HYDRAULIC GENERATORS
INSTALLATION
ATTENTION!
DYNASET HG hydraulic generator must be grounded when rubber
cushions or plastic pads are installed to the generators framework.
Grounding is also recommended when the generator is installed onto the
base machine without rubber cushions or plastic pads.
Do not ground HG through hydraulic connections. Make the grounding only to
the base machines frame. Use external galvanized wire to gain proper grounding
as shown picture 28. The ground wire is recommended to be according to the
following table.
Generator size S (kVA)
Ground wire cross-section area (mm
2
)
S < 10 kVA
2.5 mm
2
(13AWG)
10 < S < 20 kVA
4 mm
2
(11AWG)
20 < S < 40 kVA
6 mm
2
(9AWG)
S >40 kVA
10 mm
2
(7AWG)
Ground the HG from the marked grounding spot in generators frame. The
grounding spot varies between different generator models.
Picture 28: HG hydraulic generator grounging, in picture HG 6,5