Warning 
Before using the test set / service tool, ensure that the AC power supply is switched off before 
removing the lid and plugging in the test cable. 

Programmer Menus 

Main Menu 

This menu selects the various functions of the test set.  When the test set is first switched-on a screen with the 
software version is shown briefly in the lower right hand corner 

(‘nnn’

 on the illustration below).  Pressing the 

up/down arrows steps through the functions.  Pressing enter will select the menu of interest. 
 

Dycon

D2430 Series 

Test Set

3DL test set nnn

Turn Off

Information

Measurements

Commands

Faults and Status

Calibration

Advanced Information
Refer to manual
For details

 

Measurements 

The measurement menu is used to select the various voltages, currents generated by the power supply and the 
battery impedance in ohms.  The menu is accessed by pressing enter when 

‘Measurements”

’ prompt is 

shown: 

PSU Current
Measurements

Measurement Menu

Battery Impedance

Measurement Menu

PSU Voltage
Measurements

Measurement Menu

Output Currents

Measure Amps Menu

Battery Charging
Current

Measure Amps Menu

Battery Voltages

Measure Volts Menu

Output Voltages

Measure Volts Menu

Charging Voltage

Measure Volts Menu

 

Summary of Contents for D2330

Page 1: ...3X series EN54 certified 24VDC Switched Mode Power Supply Units Dycon Power Solutions Ltd Unit A Cwm Cynon Business Park Mountain Ash South Wales CF45 4ER United Kingdom Tel 44 0 1443 471 900 www dyconpower com info dyconpower com D2330 060116 V1 1 ...

Page 2: ...D2330 060116 V1 1 ...

Page 3: ... power supply in large box 2 x 17 5 18 Ah batteries D2435 17 5 0A 24V power supply in large box 2 x 17 5 18 Ah batteries The D2330 allows the installer to monitor the performance of the power supply system currents and voltages the condition of the batteries and a log of PSU events and faults It can also be used to calibrate and test power supplies Test Set Service Tool Description The D2330 is su...

Page 4: ... the unit is accidentally left on continuously the programmer will automatically power down after 15 minutes of non use The test set will stay on continuously when the charging adapter is plugged in and charging Test Set Service Tool Specifications SPECIFICATIONS Charging USB Micro B 5V 450mA Maximum Charge Time 2 hours to full charge Battery Rechargeable LiPo battery 3 7V nominal 800mAH Battery L...

Page 5: ...menu of interest Dycon D2430 Series Test Set 3DL test set nnn Turn Off Information Measurements Commands Faults and Status Calibration Advanced Information Refer to manual For details Measurements The measurement menu is used to select the various voltages currents generated by the power supply and the battery impedance in ohms The menu is accessed by pressing enter when Measurements prompt is sho...

Page 6: ...shown is typical of a fully charged set of batteries Battery 1 and Battery 2 voltages are shown separately the bottom Batteries voltage display is the sum of the individual battery voltages NOTE The individual battery voltages will seldom be identical but should be balanced to at least 1V with respect to each other Actual voltage values will depend on the charge state and temperature and are not n...

Page 7: ... 1 5A D2431 7 2 x 7Ah batteries 24V 3A D2433 7 2 x 7Ah batteries 24V 3A D2433 17 2 x 17Ah batteries 24V 5A D2435 17 2 x 17Ah batteries Commands The command menu remotely controls the switching of the two outputs in addition to the two local control inputs OP1 Control Command Menu OP2 Control Command Menu OP1 Control The OP1 control screen is shown opposite The first line displays the current outpu...

Page 8: ...t screen The PSU status is shown as follows First line Output switched status either On or Off Second line Output voltage Third line Output current Fourth Line AC On or Off PSU fault status OK or Fail NOTE The Fail PSU status is displayed if any of the faults other than AC power failure are pending Battery Charging and Current Share Status A typical battery status is displayed in the adjacent scre...

Page 9: ...voltage fault and subsequent shutdown 3 O P1 fuse fault Output 1 fuse fault 4 O P2 fuse fault Output 2 fuse fault 5 PSU under minimum battery charging voltage fault Inability to correctly charge the battery because voltage is too low fault 6 PSU not charging battery fault Charging circuit malfunction fault 7 Battery lead disconnected fault One or both batteries are disconnected 8 Battery high resi...

Page 10: ...eful only to trained technicians Calibrate Battery Current Monitor Before calibrating battery 1 must be disconnected as prompted If the battery is not disconnected then Disconnect Battery will be displayed and the procedure will have to be started all over again When the calibration is completed successfully the display will show Calibration Done Note There is a hidden Advanced Information screen ...