11
Figure 11
- Vertical Flue Assembly Type
5m
3m
Chimney Lenght Setting Definitions:
Depending on the flue lenght configuration there is a parameter defined to control fan speed to have the
best efficiency and emmission values of combustun. As the installation completed, this parameter must be set
by an authorized service technician at start-up. This setting is needed only for the start-up of gas water heater,
changing chimney lenghts of installation and changing the electronic board.
Product
Elbow
L (m)
Lmax (m)
P
11 P
arameter
Setting value
PH
OE
N
IX
P
H
HM
11
1x90
⁰
≤ 1
4
4
1x90
⁰
1< ≤ 2
1x90
⁰
2< ≤ 3
1x90
⁰
3< ≤ 4
2x90
⁰
≤ 1
3
3
2x90
⁰
1< ≤ 2
2x90
⁰
2< ≤ 3
3x90
⁰
≤ 1
2
2
3x90
⁰
1< ≤ 2
Table 3
Serviceman must save the flue lenght info. When switch on the power at first time,
"FA" symbol is seemed on the screen with fan icon. Serviceman can change the
flue lenght value by rotating the button. For saving the value, serviceman must push
the button and wait until blink fan icon.
Caution
: Any flue kit restrictor must not used.