THERMOSTAT AND ACCESSORY WIRING DIAGRAMS
DIGITAL TANK THERMOSTAT WIRING
This Ambient Air Limit Thermostat temporarily disables compressor operation when the return (entering) air temperature is above or
below the normal operating temperature range. The return (entering) air temperature operating range for the HPWH is 50°F to 95°F
(10°C to 35°C).
The heating stage set point is factor set at 95°F (35°C).
When the High Ambient Kit accessory is installed to allow operation at return (entering) air temperatures above 95°F
37
Figure 1
5
REMOTE TANK
TEMPERATURE
SENSOR
REMOTE AIR
TEMPERATURE
SENSOR
RANCO DIGITAL THERMOSTAT
PART # ETC 212000-000
24V COM
NC NO C
NC C NO
DIGITAL TANK THERMOSTAT
FULL GAUGE - MODEL MT511Ri
NOTE:
TANK TEMPERATURE
SETTING MUST NOT
EXCEED 140°F (60°C)
C
NO NC
12
11
10
9
8
7
6
5
4
3
2
1
OUTPUT
(24 VAC COM)
(24 VAC HOT)
HPWH
TERMINAL
STRIP
AMBIENT AIR
LIMIT THERMOSTAT
OUTPUT 1
OUTPUT 2
AMBIENT AIR LIMIT THERMOSTAT
CONFIGURATION NOTES:
1) Configure stage 1 for cooling.
2) Configure stage 2 for heating.
3) Set cooling set point at 50°F
4) *Set heating set point 95°F
5) Set cooling differential to 10°F
6) Set heating differential to 5°F
7) Locate remote air temperature
sensor near return (entering) air
connection or inside return air
ducting near unit.
* When High Ambient Air Kit is installed
adjust heating set point to 120°F
Summary of Contents for WH-35
Page 2: ......
Page 32: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC SINGLE PHASE 60 HZ 32 ...
Page 33: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ WH 35 WH 55 and WH 75 only 33 ...
Page 34: ...UNIT WIRING DIAGRAMS FUSE SIZES 208 230 VAC THREE PHASE 60 HZ only 34 ...
Page 35: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ 35 ...
Page 36: ...UNIT WIRING DIAGRAMS FUSE SIZES 460 VAC THREE PHASE 60 HZ only 36 ...