background image

GVL 8301-K

8/12

GVL 8301-K

 

English

99.821.72 1.4/02/16

Type 

GVL 8301-K

Nominal voltage 

230 V AC, 50 Hz

Rated power 

30 VA

Stand-by operating   4,3 W

Class of rating 

short-time duty, 20%

Protection class 

II

Ingress protection 

IP 54

Temperature range 

-5...+60°C

Output voltage 

24 V DC, unstabilized

Output current 

max. 1 A

Housing 

plastic

Colour 

light grey (~RAL 7035)

Dimensions 

139 x 119 x 70 mm

Technical Data

CLOSE diode

Safety function!

The CLOSE diode, marked above, must be cut out 
with side cutting pliers, if the window, which is to 
open, is within arm's reach (fitting heights of the 
window less than 2,5 m). Through this, a „key 
operation function" will be achieved with closing of 
the window. The window wing will be closing only 
as long as the vent button is operated.

In this case, automatic control is not permissible, 
e.g. by room temperature control or wind/rain 
detector.

Observe the safety notes which are 

included to the drive!

View motherboard

T0,2A

fuse mains

drive connector

230 V protection cap

mains connector

connector for
central control

CLOSE

Diode

(s.b.)

spare
fuses

OPEN
Diode

Output voltage 24 V DC!
Do not run cables together with power lines!
In case of a cable with 

ground wire

(e.g. green / yellow) this must 

not be used

!

Wiring plan (Paragon)

230 V AC, 50 Hz

to further ones

see line lenghts and cross sections

window drive

control panel

vent button

ca. 1,2 m above

upper edge

firm flooring

external

control

4x 0,8 Ø

4x 0,8 Ø

2x 0,8 Ø

4x 0,8 Ø

rain sensor

room temperature 

control

Line lenghts and cross sections

Cross section  (mm²) =

cable lenght (m) x total current

80

total current

0.5 A

240

400

640

1 A

120

200

320

m
m
m

type

2x 1,5 mm²
2x 2,5 mm²
2x 4 mm²

230 V AC supply

Covering

Place enclosed protection cap
over supply terminal after mains
cable has been connected.

L

N

PE

230 V AC, 50 Hz

Summary of Contents for D+H GVL 8301-K

Page 1: ...GVL 8301 K instructions ...

Page 2: ...objects For triggering of 24 V DC drives 1 ventilation group 1Atotal actuating current Expandable with D H accessories Only for indoor mounting WARNING Read all safety warnings instructions illustrations and specifications provided with this product Failure to follow all instructions listed below may result in electric shock fire and or serious injury Save all warnings and instructions for future ...

Page 3: ...st be cut out with side cutting pliers if the window which is to open is within arm s reach fitting heights of the window less than 2 5 m Through this a key operation function will be achieved with closing of the window The window wing will be closing only as long as the vent button is operated In this case automatic control is not permissible e g by room temperature control or wind rain detector ...

Page 4: ...ntrol panel vent button ca 1 2 m above upper edge firm flooring external control 4x 0 8 Ø 4x 0 8 Ø 2x 0 8 Ø 4x 0 8 Ø rain sensor room temperature control Line lenghts and cross sections Cross section mm cable lenght m x total current 80 total current 0 5 A 240 400 640 1 A 120 200 320 m m m type 2x 1 5 mm 2x 2 5 mm 2x 4 mm 230 VAC supply Covering Place enclosed protection cap over supply terminal a...

Page 5: ...RS 10 24V 2 1 3 4 5 6 2x 24 V DC Window drives on one window P P S LT 84 U W M1 GVL 8301 K X1 1 2 Mot b 5 Mot b 8 Mot b 1 Mot a 4 Mot a 7 Mot a 3 Fail TMS 6 Fail TMS 9 Fail TMS 8 A Z 7 N 6 5 L 4 Az Zz 3 G 2 M2 M3 VCD 20x LT 84 U LT 84 U Connect lead directly when no automatic switch available In this case the manual operation is out of function Ask your local D H partner for further connection exa...

Page 6: ...rector 22 02 2016 Only if wind detector or rain detector available If the weather automatic is switched on via vent button LT 84 U W optional the system will automatically close in case of wind or rain The system will not automatically open again if wind or rain has stopped Opening of the system for ventilation via vent button The weather automatic can be switched off at vent button LT 84 U W opti...

Page 7: ...Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 161 491 4840 E Mail enquiry dyerenvironmental co uk www dyerenvironmental co uk ...

Reviews: