Document:
Date
Created By:
DCR#
LPN00266X01A0_A 2014-07-31
TMT 2014-285
INSTALLATION INSTRUCTIONS
LED High Bay Light Engine Module
www.e-conolight.com | 888.243.9445 | FAX: 262.504.5409
FIGURE 2
3. Slide hook into securely mounted customer supplied eye hanger
and return retainer spring to original position.
NOTE:
The luminaire should already be factory set for correct
balance. However, should you need to, the fixture may be
balanced by loosening the (2) hook adjustment retention screws
on the top of the housing and sliding the hook as necessary for
correct balance. Tighten (2) hook adjustment retention screws
when finished. See
Figure 2 on back page.
For conduit entering the hinge splice box from the side:
Use appropriately-sized threaded conduit (1/2” or 3/4”), along with
two locknuts (one for inside the hinge box and one for outside the
hinge box).
For cord and plug accessory:
Insert strain relief and cord wires into side 1/2” knockout.
NOTE:
For connecting the flexible cord to the wiring box for branch
supply, suitable Listed cord connector of the involved cord size and
standard conduit opening shall be used in order to maintain strain
relief.
3. Attach one end of the hinged splice box to luminaire by aligning
hinge slots on Mounting Bracket with hinges (on splice box), and
then inserting the hinges into the slots.
4. Make the following wire connections and then push the leads into
hinged splice box:
• Connect supply ground to luminaire ground (green).
• Connect supply common to luminaire neutral (white)
lead.
• Connect supply black to luminaire black (line).
5. Secure other end of the hinged splice box to luminaire by sliding
screw on Mounting Bracket up and over in “L” channel on the
hinged splice box. See
Figure 1.
6. Secure luminaire to hinged splice box by tightening screw
7. If installing with optional cord and plug, locate the plug and
connect to the proper socket according to the plug.
Luminaire Hook
(2) Hook
Adjustment
Retention
Screws
Retainer Spring
REFLECTOR INSTALLATION
NOTE:
Products with prismatic reflectors are not intended for use in
environments containing airborne corrosive agents such as chemical
solvents, cleaners, or cutting fluids.
1. Loosen the (3) screws on the bottom of the luminaire, shown in
Figure 3
, at least 0.1 inch.
2.
Bring reflector up to housing and line up the (3) screws from Step
1, with the keyhole slots on the reflector.
3.
Rotate reflector, turn clockwise and tighten the (3) screws from
Step 1
NOTE:
Lens is attached the same to the each version of the reflector,
Prismatic and Aluminum, as described below. Prismatic Reflector is
shown in the figure for illustration purposes.
1.
With reflector attached to light engine module, secure lens to
reflector with the four spring latches attached to the lens. See
Figure 4.
Loosen
Screws
FIGURE 3
Reflector
(4) Spring
Latches
FIGURE 4
ATTACHING LENS TO REFLECTOR