POWERCUBE User Manual
10
the DIP switch of the slaves need to turn the “#4” to “ON”.
(7) The DIP switch of the slaves no need to be changed.
(8) If the energy storage system has only one B3, it is the host itself, and still follow the above
steps.
Note: For more information of matching inverter brands, please subject to the latest document
<The list of compatibility between Dyness ESS and Inverters >.
Caution
:
The DIP switch mode in case (5),1001 is only for ICC(a special commnunication
device of some no-communication inverter), it’s a specia firmware in BMS,different from general
firmware,so if customers want to use ICC,please contact dyness to confirm.
Note:
1.After the whole system connection,set the master DIP mode according to the inverter model
firstly,then start the battery.
2.The BAT-INV comms cable is from inverter comm port to master CAN IN port,BAT-BAT cable is
from master CAN OUT to slave1 CAN IN,slave1 CAN OUT to slave2 CAN IN.
DIP Switch mode 3
ADD: 0110
DIP Switch mode 1
ADD: 0010
DIP Switch mode 2
ADD: 0100
DIP Switch mode 6
ADD: 0000
DIP Switch mode 4
ADD: 1001
DIP Switch mode 5
ADD: 0001