Dwyer Instruments TSXT Series Specifications-Installation And Operating Instructions Download Page 3

List of Parameters

COn Description

Units

Range

SET

r0

r1

r2

r6

F0

F1

c0

c1

c2

c3

c4

c5

Set point

Differential or hysteresis

Minimum value for set point

Maximum value for set point

Fan operation

Fan stoppage temperature

Stop compressor & fan with door open

Minimum compressor stoppage time

Continuous cycle time

ON time of fault cycle

OFF time of fault cycle

Minimum ON time of the compressor

Minimum time between two connections of 

the compressor

Degrees

Degrees

Degrees

Degrees

Option

Degrees

Option

Minutes

h - m

Minutes

Minutes

Minutes

Minutes

r1 to r2

0.1 to 20

-99.9 to r2

r1 to 302

off/on/con

-99.9 to 302

no/yes/con/fan

0 to 240

0.0 to 18

0 to 999

0 to 999

0 to 240

0 to 240

dEF Description

Units

Range

d0

d0

d1

d2

d3

d4

d5

d6

d7

d8

d9

d10

d11

d12

d14

Cool/Heat mode (ST13)

Type of defrosting (ST23 & 33)

Temperature at which defrosting will stop

Maximum defrosting time

First hour of day for defrosting

Delay of first defrosting

Display on defrosting

Display return limit

Compressor drip time

Interval between defrosting

Fan works on defrosting

Fan drip time

Minimum defrosting time

Fan/defrosting control probe

Units to count the defrosting cycle

Option

Option

Degrees

Minutes

h - m

Minutes

Option

Minutes

Minutes

h - m

Option

Minutes

Minutes

Option

Option

re/in

re/in

-99.9 to 302

0 to 240

00.0 to 18.0

0 to 999

off/on/-d-

0 to 240

0 to 240

00.0 to 99.0

no/yes

0 to 240

0 to 240

sd1/sd2/sd3

rt/ct

Pro Description

Units

Range

P0

P1

P2

P3

P4

P5

P6

P7

Temperature scale

Ambient probe 1 calibration

Defrosting probe 2 calibration

Product probe 3 calibration

Decimal point

Probe to display

Probe 2 present

Probe 3 present

Option

Degrees

Degrees

Degrees

Option

Option

Option

Option

°C/°F

-20.0 to 20.0

-20.0 to 20.0

-20.0 to 20.0

no/yes

sd1/sd2/sd3

no/yes

no/yes

ALA Description

Units

Range

A0

A1

A2

A3

A4

A5

A6

A7

A8

Fan and alarm differential

Maximum alarm temperature

Minimum alarm temperature

Time validation open door or external alarm

Time without alarm after defrosting

Time without alarm after opening the door

Time without alarm after connection

Alarm verification time

Probe for alarm

Degrees

Degrees

Degrees

Minutes

h - m

h - m

h - m

h - m

Option

0.1 to 20.0

0.1 to 99.9

0.1 to 99.9

0 to 999

0.0 to 18.0

0.0 to 18.0

0.0 to 18.0

0.0 to 18.0

sd1/sd2/sd3

Ini

Description

Units

Range

Hor

Min

E0

H0

H1

H2

H3

H5

H6

H7

H8

H10

HdE

MdE

Hour

Minutes

Configure digital input

Factory settings

Master slave

Keypad protection

Delay time on connecting

Keyboard code

Type of probe

Relay 2 setup

Relay 3 setup

HACCP activated

Next defrost time

Next defrost time

Hours

Minutes

Option

Option

Option

Option

Seconds

Numeric

Option

Option

Option

Option

Hours

Minutes

0 to 23

0 to 59

all/AI/In/def/ndf

0 to 3

Mst/Slv

no/yes

0 to 240

0 to 999

PTC/NTC

lit/FAn/ALA/dEF/FAI

lit/FAn/ALA/dEF/FAI

no/yes

(only read)

(only read)

Parameter Descriptions

Compressor (COn)

SET = Working Set Point. 

Temperature the system trys to maintain. Variable 

between r1 and r2.

r0 = Differential. 

When primary probe temperature >= Set+r0 Compressor ON

When primary probe temperature <= Set Compressor OFF

r6 = Fan operation on regulation.

 

Off = Fan does not connect on regulation.

  On = Fan is always connected on regulation.

  Con = Fan linked to compressor start-up.

  (Fan ON if allowed by the temperature set in F0)

F0 = Fan temperature limit.  

Direct mode. Relay selected as FAN. 

Fan OFF on regulation when probe temperature 

set in d12 is >= F0. Fan ON on regulation, when temperature is =< F0 - A0.

Reverse  mode.  Relay  selected  as  FAI. 

Fan OFF on regulation when probe 

temperature set in d12 is < F0. Fan ON on regulation, when temperature is >= F0 + A0.

F1 = Stop compressor and Fan if door opened (Circuit closure between input 

terminal 5 and common terminal 4).

 

No = the fan and compressor do not stop on regulation and continuous cycle when 

  opening the door.

  Yes = the fan and compressor stop on regulation and continuous cycle when opening 

  the door.

  Con = the compressor stop but the fan do not stop on regulation and continuous 

  cycle when opening the door.

  Fan = the fan stop but the compressor do not stop on regulation and continuous 

  cycle when opening the door.

c0 = Minimum compressor stop time. 

Minimum time since compressor stops until 

it is starts again.

c1 = Continuous cycle time. 

Duration of a continuous cold cycle.

c2 = ON time of fault cycle, 

when ambient probe is broken

c3 = OFF time of fault cycle, 

when ambient probe is broken

c4 = 

Minimum time since compressor starts until it stops.

c5 = 

Minimum time since compressor starts until it starts again.

Defrost (dEF)

d0 = Cool / Heat mode (ST13). 

re = cool; In = heat

d0 = Type of defrosting (ST23, ST33) 

  re = defrosting without connecting the compressor.

  in = defrosting by connecting the compressor.

d1 = End of defrosting temperature. 

When this temperature is reached the defrosting 

will end.

d2 = Maximum defrosting time. 

The defrosting will stop when this time is reached. If 

it is zero there will be no defrosting.

d3 = First hour defrosting of the day. 

From 00:00 hours the first defrosting is at d3 

hours. Until this time no defrosting is performed.

d4 = Delay first defrosting.

Time to carry out the first defrosting if d3 = yes.

d5 = Display during the defrosting.

 

Off = the current temperature will be shown during defrosting.

  On = the temperature at defrost beginning is frozen on display until the end of 

  defrosting and until the current temperature is equal or lower than the initial one, or 

  until d6 time elapses.

  -d- = Label -d- is displayed during defrosting, until the end of defrosting and until the 

  current temperature is equal or lower than the initial one, or until d6 time elapses.

d6  =  Display  return  limit. 

Maximum  time  before  viewing  the  current  temperature 

again after defrosting.

d7 = Compressor drip time. 

Time since defrosting ends until the compressor can 

be connected.

d8 = Interval between defrosting. 

Time between the start of a defrosting and the start 

of the following one. If it is zero defrosting is not done automatically by time.

d9 = Fan operation during defrosting time. 

It determines if the fan is connected or 

not during defrosting.

d10 = Fan drip time. 

Time since defrosting ends until fan can be connected.

d11 = Minimum Time duration defrosting. 

Once defrosting begins it stays at least 

during this time

d12 = Fan & defrosting control probe.

 

sd1 = primary probe

  sd2 = defrosting probe

  sd3 = product probe

d14 = Units to count the defrosting cycle.

 

rt = according to the working time of the controller

  ct = according to the working time of the compressor

Note: 

For parameter settings described as h-m, the first 2 digits represent hours, and 

the third represents tens of minutes. (Example: 4.2 is 4 hours and 20 minutes).