AN24 & AN28 Annunciators  

 

Instruction Manua 

15

 

 

Silence Pushbutton 
Enable/Disable 

1.  Press and hold 

ACK

 and 

RESET

 for 3 

seconds until all LEDs cycle, then release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle.

1

 

3.  Press 

RESET

 within 3 seconds of release 

while LEDs blink.

1

 

4.  Press the 

ACK

 pushbutton twice until LED 3 

is either off or brightly on. 

5.  Press the 

RESET

 pushbutton to turn LED 3 

off to disable the silence pushbutton or 
brightly on to enable the silence pushbutton. 

6.  Press 

ACK

 to accept the silence pushbutton 

setting. 

7.  Press and hold 

ACK 

for five seconds to 

return to normal operation. 

The green power LED will blink quickly to indicate the 
unit is in the advanced programming mode. The unit 
will automatically leave setup mode if no pushbutton 
is pressed for 3 minutes. 

Note: LED 1 and 2 are used for relay fail-safe setup 
(see page 13)

 

 

1

The unit will automatically leave setup mode if steps 

2 and 3 are not followed. 

No Lock-In Sequence Option 

ISA sequence option 4 

no lock-in

, may be added to 

any sequence. Momentary alarms will clear without 
the 

ACK

 pushbutton. Sequences A, F1A, F2A, and 

F3A will automatically clear any momentary alarm. 
Sequences M, F1M, and F2M will clear all momentary 
alarms when the 

RESET

 pushbutton is used, 

regardless of what channels have previously been 
acknowledged with 

ACK

Selecting No Lock-In Operation 

1.  Press and hold 

ACK

 and 

RESET

 for 3 

seconds until all LEDs cycle, then release. 

2.  Press 

RESET

 within 3 seconds of release 

while LEDs cycle.

1

 

3.  Press 

RESET

 within 3 seconds while LEDs 

blink.

1

 

4.  Press the 

ACK

 pushbutton three times until 

LED 4 is either off or brightly on. 

5.  Press the 

RESET

 pushbutton to turn LED 4 

off to disable the 
no lock-in option or on to enable the no lock-
in option. 

6.  Press 

ACK

 to accept the option setting. 

7.  Press and hold 

ACK 

for five seconds to 

return to operation. 

The green power LED will blink quickly to indicate the 
unit is in the advanced programming mode. The unit 
will automatically leave setup mode if no pushbutton 
is pressed for 3 minutes. 

Note: LED 1 and 2 are used for relay fail-safe setup 
(see page 13), and
 LED 3 is used for silence 
pushbutton enable/disable (see page 14).
 

1

The unit will automatically leave setup mode if steps 

2 and 3 are not followed. 

Reset to Factory Defaults 

1. 

Hold the 

ACK

 and 

RESET

 pushbuttons for 3 

seconds until all red LEDs cycle. Release once the 
LEDs begin to cycle. 

2. 

Press and hold the 

RESET

 button for 5 seconds. If 

the 

RESET

 button is not pressed within 3 seconds 

of releasing 

ACK

 and 

RESET

, the unit will return 

to run mode without reset. 

3. 

Reset the 4-position switch on the rear of the 
control to the indicated default settings. 

 

Factory 

Default 

Switch 

Positions 

 

 

 

Troubleshooting 

If the annunciator is not working as expected, refer to 
the recommendations below. 

Troubleshooting Tips 

Symptom 

Check/Action 

Power LED off 

Check power at power 
connector 

Audible alarm does not 
sound when alarm state 
detected 

Check: 
1. 

Rear switch position 4  
is ON. 

2. 

No external pushbutton 
contacts on the input 
connector are shorted. 

Power light blinks and 
channel/point indicators 
flash intermittently when 
powered up. 

Check that no external 
pushbutton contacts on the 
signal connector are shorted  
to common. 

Display sequence does not 
function as expected. 

Check: 
1. 

Verify sequence selection 
as shown on pag

12

2. 

Check that no external 
pushbutton contacts on the 
input connector are 
shorted.  

If the display locks up or 
the unit does not respond 
at all  

Cycle the power to restart the  
microprocessor. 

Relay operation is 
reversed 

Check: 
1. 

Fail-safe settings as shown 
on pag

13

2. 

Wiring of relay contacts 

Other symptoms not 
described above 

Call Technical Support for  
assistance. 

 

To reset unit to factory default settings of sequence 
F2A-1, first out indication with silence and 
acknowledge pushbuttons with automatic reset,  
see 

Reset to Factory Defaults

. 

Summary of Contents for AN24 Series

Page 1: ...cluding First Out Multiple Unit First Out Indication Free Custom Message Labels Silence Acknowledge and Reset Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Operating Temperature Range 40 to 65 C 40 to 149 F UL C UL Listed E160849 508 Industrial Control...

Page 2: ...ll not exceed the purchase value repair or replacement of the defective unit See Warranty Information and Terms Conditions on www dwyer inst com for complete details 2020 Dwyer Instruments Inc All rights reserved Introduction The Series AN24 AN28 is a multipurpose panel mounted alarm annunciator available for four or eight inputs It can be set up to respond to alarm conditions based on 8 field sel...

Page 3: ...Overview 11 Front Panel Pushbuttons and Status LED Indicators 11 Full Function Test 11 Multiple Unit First Out Indication 11 Shared Front Panel Buttons 11 Annunciator Sequence Selection 12 Sequence Programming 12 Sequence Descriptions 12 Normally Open Normally Closed Input Setup 12 Programming NO NC Inputs 12 NO NC Programming Example 13 Relay Operation 13 Relay 1 Operation 13 Relay 2 Operation 13...

Page 4: ...r Labeling for AN24 1 8 Figure 6 Connector Labeling for AN28 1 8 Figure 7 Connector Labeling for AN24 2 8 Figure 8 Connector Labeling for AN28 2 8 Figure 9 Power Connections 9 Figure 10 NO NC Contact Inputs 9 Figure 11 Open Collector NPN Transistor Inputs 9 Figure 12 Relay 24 V Output Connections 9 Figure 13 AC and DC Loads Protection 10 Figure 14 Low Voltage DC Loads Protection 10 Figure 17 Syste...

Page 5: ...n to normal operation with the programmed input types Basic Connections All connections are made to removable screw terminal connectors located at the rear of the instrument For complete connection details see page 8 Use copper wire with 60 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable...

Page 6: ...humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color black Mounting 1 8 DIN panel cutout required Two panel mounting bracket assemblies provided Tightening Torque Screw terminal connectors 5 lb in 0 56 Nm Overall Dimensions 4 68 x 2 45 x 4 19 62 mm x 119 mm x 106 mm H x W x D Weight 9 6 oz 272 g...

Page 7: ...trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the unit malfunctions please contact your supplier or the factory for assistance Panel Mounting Prepare a sta...

Page 8: ...y regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prevent damage to the instrument and ensure personnel safety Connectors Labeling The connectors label affixed to the instrument shows the location of all connectors available with requested configuration Figure 4 Connector Labeling for AN24 1 Figure 5 Connector Labeling for AN28 ...

Page 9: ... input channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistors program inputs for normally closed input operation see page 12 Open circuit voltage is approximately 3 3 VDC provided by a 47 kΩ internal pullup resistor The following figure shows an example of open collec...

Page 10: ... Snubbers Available from Dwyer RC networks are available from Dwyer and should be applied to each relay contact switching an inductive load Part number PMA 09 External Input Types The external Silence SIL Acknowledge ACK and Reset RST inputs may be contacts i e pushbuttons relay contacts etc open collector inputs OC or TTL signals However throughout this manual the term pushbutton is used to descr...

Page 11: ...h reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 16 LED TEST SILENCE ACK Press and release the SILENCE and ACK pushbuttons to flash the channel indicator LEDs for a lamp test Full Function Test Press and hold SILENCE and ACK for 5 seconds to perform a function test This tests the sequence operation and h...

Page 12: ...Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and common will cause an alarm condition 3 An active logic level high or no supplied active logic level on an input channel will cause an alarm condition Programming NO NC Inputs 1 Press and hold ACK and RESET f...

Page 13: ...ed Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for each relay Programming Relay Fail Safe 1 Press and hold ACK and RESET for 3 seconds When all LEDs cycle release 2 Press RESET within 3 seconds of release while LEDs cycle 1 3 Press RESET within 3 seconds of re...

Page 14: ...ble disable option see page 14 and no lock in option see page 15 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2 ON OFF Relay 1 ON OFF Relay 2 NORMAL FAIL SAFE Alarms Cleared Alarm Occurance Relay On Relay is energized Relay Off Relay is de energized Alarm Occurrence A new alarm occurs when there is no previous unackno...

Page 15: ...to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed for 3 minutes Note LED 1 and 2 are used for relay fail safe setup see page 13 and LED 3 is used for silence pushbutton enable disable see page 14 1The unit will automatically leave setup mode if steps 2 and 3...

Page 16: ...input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indication First Out Reset F3A Only The RESET pushbutton is used to reset the first out indication only Normal Inputs are in the normal state LED Condition Descriptions 1st Pt Indicates the behavior of the firs...

Page 17: ...ady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Condition Normal 1st Pt LED Off Next Pt LED Off Horn Off Condition Alert 1st Pt LED Flash Nex...

Page 18: ... Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK before RESET Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Intermittent Flash Fast Flash On ACK Pushbutton Acknowledge Slow Flash Steady Off RESET Pushbutton 1st Out Reset Steady Steady Off Normal O...

Page 19: ...art Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Reset Off Off Condition LED Horn Normal Off Off Alert Flash On ACK Pushbutton Acknowledge Steady Off Normal Steady Off RESET Pushbutton Normal Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert F...

Page 20: ...teady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady Off RESET Pushbutton Normal Off Off Off Condition Normal 1st Pt LED Off Next Pt LED Off Horn Off Return to Normal Reset while Normal Condition Alert 1st Pt LED Flash Next Pt LED Steady Horn On Condition Norm...