DIP SWITCHES

Auxiliary dip switch controls are located behind front

panel, through an opening below the control panel.

To access, remove front panel. See Fig. 10.
Dip switches are accessible without opening the

control box. Unit must be powered

OFF

to

effectively change their status.

Dip Switches 

Fig. 19 – Dipswitch Location on Unit

Electric heat only (for Heat Pumps)

Wall Thermostat enable

Fan CON/CYC for heating

Fan CON/CYC for cooling

Setpoint Limit 1

Setpoint Limit 2

Freeze guard

Dipswitch

UP

Down

Fig. 20 – Dip Switches

Table 5—DIP SWITCH FUNCTIONS

No,

UP

DOWN

REMARKS

DEFAULT

1

Electric Heat Only

Heat Pump

For Heat Pump unit only.

DOWN

2

Wall Thermostat Enable

Control Panel Enable

DOWN

3

Fan Continuous Run for Heating

Fan Cycle for Heat

DOWN

4

Fan Cycle for Cool

Fan Continuous Run for Cooling

DOWN

5*6

UP*UP

68---75

˚

F

20---24

˚

C

UP*DOWN

63---80

˚

F

18---28

˚

C

DOWN*UP

65---78

˚

F

19---26

˚

C

DOWN*DOWN

61---86

˚

F

16---30

˚

C

(full range)

Two configurations (5*6)

combine to select set point

range.

When set point limit set,

display always shows full

range.

DOWN*UP

65---78

˚

F

19---26

˚

C

7

Freeze Guard Disable

Freeze Guard Enable

DOWN

Electric Heating Only / Emergency Heat (For

Heat Pump Units Only)

This setting is typically used for Emergency Heating.

Wall Thermostat Enable

A wired wall thermostat can be connected to the unit.

If it is, this dipswitch must be moved to the Wall

Thermostat Enable Position, before the wall

thermostat will begin control.

Heat and Cool Fan CON/CYC Dip--switches

Allows the fan to operate in continuous or cycle

modes while the unit is in heating or cooling mode

(continuous or cycle):

CON

(Continuous)

Allows fan to run continuously, circulating air even when the

temperature setting has been satisfied. This switch helps to
maintain the room temperature closer to the thermostat setting.

CYC

(Cycle)

This setting allows the fan to cycle on and off with the
compressor or electric heater. The fan stops a short time after

the temperature setting is satisfied.

Setpoint Temperature Limits

Provides a restricted range of temperature control.

Room Freeze Protection

If unit senses a room temperature below 40

˚

F

(4.4

˚

C), the fan motor and electric strip heat will turn

on and warm the room to 50

˚

F (10

˚

C). The fan stops

a short time after the temperature is satisfied.

NOTE: Configuration DIP switches are only read 

during a power up cycle.

See Table 5 – 

Dip Switch Functions

 for functions of 

each dip switch position.

Summary of Contents for GB Series

Page 1: ..._____________________________ Phone Number ________________________________ Technician Name _________________________________ _________________________________________________ NOTE TO EQUIPMENT OWNER Thank you for purchasing a Gree E TAC Please read this Owner s Information Manual carefully before installing and using this appliance Keep this manual for future reference For your convenience please...

Page 2: ...eve Preparation 8 8 Installation of Gree Wall Sleeve Using Non Gree Grille Install Unit Into Wall Sleeve 9 SYSTEM CONFIGURATION Ventilation Control 10 Adjusting Air Direction 10 Dipswitches 11 Keypad Configuration 12 AUXILIARY CONTROLS Wall Thermostat Terminal 14 Energy Management Input 14 Intelligent Self Checking Control 14 OPERATION 15 CARE AND CLEANING 16 PREVENTATIVE MAINTENANCE 17 TROUBLESHO...

Page 3: ...mmediately repair or replace all electric service cords that have become frayed or otherwise damaged Unplug or disconnect the unit at the fuse box or circuit breaker before making any repairs WARNING NOTE We strongly recommend that any servicing be performed by a qualified individual GENERAL BEFORE YOU BEGIN Read these instructions completely and carefully IMPORTANT Save these instructions for loc...

Page 4: ...ic defrost protection for heat pump models only When the outdoor temperature gets too cold approx 40 F 4 4 C and the unit can no longer effectively heat with the compressor the unit will automatically switch to electric heating The unit will then heat with electric heat until the outside temperature rises enough approx 40 F 4 4 C so the compressor can be used again Automatic Quick Warm up for heat...

Page 5: ...tselected See section on unit configuration for more details Energy Management Sometimes known as Front Desk Control an input is provided so that the unit can be manually disabled from a different location If the unit detects 24vac on this input it will automatically turn itself off If no voltage is detected on the input the unit will run normally Wall Thermostat Control A wired wall thermostat ca...

Page 6: ...d through the service cord plug or through separate ground wire provided on hard wired units Be sure that the branch circuit or general purpose outlet is grounded VOLTAGE SUPPLY Check voltage supply at outlet For satisfactory results the voltage range must always be within the ranges found on the data information plate Cord connected Units for the standard 208 230 v units and be within reach of th...

Page 7: ...Metal Sleeve SLV149 Friedrich T Series Metal 11 1 2 292 1 mm Deep Wall Sleeve Standard Depth Wall Sleeve 16 X 42 X 133 4 in 406 4 X 1067 X 349 3 mm PXWS FR SLEEVE EXT accessory is required for retrofit into Friedrich T Series wall sleeves Minimum wall sleeve opening must be greater than 14 75 X 40 00 in 374 7 x 1016 mm These units can retrofit Carrier General Electric Amana Trane and Friedrich sle...

Page 8: ...or to performance loss and premature damage to major components CONDENSATE REMOVAL SYSTEM Gree s series has a new condensate water disposal system The outdoor fan prop has a built in slinger ring which draws condensate water and sprays it on the warm outdoor coil for evaporation Thus providing better disposal of excess condensate and improving unit operating efficiency It is normal and desirable t...

Page 9: ...al injury or death Chassis weighs up to 150 pounds 68 0 kg Seek help when lifting unit Lift unit by holding unit basepan WARNING UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Failure to remove shipping tape and screw will prevent fresh air vent door from opening and may result in damage to vent door cable CAUTION Fig 8 Shipping Tape Location...

Page 10: ...ciency Energy Tip Keep the vent control at CLOSE Room air will be filtered and circulated Fig 16 Ventilation Control Location ADJUSTING AIR DIRECTION To adjust air direction 1 Remove front panel See Fig 10 2 Remove louver screws that hold louver insert in place from back side of front panel See Fig 17 3 Turn louver insert and rotate 180 See Fig 18 4 Replace louver insert 5 Replace screws and front...

Page 11: ...le DOWN Electric Heating Only Emergency Heat For Heat Pump Units Only This setting is typically used for Emergency Heating Wall Thermostat Enable A wired wall thermostat can be connected to the unit If it is this dipswitch must be moved to the Wall Thermostat Enable Position before the wall thermostat will begin control Heat and Cool Fan CON CYC Dip switches Allows the fan to operate in continuous...

Page 12: ...g mode Not normally required Indoor Air Temperature Sensor Biasing for Heating mode Sometimes known as an anticipator the air temperature sensor bias is used to adjust the room air temperature reading when in heating mode Not normally required Indoor Temperature Display Changebetween showing setpoint only on thedisplay during heating and cooling modes SP or displaying room temperature during heati...

Page 13: ...ostat the unit will automatically switch over to electric heating R W Y O Gh Gl C Fig 22 Terminal Connector Removal and Replacement Install Thermostat Wiring 1 Check to be sure power to unit is disconnected 2 Pull terminal connector to remove NOTE Terminal connector can be removed and replaced to simplify thermostat wiring 3 Connect wires from the thermostat to terminals on unit terminal connector...

Page 14: ...der normal operation unit status indicator STATUS on main PCB light is steadily ON If there is a major problem the unit will shut down and display a diagnostic failure code on the unit s display If it is only a minor failure and unit is correcting the fault by itself the diagnostic code will be flashed on the status LED that can easily be seen when the front panel is removed see Fig 24 Failure STA...

Page 15: ...MODE OPERATION DRY 5 TIMER MODE Timer ON When the unit is ON the Timer ON function can be set Time setting range is 0 5 to 24 hours When the selected time is reached the unit will turn ON and operate according to system settings Timer OFF When the unit is OFF the Timer OFF function can be set Time setting range is 0 5 to 24 hours When the selected time is reached the unit will turn OFF Timer Setti...

Page 16: ... clean if necessary AIR FILTERS IMPORTANT TURN UNIT OFF BEFORE CLEANING UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not operate unit without filters in place If a filter becomes torn or damaged it should be replaced immediately Operating without filters in place or with damaged filters will allow dirt and dust to reach indoor coil and r...

Page 17: ...r coil with warm water and a mild detergent Do not use corrosive coil cleaners Never use high pressure spray on coils Clean basepan and outdoor vent filter Clean outdoor orifice and fan Clean indoor coil Never use high pressure spray on coils Clean indoor fan wire screen and front panel Clean or install new indoor air inlet filter s Clean wall sleeve and outdoor grille Inspect cord and receptacle ...

Page 18: ...ed comfort Wait approximately 3 minutes for compressor to start DISPLAY HAS STRANGE NUMBERS CHARACTERS ON IT The unit may be in a diagnostic condition Check Intelligent Self checking Control section to determine if unit has had a failure The unit may be set for C instead of F see the keypad configuration section UNIT MAKING NOISES Clicking gurgling and whooshing noises are normal during operation ...

Page 19: ...32 34 32 72 59 0 31 14 31 51 31 87 60 0 30 35 30 70 31 05 61 0 29 58 29 91 30 25 62 0 28 83 29 15 29 47 63 0 28 10 28 41 28 72 64 0 27 40 27 69 27 99 65 0 36 71 26 99 27 28 66 0 36 04 26 31 26 59 67 0 25 39 25 66 25 92 68 0 24 76 25 01 25 27 69 0 24 15 24 39 24 64 70 0 23 55 23 79 24 03 71 0 22 97 23 20 22 43 72 0 22 40 22 63 22 85 73 0 21 85 22 07 22 29 74 0 21 32 21 53 21 74 75 0 20 80 21 01 21 ...

Page 20: ...0 10 48 10 62 10 77 105 0 10 25 10 39 10 53 106 0 10 02 10 16 10 30 107 0 9 791 9 937 10 08 108 0 9 573 9 719 9 866 109 0 9 361 9 506 9 653 110 0 9 154 9 299 9 446 111 0 8 952 9 097 9 243 112 0 8 755 8 900 9 046 113 0 8 563 8 708 8 854 114 0 8 376 8 520 8 667 115 0 8 193 8 338 8 484 116 0 8 015 8 159 8 305 117 0 7 841 7 985 8 131 118 0 7 671 7 815 7 961 119 0 7 506 7 650 7 796 120 0 7 344 7 488 7 ...

Page 21: ...21 GB Series Typical Wiring Schematic for Standard Units Except Models with 5KW Elec Heaters ...

Page 22: ...22 GB Series Typical Wiring Schematic for Models with 5KW Elec Heaters ...

Page 23: ...s is the responsibility of the installer 5 Failure to start due to voltage conditions blown fuses open circuit breakers or any other damages due to the inadequacy or interruption of electrical services 6 Damage or repairs needed as consequence of any misapplication abuse unauthorized alteration improper servicing or operation 7 Damage as a result of floods winds fires lightning accidents corrosive...

Page 24: ...right 2012 Gree Electric Appliance Inc Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No PTAC ETAC 1S1 Printed in U S A Edition Date 01 12 66129908812 3 CONTACT THE DISTRIBUTOR SERVING YOUR AREA Your dealer can give you his name or you can consult your yellow pages 1 CHECK THE THINGS YOU CAN DO YOURSELF These include ...

Reviews: