background image

until pushbutton is released. When released, motor will 
stop operating. 

NOTE: 

Blinds control function is always enabled, though room 

is unoccupied.

 Lowering Blinds down (IN4 in Option 2 and Option 4)

This input is used to manually control blinds closing or lowering 
down, with the herein operating scheme: 

 

-  While motor being stopped, by pressing button shortly 

(less than 1 second), motor will lower down to the default 
value

 

- While motor is moving (raising up or lowering down), 

motor will stop by pressing button shortly (less than 1 
second).

 

- While motor being stopped, by pressing button long 

(more than 1 second), lowering motor will activate while 
pushbutton will be pushed. When release the button, 
motor will stop operating.

 

- If pushbutton is long pressed (more than 1 second) while 

lowering motor is activate, the motor keep activate until 
releasing the pushbutton. When released, motor will stop 
operating.

 

- If pushbutton is long pressed (more than 1 second)  while 

raising motor is activate, raising motor will stop and after 
1 second will automatically activate lowering motor until 
pushbutton is released. When released, motor will stop 
operating.

NOTE

: Blinds control function is always enabled, though room 

is unoccupied.

Motion sensor (IN1 in Option 3) and Door contact (IN3 in 
Option 3)

Occupancy room state detected by motion sensor is determined 
by two sensors: 

 

- Motion Sensor

 

- Door contact input

Inputs can be on diff erent states:  

Input

Possible states

Input state

IN1

No motion detection

Open (NO)

Input

Possible states

Input state

IN1

Motion detection

Closed

IN3

Door closed

Closed (NC)

IN3

Door open

Open

System detection is described herein:

1) Change room state between Unoccupied into Occupied:

In order to change the room state into occupied state, it must 
follow this sequence: 

 

- Open the door

 

- Close the door

 

- Motion detection --> Room changes into Occupied state

After closing the door, if motion is detected, controller changes 
room state into occupy.

 

- When room changes into Occupied state, pushbuttons are 

enabled in order the user can connect climate. 

2) Changes room state between Occupied into Unoccupied:
In order to change room state into unoccupied state, it must 
follow this sequence: 

 

- Open the door

 

- Close the door

 

- No motion detection --> Room changes into  

 

Unoccupied state after a preset time.

After closing the door, if NO motion is detected, controller 
counts the leaving time confi gured on parameter P7 and 
when time expires room changes into Unoccupied state

 

- When room changes into unoccupied state, climate can 

switch from one of both possible states depending on the 
parameter P6 set: La climatización se apaga (OFF)

•  Climate switches off  (OFF)

•  Climate switches to ECO state, establishing ECO Cool 

or Heat set-point depending on mode climate at that 
moment. 

 

- If room has been changed into unoccupied state and after 

that, any motion is detected, system enables again the 
device and room will be in Occupied state.

NOTE:

  This operating mode can interact with Courtesy lighting 

output (OUT1) and Lighting (OUT2). This operating is described 
on “Device outputs operating description” section.

Device inputs operation (continuation)

Device outputs operating description

Courtesy lighting (OUT1 in Option 1, Option 2 y Option 3)

This output is controlled by the room occupancy detection 

on the basis of Key card input (IN1) or Motion sensor (IN1) and 
Door contact (IN3), depending on the following scheme::

1) Occupancy detection by Keycard contact:

 

- Keycard insertion activates OUT1. After preset time on P8 

parameter, the output is automatically disabled.

 

- Removing keycard, output is automatically enabled. After 

preset time on P8 parameter, the output is automatically 
disabled.

2) Occupancy detection by Motion sensor and Door Contact:

 

- Opening the door activates OUT1. While door is open, 

lighting is switch on.

 

- Closing the door, device starts a preset time on P8 count-

down. After that time, output is automatically disabled.  

Lighting (OUT2)

1) Occupancy detection by Key Card contact:

 

- Keycard insertion activates OUT2

 

- Removing keycard, output will disable after the time for 

leaving room preset on P7 parameter. 

2) Occupancy detection by Motion sensor:

 

- Opening the door activates OUT2 if room is on unoccu-

pied state. 

 

- If closing the door room changes into occupied state, 

output will remain activate while room will be on occu-
pied state. 

 

- If closing the door room changes into unoccupied state, 

by closing the door it starts the countdown of leaving the 
room time preset on P7 parameter, after it output is swit-
ched off .

Zone 2 Valve actuator (OUT4 in Option 1 and Option 3)

This output is used to control a second climate zone. Ambient 

zone temperature is measured by the built in temperature sen-
sor or by an external temperature sensor connected to IN4. P29 
parameter sets the desirable temperature sensor.  

Activating and deactivating of climate, as well as set-point 

zone temperature depends on principal zone.

Zone climate control is performed with a 0,5ºC hysteresis

Raising curtain up (OUT3 in Option 2 y Option 4)

This output is used to control blinds opening or raising up, 

depending on the operating scheme defi ned on “Input Raising 
blinds up” section.

Throughout P26 parameter it can be confi gured the automati-

cally raising blinds up when room changes into Occupied state

Lowering blinds down (OUT4 in Option2 and Option4)

This output is used to control blinds closing or lowering down, 

depending on the operating scheme defi ned on “Input Lowe-
ring blinds down” section.

Throughout P25 parameter it can be confi gured the automa-

tically lowering blinds down when room changes into Unoccu-
pied state. 

INS1114507000-0 

 

 

 

 

             3

© 2014 e-Controls®

Summary of Contents for e-Room Panasonic Stand-Alone

Page 1: ...point temperature is used to limit maximum value on heat mode and minimum set point temperature is used to limit minimum value on cool mode Maximum minimum user set point temperatures are maximum and minimum values that user can set throughout the pushbuttons Maximum minimum real set point temperatures are maximum and minimum values that perform to the machine Real values override values which use...

Page 2: ...is enabled and can operate When window is opened climate system stops working leaving the room temporarily without climate The device screen displays an open window icon and disappear the AUTO or fan coil speeds icon just in case the device is in Device inputs operation MANUAL mode Climate zone number 2 controlled by valve actuator also deactivates while window is open When window is closed again ...

Page 3: ...int depending on mode climate at that moment If room has been changed into unoccupied state and after that any motion is detected system enables again the device and room will be in Occupied state NOTE This operating mode can interact with Courtesy lighting output OUT1 and Lighting OUT2 This operating is described on Device outputs operating description section Device inputs operation continuation...

Page 4: ...coil speed following the sequence I II III AUTO After speed III AUTO mode is selected again Set point temperature Set point temperature value increments or decrements until maximum and minimum limits configured on the device 5 seconds after the last press the device returns to resting state displaying ambient temperature or set point temperature depending on how it has been configured After 10 sec...

Page 5: ...speed indicator It indicates the fan coil speed between the possible selection LOW MED and HIGH and operating mode selected AUTO Manual Display description When some operating failure exists on the installation or the device display shows the alarm detected throughout a number and the alarm sign icon and the blinking red LED Device can show three possible types of alarms Operating alarm The corres...

Page 6: ...T4 Unit Indoor L1 Courtesy Lighting L2 Room Lighting C1 Contactor C1 Inputs Dry Contact Outputs Max 5A 250Vac contact Indoor Unit Neutral Phase Lighting Window 16 15 14 13 12 11 10 9 1 2 3 4 5 6 7 8 R1 R2 OUT2 e Room Panasonic Model Stand Alone Supply R1 R2 100mA IP20 Made in Spain www e controls es R 16 15 14 13 12 11 10 9 7 8 6 5 4 3 2 1 R1 R2 IN2 IN1 IN4 IN3 OUT1 OUT3 OUT4 Unit Indoor Up Down C...

Page 7: ... of electrical systems for household HBES and automation and control systems for buildings BACS EN 50491 3 2009 CE Conformity Low Voltage Directive LVD 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Standards Electrical safety EN 50491 3 2009 EN 50491 4 1 2012 Electromagnetic Compatibility EN 50491 5 1 2010 EN 50491 5 2 2010 Technical features e Room Panasonic Stand Alone white fra...

Reviews: