 5 Unit Set up and Recording The unit will need to be configured to suit the end user If recording either via the onboard microphone or the in line connector the unit will need to be supplied with...

Page 3: ...erwise the unit will be damaged To change to the second third or fourth stage tone link the ve supply line to terminal relevant stage terminal Ie for Stage 2 link the ve supply to the S2 terminal for...

Page 4: ...llo unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or...

Page 5: ...tage 3 Switch 2 Off Switch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Pla...

Page 6: ...3 Set Switch S2 positions 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Swit...

Page 7: ...16 11 22 Sheet 7 of 10 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stag...

Page 8: ...4200 Document No D165 00 001 IS_Issue_4 16 11 22 Sheet 8 of 10 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper J4 ME to ON position centre and right pin conne...

Page 9: ...mper J6 to Sync on Set jumper J5 S M on Master unit to master position on Set jumper J5 S M on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power...

Page 10: ...ne 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 s...