Page
7
of
10
D2330-060116-V1.1
Battery Impedance
When selected the following display is shown:
‘Rbat’
is the combined impedance (resistance) of the battery, battery leads, connectors and PSU charging path
and must not exceed 0.177Ohms.
If the test fails then a typical display might show the following:
If the test is attempted when the battery is not fitted or AC power is not present
the following display is shown:
Information
The information menu is used to view the software version of the PSU firmware and the PSU type.
Software Version
Information Menu
PSU Hardware Type
Information Menu
Software Version
When selected the following display is shown. The two characters before
and adjacent to the “V” indicate the version:
PSU Hardware Type
The display shows the PSU hardware type:
Currently there are three types:
24V 1.5A: D2431-7 (2 x 7Ah batteries)
24V 3A: D2433-7 (2 x 7Ah batteries)
24V 3A D2433-17 (2 x 17Ah batteries)
24V 5A: D2435-17 ((2 x 17Ah batteries)
Commands
The command menu remotely controls the switching of the two outputs in addition to the two local control
inputs.
OP1 Control
Command Menu
OP2 Control
Command Menu
OP1 Control
The OP1 control screen is shown opposite. The first line displays the current
output status, either
“On”
or
“Off”
and is updated in real time. The second line
indicates if local or serial control is in operation in real time. When
‘Serial’
control is selected then numeric keys can be used to control the output.
Number
‘1’
switches the output on and
‘2
’ switches the output off. Numbers ‘
4’
and ‘
5’
select between serial and
local control.
Battery Test Results
Rbat = 0.095 Ohms
Test Passed
Limit 0.177 Ohms
Waiting For Data
Fault Halted Test!
Battery Test Results
Rbat = 0.186 Ohms
Test Failed!
Limit 0.177 Ohms
Version Number
EN54PSU08V
PSU Hardware Type
24V 1.5A
OP1 On
OP1 Local Control
1=On
2=Off
4=Local
5=Serial