ECOMPACT Slim
Page 23
© Wood Energy Solutions
woodenergysolutions.co.uk
Before we can carry out the auger calibration we must temporarily disconnect the boiler door
switch as we will have the boiler door open during this procedure. This can be done by turning off
all electrical power to the boiler and removing the cover from the control board. Undo connections
57/58 and a link wire or ‘jumper’ between these connections.
Once the door switch has bee disconnected and the
hopper has been filled with fuel the auger will need
to be primed. This is accessed through the :
User Menu > Load function
When this function is activated the slide plate
mechanism must open first (usually about 30
seconds), before the main feed auger starts to turn.
Wait until pellets can be heard dropping into the
burner then continue to allow pellets to feed into
the burner for a further 30 seconds. Pressing the
ESC key (P1) will stop the Load function. The burner
auger will continue to run for 30 seconds to push
the fuel in the burner onto the grate.
Clear the fuel from the grate and remove the grate
from the burner. The system is now ready to check
the calibration of the auger.
Commissioning