HYDRAULIC GENERATORS
TECHNICAL SPECIFICATIONS
STANDARD MODELS 50HZ
HG 50
HG 50
HG 60
HG 70
OUTPUT CHARACTERISTICS
Output power max.
kVA
50
50
60
70
Output Voltage
V
230/400 VAC 230/400 VAC 230/400 VAC 230/400 VAC
Nominal Current *
1~phase / 3~phase
A
130,4 / 72,2
130,4 / 72,2
156,5 / 86,6
182,6 / 101,0
Frequency
Hz
50
50
50
50
Phase
1/3
1/3
1/3
1/3
IP
23
23
23
23
Voltage regulator
AVR
AVR
AVR
AVR
Sockets
(1 phase / 3 phase / cable K)
- / - / K
- / - / K
- / - / K
- / - / K
HYDRAULIC CONNECTION
Pressure line P
P
BSP 1”
BSP 1”
BSP 1”
BSP 1”
Return line T
T
BSP 1 1/4”
BSP 1 1/4”
BSP 1 1/4”
BSP 1 1/4”
Drain line D
D
M22x1,5
M22x1,5
M22x1,5
M22x1,5
HYDRAULIC POWER REQUIREMENTS
Flow min.
l/min
(gpm)
190 (50.2)
122 (32.2)
122 (32.2)
167 (44.1)
Flow max.
l/min
(gpm)
230 (60.7)
140 (36.9)
140 (36.9)
185 (48.8)
Pressure at nominal power output
bar
(psi)
160 (2300)
280 (4100)
320 (4600)
400 (5800)
Pressure max.
bar
(psi)
250 (3600)
420 (6100)
420 (6100)
420 (6100)
Pressure when unloaded
bar
(psi)
40 (580)
40 (580)
40 (580)
30 (440)
HYDRAULIC FLUID REQUIREMENTS
Viscosity
cSt
10-200 / optimum 25-35
Temperature
°C(°F)
max. 70 (158)**
Filter ratio
μm
25 or better
Cooling capacity requirements
***
kW
9,2
9,8
11,2
14
OVERALL DIMENSIONS
Length
mm
(in)
1250 (49.2)
1135 (44.7)
1147 (45.2)
1157 (45.6)
Width
mm
(in)
402 (15.8)
402 (15.8)
403 (15.9)
403 (15.9)
Height
mm
(in)
490 (19.3)
490 (19.3)
481 (18.9)
481 (18.9)
Weight
kg
(lbs)
249 (549)
249 (549)
280 (616)
290 (638)
Summary of Contents for HG 1
Page 2: ......
Page 71: ...DYNASET OY all rights reserved...