GVL 8301-K
8/12
GVL 8301-K
English
99.821.72 1.4/02/16
Type
GVL 8301-K
Nominal voltage
230 V AC, 50 Hz
Rated power
30 VA
Stand-by operating 4,3 W
Class of rating
short-time duty, 20%
Protection class
II
Ingress protection
IP 54
Temperature range
-5...+60°C
Output voltage
24 V DC, unstabilized
Output current
max. 1 A
Housing
plastic
Colour
light grey (~RAL 7035)
Dimensions
139 x 119 x 70 mm
Technical Data
CLOSE diode
Safety function!
The CLOSE diode, marked above, must be cut out
with side cutting pliers, if the window, which is to
open, is within arm's reach (fitting heights of the
window less than 2,5 m). Through this, a „key
operation function" will be achieved with closing of
the window. The window wing will be closing only
as long as the vent button is operated.
In this case, automatic control is not permissible,
e.g. by room temperature control or wind/rain
detector.
Observe the safety notes which are
included to the drive!
View motherboard
T0,2A
fuse mains
drive connector
230 V protection cap
mains connector
connector for
central control
CLOSE
Diode
(s.b.)
spare
fuses
OPEN
Diode
Output voltage 24 V DC!
Do not run cables together with power lines!
In case of a cable with
ground wire
(e.g. green / yellow) this must
not be used
!
Wiring plan (Paragon)
230 V AC, 50 Hz
to further ones
see line lenghts and cross sections
window drive
control panel
vent button
ca. 1,2 m above
upper edge
firm flooring
external
control
4x 0,8 Ø
4x 0,8 Ø
2x 0,8 Ø
4x 0,8 Ø
rain sensor
room temperature
control
Line lenghts and cross sections
Cross section (mm²) =
cable lenght (m) x total current
80
total current
0.5 A
240
400
640
1 A
120
200
320
m
m
m
type
2x 1,5 mm²
2x 2,5 mm²
2x 4 mm²
230 V AC supply
Covering
Place enclosed protection cap
over supply terminal after mains
cable has been connected.
L
N
PE
230 V AC, 50 Hz