background image

8

Field Joint Assembly Instructions

Parts included in Field Joint Kit: 

Identify all parts before proceeding 

with installation.

(16) 3/8-16 x 1-1/2 long screws

(16) 3/8-16 Elastic Stop Nuts

(32) Flat Washers

(1) Length Sealant (Sika) Tape 

(1) Hole Punch

(1) Vent Pipe Extension

1) Carefully clean and dry both 

accessway flanges with solvent. 

IMPORTANT: Sealing surfaces 

must be dry to ensure the 

sealant adheres correctly.

2)

 

Starting at one hole of tank 

flange, apply two layers of Sika 

Tape around the inside half of the 

flange. Align the outside edge of 

the tape with the bolt circle. Move 

to the adjacent hole and apply 

one layer of Sika Tape around 

the outside of the flange. Align 

inside of tape with the bolt circle. 

Remove the backing paper as you 

lay the adhesive on the flange. 

Do not stretch Sika tape during 

application; it may result in a 

leak.

 The tape should overlap at 

the end by approximately 1/2 inch, 

as shown in Fig. 5a. If a section 

of Sika Tape is misapplied, the 

bad section may be cut out and 

replaced. Cut away the poorly laid 

portion cleanly with a knife and be 

sure to over lap the tape at each 

end about 1/2 inch.

3) Using the tool provided, 

punch a hole through the tape at 

each of the 16 existing bolt holes 

in the flange. 

Be careful to keep 

the exposed sealant clean and 

dry.

4) Insert three of the sixteen 3/8-

16 x 1-1/2” long bolts, with a flat 

washer, into the flange attached to 

the upper part of the accessway. 

These will act as guides while 

aligning the bolt pattern of the two 

flanges. 

5) Support the upper accessway 

section a few inches over the 

tank, making sure to align the vent 

port in the lid with the vent pipe 

in the tank. Once aligned, lower 

the upper section onto the mating 

flange using the three bolts to 

guide it to the proper position. See 

Fig. 5b.

6) Insert the remaining 13 bolts 

with flat washers into the flanges. 

Place a flat washer and elastic 

stop nut on the end of each bolt, 

turning the nut on just enough to 

hold the washer in place.  

7) Tighten the bolts until the 

sealant begins to squeeze out 

from between the flanges. To 

ensure a consistent, sturdy seal, 

tighten them in the following 

sequence: 1, 9; 5, 13; 3, 11; 7, 15; 

2, 10; 4, 12; 6, 14; 8, 16.  Always 

be sure to tighten one bolt and 

then the bolt at the position 180° 

from it; see Fig. 1 for position 

numbers.

8) Using the same sequence as 

in Step 7, tighten each bolt to 60 

in-lbs. Visually inspect the joint, 

each bolt and each nut should 

have a flat washer between it and 

the flange, and a uniform amount 

of sealant should be protruding 

from the seam along the entire 

perimeter.

In the event that there are 

any voids in the sealant, the 

joint may leak. Take corrective 

actions if necessary and be 

sure that the joint is leak free 

before continuing.

9) 

In order to properly vent 

the station, apply PVC primer/

cement (not provided) and 

assemble the included sections 

of vent pipe by using the 

provided 2” PVC couplings. 

After the pipe sections have 

been assembled, ensure that 

the bottom end of the pipe 

is secured in the lower vent 

grommet, then slide the top 

end of the pipe through the 

receptacle on the bottom of the 

lid.

IT IS EXTREMELY IMPORTANT THAT THE JOINT IS SEALED PROPERLY BEFORE 

BACKFILLING. EXCAVATING A UNIT FOR REPAIR IS VERY EXPENSIVE AND CAN BE EASILY 

AVOIDED BY USING PROPER CAUTION DURING THE FOLLOWING PROCEDURE.

Figure 5a

Figure 5b

Summary of Contents for Extreme Series

Page 1: ...1 DH272 DR272 DH502 DR502 Typical Installation Instructions Warranty Information Duplex Stations 270 Gal 500 Gal Capacities...

Page 2: ...M grommet 4 5 ID For DWV pipe 8 WET WELL VENT 2 0 tank vent supplied by factory in units with accessways 9 GRAVITY SERVICE LINE 4 DWV 4 5 OD Supplied by others 9a STUB OUT 4 X 5 Long watertight stub o...

Page 3: ...3 FAILURE TO COMPLY WITH INSTALLATION INSTRUCTIONS WILL VOID WARRANTY SEAL CONDUIT PER NEC SECTION 300 5 300 7 Figure 1a...

Page 4: ...r level then the inlet the inlet must be sleeved with an 8 tube before pouring If your unit is a model taller than 93 it may be shipped in two sections requiring field assembly See Field Joint Assembl...

Page 5: ...The units are supplied with a vent pipe from the wetwell to the top of the accessway Failure to properly vent the tank will result in faulty operation and will void the warranty 7 ELECTRICAL CONNECTIO...

Page 6: ...de of the station reaching down into the burial depth Attach the small fiberglass guard protective shroud provided with the station to protect the exposed cable where it enters the station Four self t...

Page 7: ...T260 panels Reset is not required Protect Panel Turn pump and alarm breakers off and back on simultaneously Protect Plus Panels Perform a cold start from the Initialize System menu Any user setting th...

Page 8: ...tank making sure to align the vent port in the lid with the vent pipe in the tank Once aligned lower the upper section onto the mating flange using the three bolts to guide it to the proper position...

Page 9: ...t to be poured in place If the concrete anchor is to be poured while the station is in place lift the unit by securing straps to the eyebolts supplied on the lower flange as shown below Keep station o...

Page 10: ...onsulting engineer must revise the calculations as shown in this document Physical Constants 1 Density of Water 62 4 lb cu ft 2 Density of Concrete 150 lb cu ft in air 3 Density of Concrete 87 6 lb cu...

Page 11: ...e net buoyant force acting on the station Fnet buoyant is equal to the buoyant force Fbuoyant minus the weight of the grinder pump station Fnet buoyant 2870 4 lb 705 lb 2165 4 lb B Ballast Force 1 Det...

Page 12: ...Force Buoyant Force 5973 0 lb 2165 4 lb 3807 6 lb The approach outlined above may be used to calculate the ballast requirements listed below Chart 1 Station Height in Wetwell Volume cu ft FNet Buoyant...

Page 13: ...13...

Page 14: ...onsulting engineer must revise the calculations as shown in this document Physical Constants 1 Density of Water 62 4 lb cu ft 2 Density of Concrete 150 lb cu ft in air 3 Density of Concrete 87 6 lb cu...

Page 15: ...et buoyant force acting on the station Fnet buoyant is equal to the buoyant force Fbuoyant minus the weight of the grinder pump station Fnet buoyant 5697 1 lb 845 lb 4852 1 lb B Ballast Force 1 Determ...

Page 16: ...Buoyant Force 12606 0 lb 4852 1 lb 7753 9 lb The approach outlined above may be used to calculate the ballast requirements listed below Chart 2 Station Height in Wetwell Volume cu ft FNet Buoyant lb S...

Page 17: ...17...

Page 18: ...at grade discard existing welded on shroud and attached corrugations shroud is not to be reused Caution Be careful not to cut either the vent pipe or the pump breather cable 6b Clamped on shroud Remo...

Page 19: ...ension 18 Lube wet well vent grommet and vent pipe extension with pipe lube non grit hand cleaner or dish soap and slide vent pipe through grommet until tank shroud seats to accessway 19 Place SS band...

Page 20: ...20...

Page 21: ...21 Environment One Corporation 2773 Balltown Road Niskayuna New York 12309 1090 Voice 01 518 346 6161 Fax 518 346 6188 www eone com NA0064P01 Rev J 07 23 A Precision Castparts Company...

Page 22: ...Sanitary napkins or tampons Cigarette butts Caution Kitchen garbage disposals do not keep grease oil out of the plumbing system In addition you must never introduce into any sewer Explosives Strong c...

Page 23: ...provided the product is properly installed serviced and operated under normal conditions and according to manufacturer s instructions Repair or parts replacement required as a result of such defect wi...

Reviews: