16
Analog Input – Outlet Temperature
COV Increment Value
Supported Units:
Degrees-Celsius (62), Degrees-Kelvin (63), Degrees-Fahrenheit (64), Degrees-
Rankine (523)*
*Non-Standard BACnet unit
Analog Value – Volume Flow
COV Increment Value
Supported Units:
Cubic-feet-per-second (142), Cubic-feet-per-minute (84), Cubic-feet-per-hour (191),
Cubic-feet-per-day (248), US-gallons-per-minute (89), US-gallons-per-hour (192),
Liters-per-second (87), Liters-per-minute (88), Liters-per-hour (136), Cubic-meters-
per-second (85), Cubic-meters-per-minute (165), Cubic-meters-per-hour (135), US-
gallons-per-second (515)*, US-gallons-per-day (516)*, Liters-per-day (517)*, Cubic-
meters-per-day (518)*
*Non-Standard BACnet unit
Analog Value – Mass Flow
COV Increment Value
Supported Units:
Kilograms-per-second (42), Kilograms-per-minute (43), Kilograms-per-hour (44),
Kilograms-per-day (526)*, Pounds-mass-per-second (119), Pounds-mass-per-minute
(45), Pounds-mass-per-hour (46), Pounds-mass-per-day (47812)
*Non-Standard BACnet unit
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AI3
"Outlet Temperature"
ANALOG_INPUT (0)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Degrees-Celsius (62)
1.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Default Value Minimum Value Minimum Value Increment
1.0°C
0.1°C
10.0°C
0.1°C
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AV1
"Volume Flow"
ANALOG_VALUE (1)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Cubic-feet-per-second (142)
1.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Present Value
Status Flags
Event State
Reliability
Out of Service
Units
COV Increment
Property List
AV2
"Mass Flow"
ANALOG_VALUE (2)
Current reading
0
Normal (0)
NO_FAULT_DETECTED (0)
FALSE (0)
Pounds-mass-per-second(119)
10.0
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Real
BACnetStatusFlags
BACnetEventState
BACnetReliability
Boolean
BACnetEngineeringUnits
Real
BACnetARRAY[N] of BACnetPropertyIdentifier
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Default Value Minimum Value Minimum Value Increment
1.0 ft³/s
0.133 ft³/s
13.3681 ft³/s
0.1 ft³/s
Default Value Minimum Value Minimum Value Increment
10.0 lbm/s
10.0 lbm/s
100.0 lbm/s
0.1 lbm/s