24

WARNING

During the time the Legionella function is 

performed, there is a risk of scalding when opening the taps.

Legionella function

When the Legionella function is activated, the DHW storage tank temperature is periodically raised 

to the Legionella funct setpoint. The Legionella funct setpoint can be maintained during the set 

dwelling time.

Off

Function is deactivated.

Periodically

The Legionella function is repeated according to the period (Legionella funct

periodically 1641)). If the Legionella setpoint is attained via solar heating – independent

of the selected interval – the time period is started again.

This means that the heat source is switched on only if the solar plant was not able to

ensure the required Legionella funct setpoint within the set period of time.

Fixed weekday

(The Legionella function can be activated on a fixed Legionella funct weekday (1642)).

When using this setting, heating up to the Legionella setpoint takes place on the

selected weekday, independent of previous storage tank temperatures.

This setting is intended primarily for plant without solar integration.

Legionella function setpoint

The Legionella setpoint can be adjusted between 55 °C and 95 °C. When the Legionella function is 

activated, the DHW storage tank is heated up until the value set here is reached. For the Legionella 

function to be regarded as fulfilled, sensor B3 at the top or both sensors B3 and B31 must reach the 

Legionella  setpoint  which  must  be  maintained  for  the  set  dwelling  time,  depending  on  Type  of 

charging  (5022).The  higher  the  temperature  level  of  the  storage  tank,  the  shorter  the  required 

dwelling time at that level.The figures given in the table are guide values. They do not guarantee 

that legionella viruses will be completely killed.

Storage tank

temperature

Dwelling time

80 °C

70 °C

66 °C

60 °C

55 °C

50 °C

45 °C

A few seconds

1 minute

2 minutes

32 minutes

6 hours

No killing of viruses
Ideal conditions for viruses

Summary of Contents for FELIS Series

Page 1: ...FELIS WALL HUNG CONDENSING BOILER FELIS FL 50 65 100 125 150 HM INSTALLATION AND USER MANUAL...

Page 2: ......

Page 3: ...ProductFeatures 4 I Product Notation and Technical Dimensions 5 I Detailed Drawings and List of Components 6 I Technical Specification Table 9 I Packaging 11 11 17 I 17 I 19 I 19 I INSTALLATION and CO...

Page 4: ...tilizing your boiler s complete features and to use your appliance safely for a long time please read the manual carefully Please keep all the documents that come with your appliance for future refere...

Page 5: ...n using these chemicals please follow the instructions Any dirt blockages welding residuals burr flug etc particules left inside the pipes will affect the boiler s performance These residuals will cau...

Page 6: ...id underneath the appliance First startup of the appliance must be done by the authorized service Natural gas usage must be approved by the related gas company prior to the first startup The gas type...

Page 7: ...em that supports multiple languages with descrpitive menus White backlighted LCD screen shows information about working mode CH and DHW set points real time temperatures fault codes with descriptions...

Page 8: ...nection Lid Siphon Connection Lid Dimensions A B C D E F G H I Felis FL 50 HM DG 501 mm 835 mm 525 mm 145 mm 304 mm 80 125 mm 1 1 4 1 1 4 3 4 Felis FL 65 HM DG 501 mm 835 mm 590 mm 145 mm 304 mm 80 12...

Page 9: ...C TEMP SENSOR OUTLET 13 CONDENSATION HOSE 4 IGNITION TRANSFORMER 14 BOILER OUTLET PIPE HOT 5 HEAT EXCHANGER 15 BOILER INLET PIPE COLD 6 AIR PURGER 16 HEAT EXCHANGER HANGING BRACKET 7 FLUE GAS SENSOR 1...

Page 10: ...7 Felis 65 Figure 2b Felis 65 Detailed Drawings...

Page 11: ...8 Felis 100 125 150 Figure 2c Felis 100 125 150 Detailed Drawings...

Page 12: ...6 4 84 3 87 8 87 1 87 5 Efficiency 30 Output at Low Temperature Regime 1 97 2 97 5 97 4 97 1 97 2 Electrical Consumption at Full Load elmax Watt 75 115 139 226 297 Electrical Consumption at Part Load...

Page 13: ...Figure 3 Electronic Board Circuit Diagram 10 Electrical Board Circuit Diagram...

Page 14: ...ure It must be connected to a heating circuit suitable for its capacity and nominal output Felis boilers are suitable with flue types C13 x C33 x C43 x C63 x and C93 x therefore its flue system is sep...

Page 15: ...service maintenance and usage spaces required around the appliance is indicated in Figure 5 E C A Felis condensing boiler must be hung to a brick wall with the supplied hanging bracket For installatio...

Page 16: ...e water outlet to prevent the flue gas to leak into the surrounding air Galvanised and copper alloy parts should not be used in the pipes and connection parts all parts of condensate drain should be i...

Page 17: ...s gaskets should be mounted correctly to prevent flue gas leakage to the fresh air intake Horizontal flue kit must be installed with a 3 slope towards the appliance to keep the condansate water flowin...

Page 18: ...d d l Figure 7 Flue Types 15 I I I I...

Page 19: ...ostats can be used for heating control of the system Figure 8a Figure 8c E C A On Off Room Thermostat Wireless 7006907522 Wired 7006907519 Figure 8d Figure 8b E C A On Off Room Thermostat T6360 700690...

Page 20: ...of the appliance and system with its wide LCD screen and multi language support while allowing full control on the appliance Figure 9 Felis Control Panel and Buttons By pressing Info button user can s...

Page 21: ...n be manually reset from the reset button on the slave appliances For more information please refer to Cascading Applications section of this manual 18 Figure 11 User Interface for Slave Appliances Wi...

Page 22: ...time program and parameters 501 506 decides the times of the day for the heating to switch on and off You can see the arranged time program as a line chart in the bottom of the LCD screen TIME PROGRAM...

Page 23: ...ive Automatic summer winter changeover ECO functions and 24 hour heating limit inactive in the case of continuous operation with Comfort setpoint Continuous operation When using protection mode the he...

Page 24: ...wer outside temperatures If you can t achieve desired room temperature heating curve slope must be adjusted Increasing the slope increases water temperature in lower outside temperatures Decreasing th...

Page 25: ...rams After activating manual operation mode pressing Return button goes back to main screen When maintenance special operation symbol appears on the screen user can press Info button to change to the...

Page 26: ...the Frost Protection setpoint applies Time program 4 DHW When using this setting a specific time program is available for DHW heating For every weekday a time program with a maximum of 3 on phases ca...

Page 27: ...y 1642 When using this setting heating up to the Legionella setpoint takes place on the selected weekday independent of previous storage tank temperatures This setting is intended primarily for plant...

Page 28: ...tive in Automatic operation In the other operating modes they are started and run in the background to become active whenever Automatic operation is selected When a holiday period has elapsed the cont...

Page 29: ...consistencies occured during these controls will be shown as error and fault codes on the LCD screen and will be indicated with a bell sign on the upper left Some detailed information for the possible...

Page 30: ...27...

Page 31: ...28...

Page 32: ...29...

Page 33: ...30...

Page 34: ...ing any chemical substances Usage of chemicals like detergents etc could cause rust and scratches ALL RIGHTS RESERVED Our company reserves the right to make changes on the products installation and us...

Page 35: ...105 mm 235 mm 65 mm 240 mm 330 mm 435 mm 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 5 FLUE 80 125mm 1 2 3 4 2 1 3 4 145 mm 220 mm 5 5 FELIS 50 kW CIRCUIT AND FLUE CONNECTIONS 32...

Page 36: ...105 mm 260 mm 65 mm 240 mm 435 mm 445 mm 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW1 GAS 5 FLUE 80 125mm 1 2 3 4 2 1 3 4 145 mm 220 mm 5 5 33 FELIS 65 kW CIRCUIT AND FLUE CONNECTIONS...

Page 37: ...98 mm 130 mm 185 mm 290 mm 71 mm 93 mm 280 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 34 FELIS 100 kW CIRCUIT AND FLUE CONNECTIONS...

Page 38: ...98 mm 130 mm 185 mm 365 mm 71 mm 93 mm 280 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 35 FELIS 125 kW CIRCUIT AND FLUE CONNECTIONS...

Page 39: ...98 mm 210 mm 437 mm 71 mm 93 mm 270 mm 405 mm 145 mm 236 mm 1 2 3 4 5 5 1 2 4 3 1 SIPHON 2 CH RETURN 1 3 4 CH FLOW 1 GAS 1 5 FLUE 100 150mm 36 FELIS 150 kW CIRCUIT AND FLUE CONNECTIONS...

Page 40: ......

Page 41: ...37 INFORMATION ABOUT REGULATIONS EU 811 2013 AND EU 813 2013 FEL S FL 50 65 100 125 150 HM Product Fiches and Package Label Calculations...

Page 42: ...for installation assembly and maintanence are described in the installation and service manual Specific precautions for assembly installation and maintanence Rated heat output Prated Annual energy con...

Page 43: ...this fiche may not correspond to its actual energy efficiency once installed in a building as this efficiency is influenced by further factors such as heat loss in the distribution system and the dim...

Page 44: ...sup 1 2 II package without hot water storage tank II package with hot water storage tank 0 0 0 0 1 0 3 0 37 0 2 0 55 0 70 0 3 0 75 0 85 0 4 0 85 0 94 0 5 0 95 0 98 1 The intermediate values are calcul...

Page 45: ...61000 4 4 61000 4 5 61000 4 6 61000 4 11 A a da imzas bulunan irketimiz yukar da ad tipi ve modeli belirlenen cihazlar ekte yer alan B 18 05 2708 EU numaral rapor dahilinde ilgili standartlara AT Gaz...

Page 46: ......

Page 47: ...Gas Fueled Boiler E C A Serial No Delivery Place and Date Maximum Repair Period 2 0 Work Days Warranty Period 3 Years AUTHORIZED SERVICE Installation Date Date Signature and Stamp Phone Fax FREE INITI...

Page 48: ...Sanayi B lgesi 3 K s m Mustafa Kemal Bulvar No 13 45030 MANISA Mustafa Kemal Bulvar No 13 45030 MANISA TURKEY Tel 90 236 213 00 21 Tel 90 236 213 00 21 Fax 90 236 213 08 59 Fax 90 236 213 08 59 email...

Reviews: