User Manual HTP201 Humidity and Temperature Probe with Analogue Outputs

■ 

For outdoor applications the HTP201 shall be equipped with a radiation shield (HA010502) which 

provides protection from rain, snow and ice. This also causes a natural ventilation which largely 

prevents overheating of the probe in the sun and thus a distortion of the measured values. 

■ 

Best accuracy is achieved with a velocity of min. 0.2 m/s of the air surrounding the probe. Depending 

on the installation position, flow direction and flow velocity, the accuracy may decline. The following 

table gives a concise overview. Please note that the vertical positioning with the sensing element 

upside is the most sensitive one concerning accuracy. Because of possible self heating due to the 

sensor electronics, it is crucial to have the indicated air flow velocity.

Flow direction of medium

> 0.2 m/s

> 0.2 m/s

This type of mounting  

is not recommended

> 0.2 m/s

> 0.2 m/s

This type of mounting  

is not recommended

> 0.2 m/s

> 0.2 m/s

Tab. 1 

Mounting position, air velocity and accuracy

5  Maintenance and Service

HTP201 does not require any special maintenance, nevertheless for high accurate measurements 

especially over wide RH and T ranges it is recommended to calibrate the probe every 12 months. If 

needed, the enclosure or the sensing element may be cleaned as described below.

5.1  Cleaning

Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the probe. Do not use any 

solvents or abrasive cleaning agents.

In case of dusty, oily and polluted environment:

■ 

Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the probe. Do not use 

any solvents or abrasive cleaning agents.

■ 

The filter cap shall be replaced once in a while with an E+E original one (see below).

■ 

If needed, the sensing element of the humidity probe can be cleaned by the user (see cleaning 

instructions - 

www.epluse.com/cleaning-instructions

).

5.2  Filter Cap Replacement

In a dusty or polluted environment it might be necessary to replace the filter cap once in a while. In most 

of the cases, a clogged filter shows visible contamination or dirt. Longer response time of the humidity 

measurement also indicates a clogged filter cap. In such cases, replace the filter by a new, original one, 

see chapter 5.5 Spare Parts.

Procedure

■ 

Turn the filter cap counter-clockwise for removing it.

■ 

Install the new filter cap finger tight by turning it clockwise.

While replacing the filter cap take very good care to not touch or rub the sensing element.

Summary of Contents for HTP201

Page 1: ...BA_HTP201 v1 0 Modification rights reserved User Manual HTP201 Humidity and Temperature Probe with Analogue Outputs ...

Page 2: ... equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the in...

Page 3: ... 5 3 1 General 5 3 2 Dimensions 6 3 3 Electrical Connection 7 3 3 1 M1 Models RH T 7 3 3 2 M6 Models RH T passive 8 4 Installation 8 4 1 Wall and Ceiling Mount 8 4 2 Duct Mount 8 4 3 Recommendations for accurate Humidity and Temperature Measurement 8 5 Maintenance and Service 9 5 1 Cleaning 9 5 2 Filter Cap Replacement 9 5 3 Protection during Site Cleaning Operations 10 5 4 Repairs 10 5 5 Spare Pa...

Page 4: ...ection maintenance and commissioning shall be performed by qualified personnel only Use the HTP201 only as intended and observe all technical specifications Do not use HTP201 in explosive atmosphere or for measurement of aggressive gases 1 2 2 Intended Use The HTP201 is intended for highly accurate and cost effective humidity RH and temperature T measurement in demanding process applications The R...

Page 5: ...ocess Service operations other than described in this user manual may only be performed by the manufacturer Disclaimer of Liability The manufacturer or their delegated representative is only liable in case of intent or gross negligence The accountability is limited to the value of the order issued at the time to the manufacturer The manufacturer is not liable for damages originated from disregardi...

Page 6: ... 4 M12x1 11 0 43 12 0 5 106 4 2 12 0 5 34 1 3 Current versions With connector Type E9 With cable Type E8 131 5 2 12 0 5 34 1 3 12 0 5 34 1 3 127 5 M12x1 11 0 43 Fig 1 Dimensions of HTP201 in mm inch 44 1 73 Ø5 Ø0 2 20 0 79 20 0 79 1 5 0 06 122 4 8 44 1 73 Ø105 Ø4 13 174 6 85 94 3 7 Fig 2 Dimensions of optional radiation shield ordering code HA010502 in mm inch ...

Page 7: ... 3 1 M1 Models RH T Voltage versions A1 A2 A3 With connector HTP201 M1xE9x Pin number Function 1 Supply voltage V 2 RH 3 GND 4 T M12 device plug front view 1 2 3 4 With cable HTP201 M1xE8x Supply voltage according to technical data V white GND brown RH green T yellow V V Current version A6 With connector HTP201 M1A6xE9 Pin number Function 1 Supply voltage V 2 RH 3 not connected 4 T M12 device plug...

Page 8: ...ng on the connection cable Fig 3 Optional wall and ceiling mount ordering code HA010211 4 2 Duct Mount The probe also can be installed into a duct using the plastic flange HA010214 or the stainless steel flange HA010201 not included in the scope of supply see data sheet Accessories Fig 4 Optional plastic flange ordering code HA010214 Fig 5 Optional stainless steel flange ordering code HA010201 4 3...

Page 9: ...surements especially over wide RH and T ranges it is recommended to calibrate the probe every 12 months If needed the enclosure or the sensing element may be cleaned as described below 5 1 Cleaning Use a damp soft cloth to remove deposits of dust or dirt from the exterior of the probe Do not use any solvents or abrasive cleaning agents In case of dusty oily and polluted environment Use a damp soft...

Page 10: ...cturer only The attempt of unauthorized repair excludes any warranty claims 5 5 Spare Parts Description Order code Filter caps for probes with Ø12 mm Please refer to the datasheet Accessories 6 Accessories For further information see datasheet Accessories General Order code M12x1 connector 4 pole socket for self assembly HA010707 Connection cable 5 pole M12x1 plug socket shielded 2 m 6 6 ft 5 m 16...

Page 11: ...y of the factory calibration with an enhancement factor k 2 2 times standard deviation The accuracy was calculated in accordance with EA 4 02 and with regard to GUM Guide to the Expression of Uncertainty in Measurement Temperature T Measuring range 40 80 C 40 176 F Accuracy Incl hysteresis non linearity and repeatability 0 5 0 6 0 4 0 3 0 2 0 1 T C T C Outputs Analogue RH 0 100 T 40 60 80 C see or...

Page 12: ...e 1 5 m 4 9 ft 3 m 9 8 ft 5 m 16 4 ft PVC Ø4 3 mm 4 x 0 25 mm2 for RH T with voltage output Ø4 3 mm 3 x 0 25 mm2 for RH T with current output Ø4 8 mm 6 x 0 14 mm2 for RH T passive with current output Storage conditions 40 80 C 40 176 F 0 95 RH non condensing Material Enclosure Probe cable cable versions Polycarbonate PC or stainless steel 1 4404 Polyvinyl chloride PVC Protection rating IP65 Electr...

Page 13: ...epluse fr E E Elektronik Germany Obere Zeil 2 61440 Oberursel Tel 49 6171 69411 0 E mail info epluse de E E Elektronik India 801 Sakhi Vihar Road 400072 Mumbai Tel 91 990 440 5400 E mail info in epluse com E E Elektronik Italy Via Alghero 17 19 20128 Milano MI Tel 39 02 2707 86 36 E mail info epluse it E E Elektronik Korea Suite 2001 Heungdeok IT Valley Towerdong 13 Heungdeok 1 ro Giheung gu 16954...

Reviews: