Dwyer Instruments StabiliSENSE RSMC Series Specifications-Installation And Operating Instructions Download Page 5

3.6 INPUTS (continued)

“REMOTE” Usage allows an operator, or staff outside of the room, to set the Room 

to Occupied or Standby (standby representing either Cleaning or Unoccupied). If the 

RSMC is configured via BACnet, the user can program the remote input for all three 

options; Occupied, Unoccupied and Cleaning.

To set Binary Input 1, the same steps for User Input 3 outlined previously are used. 

This is usually used for one of the door contacts or for multiple door contacts in series.

3.7 OUTPUTS

The RSMC supports 1 binary output and 1 analog output (4-20 mA and 0-10 V 

selectable)  that  corresponds  to  the  reading  of  the  built-in  piezoresistive  differential 

pressure sensor. The Outputs menu can be accessed by clicking on the Settings icon 

on  the  home  screen,  selecting  Configurator,  selecting  Input/Output,  then  selecting 

Output.

There is one relay contact with “Normally Closed” and “Normally Open” connections 

available. This is selectable by choosing which Output Type Source to use.

The  4-20  mA  or  0-10  V  output  cannot  be  configured  to  correspond  to  a  different 

measurement other than the built-in differential pressure. 

The source that will drive the relay can be set up to be any of the following:

•  Master Alarm: The relay changes state when any alarm occurs in any of the rooms

•  Door Alarm: The relay changes state when any door alarm occurs in any of the 

 rooms

•  Pressure Alarm: The relay changes state when any pressure alarm occurs in any of 

  the rooms

•  Analog Alarm: The relay changes state when any analog input alarm occurs in any 

  of the rooms

•  Room XXXXX Alarm: The relay changes state when the specific room parameter 

  alarm occurs in the selected room.
  ° Where XXXXX is the parameter of the room (See Rooms Settings)

•  None – the relay will not be driven by any source.

3.8 ALARMS

The Alarm Settings menu is where all the alarm and warning functions are defined.

Both low and high limits can be changed to Enabled or Disabled individually and set to 

audio only, visual only, or both audio and visual. The alarm menu can be accessed by 

clicking on the settings icon on the home screen, selecting Configurator, then selecting 

Alarm.

For  a  positive  pressure  room  a  high  limit  may  not  be  required.  If  this  is  the  case, 

the High Alarm can be set to Disabled. For a negative room, a low limit may not be 

required. If this is the case, the Low Alarm can be set to Disabled.

“Alarm Delay” is the time between when one of the parameter values falls beyond 

an alarm condition (Low or High Limit) and when an audible, visual, or output alarm 

condition occurs. Use the “Alarm Delay” when time is needed for door entry and 

personnel access. “Return to Normal” delay is the opposite; when a parameter value 

goes out of alarm and now falls within normal range, the audible, visual, and output 

alarm conditions will persist for this period of time or until the alarm condition is cleared.

“Alarm Deadband” is a value that is added or subtracted to a limit when determining if 

a parameter has returned to a normal state. For example, if a temperature parameter 

is set with a low alarm limit of 66.5 degrees and the deadband set at 1.0 degrees, but 

the temperature falls to 66.5 and goes into an alarm, the temperature must then return 

to a value greater than 67.5 to trigger the alarm state to change from alarm to normal 

function. Alarms are available for all parameters.

3.8 ALARMS (continued)

For Analog Parameters:

For Digital Parameters:

The high and low alarm levels are enabled by choosing “ON”. The alarm levels are set 

by entering the value desired. These settings apply to all alarm behaviors.

The warning alert set point for the analog parameters is when the display changes 

from green to yellow to provide a visual warning that the parameter is getting close to 

the unacceptable or alarm condition. The warning alert set point is the amount above 

the low limit alarm, or below the high limit alarm set points when the display color 

change is desired. 

The  Interlocking  function  causes  an  alarm  condition  to  persist  even  when  the 

parameters have returned to normal operating ranges. For the interlocked alarm to 

be cleared, it must be acknowledged at the touchscreen of the RSMC. This function 

is useful when it is important for staff present in the room to acknowledge the alarm 

by responding.

Enabling the Audible Alarm causes the audible alarm within the RSMC unit to sound 

when in alarm condition. If disabled, the alarm will still be visible on the RSMC screen. 

If the RSMC is set up over the network, it will activate the alarm via the binary output 

relay; the binary output relay is configurable.

Audible Alarms could have the potential to be disruptive. If Audible Alarms are needed, 

test  several  settings  to  optimize  an  appropriate  volume  for  the  environment;  One 

second after volume selection, the buzzer will beep briefly to provide a sample of the 

volume level.

Mute Timeout is the amount of time an acknowledged alarm will be silent. When an 

audible alarm occurs, a staff member can silence the alarm by tapping the Mute Sound 

icon. Upon pressing it, the Mute Timeout starts counting down from the number of 

seconds  configured.  When  the  countdown  time  goes  to  zero  and  the  cause  of  the 

alarm condition persists, the audible alarm will sound again. The amount of seconds 

should be long enough for the staff to acknowledge it, but not be overly disruptive.

Interlocking alarm icon shown on bottom right

Summary of Contents for StabiliSENSE RSMC Series

Page 1: ...ironment such as a clean room or isolation room and an area outside the room Maintaining a constant differential pressure between the two spaces is critical in ensuring the room is protected by ingress for the outer room or vice versa The RSMC can be programmed to monitor either positive or negative room static pressure in 1 to 3 locations In total it can monitor up to 4 parameters built in differ...

Page 2: ...touchscreen operation when changes in room conditions are needed when additional information is desired or if alarms need to be acknowledged A few of the key elements of the screen are described and shown below The RSMC provides visual representation where each of the parameters are either in normal green within the caution stage yellow in the alarm state red and in cleaning mode blue The caution ...

Page 3: ... and 2 analog or BACnet inputs to be select by the user 2 2 Rooms Monitoring 4 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 2 binary contacts 3 3 Rooms Monitoring 6 parameters 1 built in differential pressure 2 analog or BACnet inputs to be select by the user and 3 binary contacts wired in series Examples of 1 room 2 room and 3 room setups are ...

Page 4: ...ter For example 0 VDC corresponds to the minimum range of the sensor and 5 VDC corresponds to the maximum range of the sensor In the Measurement box the user can define the type of measurement temperature humidity etc and the desired engineering units to be displayed If ACH Air Changes per Hour is selected duct dimensions need to be entered when the input type is selected as volumetric flow When u...

Page 5: ...try and personnel access Return to Normal delay is the opposite when a parameter value goes out of alarm and now falls within normal range the audible visual and output alarm conditions will persist for this period of time or until the alarm condition is cleared Alarm Deadband is a value that is added or subtracted to a limit when determining if a parameter has returned to a normal state For examp...

Page 6: ...the sensor assigned to the display position to the right next to Select Sensor If the BACnet option is selected the user has to input the BACnet address and sensor type of the remote sensor After completing the room settings the user can select each parameter from each room in order to use it at the alarm configuration or output configuration Each parameter is named with the room name and the sele...

Page 7: ... the output value and the user can also change the state 6 0 MAINTENANCE The Maintenance menu provides several functions that help ensure the RSMC is configured and operating accurately with proper parameters To access the Maintenance menu from the home screen press the Settings icon in the top right corner and select the Maintenance button Within the maintenance menu the following maintenance fun...

Page 8: ...rom the home screen press the Settings icon in the top right corner From the Maintenance menu select Reset A factory reset may help establish a baseline of original functionality from which to build the specific configuration for a given application New configurations can then be added by either touchscreen entry Copy from USB or over the BACnet network Selecting NO will cause the RSMC unit to rem...

Reviews: