22
US-Unit
Analogue output
[0...10 V / 0(4)...20 mA]
from
to
unit
low
(L1)
high
(H1)
Standardized
DN40:
0
260 520 SCFM
volumetric
flow DN50:
0 410
820
SCFM
DN65:
0
820
SCFM
DN80:
0
820
SCFM
Mass
flow
DN40:
0 570
1140
kg/h
DN50:
0 890
1780
kg/h
DN65:
0
1780
kg/h
DN80:
0
1780
kg/h
Standardized
flow
DN40/50
0
19685
39370
SFPM
DN65
0
23081
SFPM
DN80
0
15238
SFPM
Temperature
all
Ø -4
176
176
°F
Switching output
[switching point/hysteresis]
Standardized
DN40:
210/21 420/42 SCFM
volumetric
flow DN50:
330/33
660/66
SCFM
DN65:
660/66
SCFM
DN80:
660/66
SCFM
Mass
flow
DN40:
460/46
920/92
kg/h
DN50:
700/70
1400/140
kg/h
DN65:
1400/140
kg/h
DN80:
1400/140
kg/h
Standardized flow
DN40/50
15000/1500
30000/3000
SFPM
DN65
15000/1500
SFPM
DN80
10000/1000
SFPM
Temperature
all
Ø 90/9
150/15
°F
Pulse output
pulse value = 1CF
pulse duration = 0.1 s
CONFIGURATION SOFTWARE
LIMITED LIABILITY
E+E Elektronik shall not be held liable for any damages or consequential damages (for example, but not
restricted to, loss of earnings, interruption of business, loss of information and data or any other financial
losses) resulting from the installation, use or impossibility of use of an E+E Elektronik software product and
any associated support services or non-performance of support services.
1.
General
The configuration software can be downloaded free of charge at
The configuration software, allows for a user-friendly adaptation of the flow meter to the application. In addi-
tion, the measurement values for flow and temperature can be calibrated / adjusted.
The system requirements for the installation and execution of the software are:
•
Windows XP with SP3, Windows Vista or Windows 7
•
.NET framework 3.5 with SP1
•
USB 2.0 interface
During setup there will be no installation of .NET Framework 3.5 SP1 – if the required version is not already
installed on the computer the following error message will appear at the start of the configuration software.
.NET Framework 3.5 SP1 can be installed using Windows Update.