QUICK GUIDE

EE211 - Humidity and Temperature Sensor for Continuous High Humidity

(Full User Guide at www.epluse.com/EE211)

Assembly and Installation

• 

Insert the M20 cable gland included in the scope of supply into the corresponding opening of the EE211 basis unit and fix it tight 

with the nut. 

• 

Install the EE07-MT temperature probe either directly onto the M12 connector of the EE211 basis unit or using the optional 

probe cable.

Connection Diagram

EE211-M1J3 - Digital Output

EE211-M1A2/3/5/6 - Analogue Output

Address switches

Modbus RTU

15...35 V DC 

 

24 V AC ± 20%

OUT1

OUT2

V

mA

V

mA

15...35 V DC 

 

24 V AC ± 20%

Output:   0...5 V  

 

 0...10 V

 

 0...20 mA

 

 4...20 mA

Output:

Bus termination resistor 120 Ω (jumper)

Selection output signal U / I

Setup interface

Analogue Settings

Selection Output Signal Voltage / Current

The factory setup of the output signal and scaling corresponds to the type number as ordered.

The output signal voltage (U) or current 3-wire (I) can be selected with the DIP switch on the main electronics board (see 

Connection Diagram - EE211-M1A2/3/5/6). This does not impact on the scaling of the outputs, which can be changed using the 

EE-PCS Product Configuration Software and the optional USB configuration adapter HA011066.

Digital Settings - RS485 Interface with Modbus RTU Protocol

Hardware Bus Termination

If required, the bus termination shall be realized with 120 Ohm resistor, jumper on the board.

Jumper mounted 

= bus terminated

Jumper not mounted  = bus not terminated

Address Switch:

Address setting via EE-PCS Product Configuration Software

All DIP switches at position 0 → address has to be set via

 

Product Configuration Software

Factory setting: 239 (permitted values: 1…247).

Example: Slave address is set via configuration software.

Address setting via DIP switch

Setting the DIP switches to any other address than 0, 

 

overrules the slave address set via configuration software  

(permitted values: 1…247).

Example: Slave address set to 11 (= 0000 1011 binary).

0 0 0 0 0 0 0 0

0
1

1 1 0 1 0 0 0 0

0
1

Address Switch:

For details how to set the ID address, baud rate, parity and stop bits, please see 

Full User Guide at www.epluse.com/EE211

.

Digital Settings

Factory settings

Selectable values

Baud rate

9600

9600, 19200, 38400, 57600, 76800, 115200

Data bits

8

8

Parity

EVEN

None, odd, even

Stop bits

1

1 or 2

Slave address

239

1...247