Binary Value - Alarm Low Limit Status
This object represents the current status of the alarm low limit. When active, the ALLO
LED on the instrument face is illuminated.
Binary Value - Manual Alarm Reset
This object represents the alarm type setting (ALrE in the menu). When active, the
alarm status will remain active after the alarm condition has passed.
Binary Value - Power Up Alarm Inhibit
This object represents the Low Alarm Inhibit (ALiH) SUB MENU. When enabled, the
process value must be greater than the alarm low limit before an alarm low condition
is considered active.
Positive Integer Value - Alarm Delay
This object represents the amount of time an alarm condition must be continuously
met before the alarm status becomes active.
Multi-State Value - Relay 1 Source
This object represents the relay 1 source setting. The selected source determines
when the relay is active. If the source is active, the relay will be active.
Multi-State Value - Relay 1 Action
This object represents the relay 1 action setting. The selected action determines what
happens when the relay is active. If the selected source is an alarm, then the state text
values are “Close” and “Open”.
Multi-State Value - Relay 2 Source
This object represents the relay 2 source setting. The selected source determines
when the relay is active. If the source is active, the relay will be active.
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
BV8
“Alarm Low Limit Status”
Binary Value
Inactive
{0,0,0,0}
Normal
No Fault Detected
FALSE
BACnet Object Identifier
Character String
BACnet Object Type
BACnet Binary PV
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Read
Read
Read
Read/Write**
Read
Read
Read
Read/Write
**The low alarm status can be reset to inactive by writing inactive to the present
value property. This is allowed only if the Manual Alarm Reset is Active and the
process value no longer satisfies the alarm low condition. In all other cases a BACnet
communication protocol error is returned.
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
BV9
“Manual Alarm Reset”
Binary Value
Inactive
{0,0,0,0}
Normal
No Fault Detected
FALSE
BACnet Object Identifier
Character String
BACnet Object Type
BACnet Binary PV
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Number of States
State Text
MSV3
“Relay 1 Source”
Multi-State Value
2
{0,0,0,0}
Normal
No Fault Detected
FALSE
7
{“Off”, “Set Point 1”, “Set
Point 2”, “Any Alarm”,
”Alarm High LImit”,
“Alarm Low Limit”,
“External Input”}
BACnet Object Identifier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Unsigned
BACnet Array[N] of
Character String
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Number of States
State Text
MSV4
“Relay 1 Action”
Multi-State Value
1
{0,0,0,0}
Normal
No Fault Detected
FALSE
2
{“Direct”, “Reverse”}
BACnet Object Identifier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Unsigned
BACnet Array[N] of Character
String
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Number of States
State Text
MSV5
“Relay 2 Source”
Multi-State Value
3
{0,0,0,0}
Normal
No Fault Detected
FALSE
7
{“Off”, “Set Point 1”, “Set
Point 2”, “Any Alarm”,
”Alarm High LImit”,
“Alarm Low Limit”,
“External Input”}
BACnet Object Identifier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Unsigned
BACnet Array[N] of
Character String
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
BV10
“Power Up Alarm Inhibit”
Binary Value
Inactive
{0,0,0,0}
Normal
No Fault Detected
FALSE
BACnet Object Identifier
Character String
BACnet Object Type
BACnet Binary PV
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Property
Default Value
Property Data Type
Access
Object Identifier
Object Name
Object Type
Preset Value
Status Flags
Event State
Reliability
Out Of Service
Units
Max Pres Value
Min Pres Value
PIV1
“Alarm Delay”
Positive Integer Value
0
{0,0,0,0}
Normal
No Fault Detected
FALSE
Mode Specific
3600
0
BACnet Object Identifier
Character String
BACnet Object Type
Unsigned
BACnet Status Flags
BACnet Event State
BACnet Reliability
Boolean
BACnet Engineering Units
Real
Real
Read
Read
Read
Read/Write
Read
Read
Read
Read/Write
Read
Read
Read