![Dwyer Instruments W.E. Anderson WE35 Series Specifications-Installation And Operating Instructions Download Page 10](http://html.mh-extra.com/html/dwyer-instruments/w-e-anderson-we35-series/w-e-anderson-we35-series_specifications-installation-and-operating-instructions_2544543010.webp)
10
TD01
Voltage
Cycle Time
Duty Cycle (Two-Position)
AMP Draw
Torque (in-lb)
110 VAC
4 s
85%
0.24 A
177
220 VAC
4 s
85%
0.16 A
177
24 VAC
4 s
85%
0.28 A
177
24 VDC
4 s
85%
1.28 A
177
MD01
Voltage
Cycle Time
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
10 s
85%
0.24 A
265
220 VAC
10 s
85%
0.16 A
265
24 VAC
10 s
85%
1.28 A
265
TD02 and MD02 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
20 s
85%
85%
0.24 A
442
220 VAC
20 s
85%
85%
0.16 A
442
24 VAC
20 s
85%
85%
1.28 A
442
24 VDC
20 s
85%
-
1.28 A
442
TD03 and MD03 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
30 s
85%
85%
0.57 A
885
220 VAC
30 s
85%
85%
0.35 A
885
24 VAC
30 s
85%
85%
2.03 A
885
24 VDC
30 s
85%
-
2.03 A
885
Electric Actuators Performance Rating
TD04 and MD04 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
30 s
85%
85%
0.65 A
1770
220 VAC
30 s
85%
85%
0.37 A
1770
24 VAC
30 s
85%
85%
3.57 A
1770
24 VDC
30 s
85%
-
3.57 A
1770
TD05 and MD05 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
30 s
85%
85%
1.12 A
3540
220 VAC
30 s
85%
85%
0.57 A
3540
24 VAC
30 s
85%
85%
5.13 A
3540
24 VDC
30 s
85%
-
5.13 A
3540
TD06 and MD06 (MD Not Available in 24 VDC)
Voltage
Cycle Time
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
AMP Draw
Torque (in-lb)
110 VAC
45 s
85%
85%
1.18 A
5210
220 VAC
45 s
85%
85%
0.60 A
5210
24 VAC
45 s
85%
85%
6.04 A
5210
24 VDC
45 s
85%
-
6.04 A
5210
TI01
Voltage
Cycle Time
Duty Cycle (Two-Position)
Full Load AMP Draw
Torque (in-lb)
110 VAC
2.5 s
25%
0.64
100
220 VAC
2.5 s
25%
0.32
100
24 VAC
2.5 s
25%
0.4
100
24 VDC
2.5 s
25%
0.4
100
TI02 and MI01, MI02
Voltage
Cycle Time (Two Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
5 s
10 s
25%
75%
0.38
200
220 VAC
5 s
10 s
25%
75%
0.18
200
24 VAC
5 s
5 s
25%
75%
0.7
200
24 VDC
5 s
5 s
25%
75%
0.7
200
TI03 and MI03
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
5 s
10 s
25%
75%
0.38
300
220 VAC
5 s
10 s
25%
75%
0.18
300
24 VAC
5 s
5 s
25%
75%
0.7
300
24 VDC
5 s
5 s
25%
75%
0.7
300
TI04 and MI04
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
10 s
20 s
25%
75%
0.38
400
220 VAC
10 s
20 s
25%
75%
0.18
400
24 VAC
10 s
10 s
25%
75%
0.9
400
24 VDC
10 s
10 s
25%
75%
0.9
400
TI05 and MI05
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
15 s
30 s
25%
75%
0.38
675
220 VAC
15 s
30 s
25%
75%
0.18
675
24 VAC
15 s
15 s
25%
75%
0.7
675
24 VDC
15 s
15 s
25%
75%
0.7
675
TI06 and MI06
Voltage
Cycle Time (Two-Position)
Cycle Time (Modulating)
Duty Cycle (Two-Position)
Duty Cycle (Modulating)
Full Load AMP Draw
Torque (in-lb)
110 VAC
15 s
30 s
25%
75%
0.38
1000
220 VAC
15 s
30 s
25%
75%
0.18
1000
24 VAC
15 s
15 s
25%
75%
1.1
1000
24 VDC
15 s
15 s
25%
75%
1.1
1000
MAINTENANCE/REPAIR
Upon final installation of the Series WE, only routine maintenance is required. The
Series WE is not field serviceable and should be returned if repair is needed. Field
repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping
the product back for repair. Be sure to include a brief description of the problem plus
any additional application notes.