ET DC BLUE ADVANCED INSTALLER 2012.025.12.05.2014
15
SAFETY OBSTRUCTION SENSING IN ACTION:
In the case of the door being resisted physically or obstructed while opening.
•
The motor will stop running,
•
The buzzer will beep once and operator reverts to standby mode.
•
On the next BT button trigger the motor will start closing the door.
In the case of the door being resisted physically or obstructed while closing.
•
The motor will stop running,
•
The buzzer will beep once as the motor immediately begins opening the door once again.
•
On reaching the open position the operator reverts to standby mode.
•
On the next BT button trigger the motor will begin the door closing.
SETTING THE OBSTRUCTION FORCE SENSING, SAFETY LEVEL.
Default level - 3
From Standby Mode
Action
Response
To enter the Program
menu. Press and hold SET
button until buzzer beeps
twice.
Display begins flashing “P”
and buzzer beeps twice
to confirm the main
program menu is active.
Scroll up with the UP
button until “F” flashes.
Display flashes “F” to
confirm safety force setup
mode is selected.
Press and release SET
button to enter safety
force setup.
Buzzer beeps once and
current safety force level
is displayed. (1-9)
Press and release the UP
or DOWN buttons to scroll
to the desired safety force
level. (1-9)
1 = most sensitive to
resistance in movement of
the door.
9 = least sensitive to
resistance in movement of
the door.
Press and release the SET
button to save the new
setting to memory and
exit back to the main
program menu.
The buzzer beeps once
and the display returns to
flashing “P”.
To
Scroll up or down
to next program
option.
OR
Press and release EXIT to
return to Standby mode.