4.0 SECURITY (continued)

Note: 

If the Supervisor Password has been setup and forgotten, the only recovery 

method is to perform a factory reset of the unit, which will wipe out all configuration 

settings. To perform a factory reset, press and hold the button located on the back of 

unit above terminal block pins 4 and 5. The connector for the second terminal block 

may need to be removed for easier access.

Passcode Setup

The  Operator  security  level  allows  access  only  to  alarm  acknowledgement  and  to 

change the room modes from occupied, unoccupied and cleaning. The operator 

should be defined as the person(s) that has day-to-day interaction with the monitor to 

change room operating modes (when no alarms are active). The operator and staff can 

also respond to local audible and visual alarms. If Operator Password is enabled then 

a password will be needed before changes can be made. The Supervisor Level allows 

full access to all levels of the menu structure. This mode, if enabled, is used during 

initial configuration and follow-up reconfiguration.

5.1 DIAGNOSTICS

The Diagnostics menu performs I/O and BACnet tests on the unit. The Diagnostics 

menu can be accessed by clicking the settings icon on the home screen, then selecting 

Diagnostic.

I/O Testing

In the I/O Testing menu, the screen will show the Inputs and Outputs selections. The 

unit has the capability to choose the input desired from the pull-down menu; the input 

value (volts or mA) and the corresponding calculated output value (in the Eng. units 

selected) will be displayed if a sensor is properly connected.

5.1 DIAGNOSTICS (continued)

If the user chooses the Output BI1 they can view the output value and the user can 

also change the state.

6.0 MAINTENANCE 

The  Maintenance  menu  provides  several  functions  that  help  ensure  the  RSMC 

is  configured  and  operating  accurately  with  proper  parameters.  To  access  the 

Maintenance menu from the home screen, press the Settings icon in the top right 

corner and select the Maintenance button.

Within the maintenance menu, the following maintenance functions can be accessed:

•  Calibration of the built-in pressure sensor 

•  Date and Time allows manual or BACnet setting of date/time and customization of 

  the date/time display

•  Duplicate/Cloning permits copying the RSMC configuration to and from a USB 

  thumb drive – the purpose of this is to replicate the configuration on other devices or 

  units that may be replaced in the field

•  Software Update – in the event of software upgrades or new features that could 

  become available from Dwyer Instruments

•  Reset To Factory Default – restores the unit’s original factory configuration.

6.1 PRESSURE CALIBRATION

Pressure Calibration is used to ensure accurate and reliable pressure sensing occurs 

continuously in the room environment. To access pressure calibration from the home 

screen, press the Settings icon in the top right corner. From the Maintenance menu, 

select Pressure Calibration.

Depending  on  connection,  the  unit  will  display  the  live  value  of  the  room  pressure 

being sensed at the time of menu access. Zero Adjustment can be used for either 

an on-board sensor (DP) or external sensor (UI2 and UI3). To access the on-board 

sensor,  remove  the  RSMC  display  from  the  wall  surface  and  remove  the  pressure 

tubes from the “+” (HIGH) and “-” (LOW) side of the sensor on the back of the unit. 

Let both the “+” and “-” ports open/unblocked and press the Apply the Zero Function 

button. The same can be done for external pressure transmitters at their location.

Diagnostic screen

Summary of Contents for StabiliSENSE RSMC Series

Page 1: ...ironment such as a clean room or isolation room and an area outside the room Maintaining a constant differential pressure between the two spaces is critical in ensuring the room is protected by ingress for the outer room or vice versa The RSMC can be programmed to monitor either positive or negative room static pressure in 1 to 3 locations In total it can monitor up to 4 parameters built in differ...

Page 2: ...touchscreen operation when changes in room conditions are needed when additional information is desired or if alarms need to be acknowledged A few of the key elements of the screen are described and shown below The RSMC provides visual representation where each of the parameters are either in normal green within the caution stage yellow in the alarm state red and in cleaning mode blue The caution ...

Page 3: ... and 2 analog or BACnet inputs to be select by the user 2 2 Rooms Monitoring 4 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 2 binary contacts 3 3 Rooms Monitoring 6 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 3 binary contacts wired in series Examples of 1 room 2 room and 3 room setups are ...

Page 4: ...ter For example 0 VDC corresponds to the minimum range of the sensor and 5 VDC corresponds to the maximum range of the sensor In the Measurement box the user can define the type of measurement temperature humidity etc and the desired engineering units to be displayed If ACH Air Changes per Hour is selected duct dimensions need to be entered when the input type is selected as volumetric flow When u...

Page 5: ...try and personnel access Return to Normal delay is the opposite when a parameter value goes out of alarm and now falls within normal range the audible visual and output alarm conditions will persist for this period of time or until the alarm condition is cleared Alarm Deadband is a value that is added or subtracted to a limit when determining if a parameter has returned to a normal state For examp...

Page 6: ...the sensor assigned to the display position to the right next to Select Sensor If the BACnet option is selected the user has to input the BACnet address and sensor type of the remote sensor After completing the room settings the user can select each parameter from each room in order to use it at the alarm configuration or output configuration Each parameter is named with the room name and the sele...

Page 7: ... the output value and the user can also change the state 6 0 MAINTENANCE The Maintenance menu provides several functions that help ensure the RSMC is configured and operating accurately with proper parameters To access the Maintenance menu from the home screen press the Settings icon in the top right corner and select the Maintenance button Within the maintenance menu the following maintenance fun...

Page 8: ...rom the home screen press the Settings icon in the top right corner From the Maintenance menu select Reset A factory reset may help establish a baseline of original functionality from which to build the specific configuration for a given application New configurations can then be added by either touchscreen entry Copy from USB or over the BACnet network Selecting NO will cause the RSMC unit to rem...

Reviews: