Mounting/Handling/Maintenance

Transducers are measuring instruments and be handled carefully. Generally, external forces such as

impact, shock, bending, etc. should be avoided. The TK-101 does not require special maintenance
beyond the general inspection/function check of the electrical equipment. Due to its installation in a

housing, cleaning of the TK-101 is not required. If cleaning is necessary, however, cleaning of the
device is only allowed while no voltage is applied; use a dry cloth or a fine brush for the cleaning

process.

Technical Data 

See datasheet heading 14, 14-01-01

 

(

 

www.elb-bensheim.de

 )

 

Input

Resistance range in three-wire circuit

4…10 kΩ

Measured current

0.8 mA at R

E

 = 4 kΩ, 0.33 mA at R

E

 = 10 kΩ

Measured voltage

3.3 V

Supply/output

2-wire

4…20 mA

Voltage

11...28 VDC

Burden/load

0....800 Ω ( R

Burden

 max = [(U

m

 – U

m

 

min

) / 0,02] Ω )

Output signal if fault is detected

Max. 24 mA 

Environment

Operating temperature

-20...+60 °C

Storage temperature

-40...+80 °C

Influence of errors

Max. accumulated errors 

± 1%

Influence of temperature

-0.015% / °C

Effect of variation of supply voltage

0.025% / V

Offset (optional)

Full-scale amplitude

Approx. 60...105 %

Zero-offset elevation

Approx. 0…25 %

EMC standards

See conformity declaration

     

 Characteristic labeling

See EC-type examination certificate

 TÜV 02 ATEX 1795 X 

respectively 

IECEx TUN 17.0036X

Version 05/03/2018

Errors and changes reserved

Pages: 3of 3