AN24 & AN28 Annunciators  

 

Instruction Manual 

 

 

Power Connections 

Power connections are made to a two-terminal 
connector labeled POWER. See 

Connectors Labeling

 

on page

 8

The instrument will operate regardless of 

DC polarity connection. The + and - symbols are only a 
suggested wiring convention. 

AC or DC

POWER

Recommended External Fuse:

5 A max, Slow Blow

POWER CONNECTOR

+

-

 

Figure 8. Power Connections 

 

Signal Connections 

Input signal connections are made to a 14-terminal 
connector at terminals labeled INPUT CHANNELS. 
See 

Connectors Labeling

 on page

 8

. The COM 

(common) terminal is the return for all types of input 
signals. 

Normally Open (NO) or Normally 
Closed (NC) Switches 

The following figure shows an example of normally 
open or normally closed contact inputs. 
Programming a channel for a normally open or 
normally closed contact is done with the front panel 
pushbuttons (see page 

12

). All channels are initially set 

for normally open contacts. Each contact is wired 
across an input channel and common. 

COM

SIGNAL CONNECTOR

CH3

CH1

CH2

CH4

NO

CONTACT

NC

CONTACT

 

Figure 9. NO/NC Contact Inputs 

Open Collector NPN Transistor 

Each transistor collector is connected to a separate 
input channel and all emitters connected to common. 
All channels are factory set for transistor inputs 
normally in the cuto

ff or “off” state. For normally 

active/saturation state or “on” transistors, program 
inputs for normally closed input operation; see page 

12

. 

Open circuit voltage is approximately 3.3 VDC provided 
by a 47 k

Ω internal pullup resistor. 

The following figure shows an example of open 
collector NPN transistor inputs. 

COM

SIGNAL CONNECTOR

CH3

CH1

CH2

CH4

NPN

Transistor

C

B

E

C

B

E

 

Figure 10. Open Collector NPN Transistor Inputs 

Logic Level Inputs 

Each logic level input is connected to an input channel 
with common as the return. 
Logic level inputs are factory set for normally high 
active logic level inputs. For normally low input logic 
levels, program inputs for normally closed input 
operation, see page 

12

 

Logic Level Low:  0 to 1.4 VDC 
Logic Level High:  1.5 to 28 VDC 
Input Impedance:  Approximately 47 k

Ω 

Relays and 24 V Output Connections 

Relay connections are made to a six-terminal 
connector labeled RELAY1 and RELAY2. See 

Connectors Labeling

 on page

 8

. The COM (common) 

terminals of the relays should not be confused with 
the COM (common) terminal of the signal connector. 
The 24 VDC output is available at the connector 
labeled 24V OUT, next to the relays connector. 

24V OUT

P+

P-

RELAY 2

RELAY 1

NC

NC

C

NO

C

NO

 

Figure 11. Relay & 24 V Output Connections 

Summary of Contents for AN24 Series

Page 1: ...cluding First Out Multiple Unit First Out Indication Free Custom Message Labels Silence Acknowledge and Reset Functions Sunlight Readable Indication Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply AC Models 2 SPDT Relays for Alarm Activated Devices Operating Temperature Range 40 to 65 C 40 to 149 F UL C UL Listed E160849 508 Industrial Control...

Page 2: ...ll not exceed the purchase value repair or replacement of the defective unit See Warranty Information and Terms Conditions on www dwyer inst com for complete details 2020 Dwyer Instruments Inc All rights reserved Introduction The Series AN24 AN28 is a multipurpose panel mounted alarm annunciator available for four or eight inputs It can be set up to respond to alarm conditions based on 8 field sel...

Page 3: ...Overview 11 Front Panel Pushbuttons and Status LED Indicators 11 Full Function Test 11 Multiple Unit First Out Indication 11 Shared Front Panel Buttons 11 Annunciator Sequence Selection 12 Sequence Programming 12 Sequence Descriptions 12 Normally Open Normally Closed Input Setup 12 Programming NO NC Inputs 12 NO NC Programming Example 13 Relay Operation 13 Relay 1 Operation 13 Relay 2 Operation 13...

Page 4: ...r Labeling for AN24 1 8 Figure 6 Connector Labeling for AN28 1 8 Figure 7 Connector Labeling for AN24 2 8 Figure 8 Connector Labeling for AN28 2 8 Figure 9 Power Connections 9 Figure 10 NO NC Contact Inputs 9 Figure 11 Open Collector NPN Transistor Inputs 9 Figure 12 Relay 24 V Output Connections 9 Figure 13 AC and DC Loads Protection 10 Figure 14 Low Voltage DC Loads Protection 10 Figure 17 Syste...

Page 5: ...n to normal operation with the programmed input types Basic Connections All connections are made to removable screw terminal connectors located at the rear of the instrument For complete connection details see page 8 Use copper wire with 60 C or 60 75 C insulation for all line voltage connections Observe all safety regulations Electrical wiring should be performed in accordance with all applicable...

Page 6: ...humidity 0 to 90 non condensing Connections Removable screw terminal blocks for 12 to 22 AWG wire Enclosure 1 8 DIN high impact plastic UL 94V 0 front color black Mounting 1 8 DIN panel cutout required Two panel mounting bracket assemblies provided Tightening Torque Screw terminal connectors 5 lb in 0 56 Nm Overall Dimensions 4 68 x 2 45 x 4 19 62 mm x 119 mm x 106 mm H x W x D Weight 9 6 oz 272 g...

Page 7: ...trained service personnel Installation There is no need to remove the instrument from its case to complete the installation wiring and setup Unpacking Remove the instrument from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the unit malfunctions please contact your supplier or the factory for assistance Panel Mounting Prepare a sta...

Page 8: ...y regulations Electrical wiring should be performed in accordance with all applicable national state and local codes to prevent damage to the instrument and ensure personnel safety Connectors Labeling The connectors label affixed to the instrument shows the location of all connectors available with requested configuration Figure 4 Connector Labeling for AN24 1 Figure 5 Connector Labeling for AN28 ...

Page 9: ... input channel and all emitters connected to common All channels are factory set for transistor inputs normally in the cutoff or off state For normally active saturation state or on transistors program inputs for normally closed input operation see page 12 Open circuit voltage is approximately 3 3 VDC provided by a 47 kΩ internal pullup resistor The following figure shows an example of open collec...

Page 10: ... Snubbers Available from Dwyer RC networks are available from Dwyer and should be applied to each relay contact switching an inductive load Part number PMA 09 External Input Types The external Silence SIL Acknowledge ACK and Reset RST inputs may be contacts i e pushbuttons relay contacts etc open collector inputs OC or TTL signals However throughout this manual the term pushbutton is used to descr...

Page 11: ...h reset acknowledged channels automatically See selected sequence details for complete function description see Full Sequence Descriptions page 16 LED TEST SILENCE ACK Press and release the SILENCE and ACK pushbuttons to flash the channel indicator LEDs for a lamp test Full Function Test Press and hold SILENCE and ACK for 5 seconds to perform a function test This tests the sequence operation and h...

Page 12: ...Alarm Conditions for normally closed inputs 1 An open contact between an input channel and common will cause an alarm condition 2 An off or cutoff state transistor between an input channel and common will cause an alarm condition 3 An active logic level high or no supplied active logic level on an input channel will cause an alarm condition Programming NO NC Inputs 1 Press and hold ACK and RESET f...

Page 13: ...ed Relay Fail Safe In fail safe operation a relay coil is energized in non alarm condition In case of power failure relays will go to alarm state Fail safe operation is set independently for each relay Programming Relay Fail Safe 1 Press and hold ACK and RESET for 3 seconds When all LEDs cycle release 2 Press RESET within 3 seconds of release while LEDs cycle 1 3 Press RESET within 3 seconds of re...

Page 14: ...ble disable option see page 14 and no lock in option see page 15 Relay Operation Overview The following figure illustrates the operation of the relays ACK Pressed ON OFF Relay 1 ON OFF Relay 2 ON OFF Relay 1 ON OFF Relay 2 NORMAL FAIL SAFE Alarms Cleared Alarm Occurance Relay On Relay is energized Relay Off Relay is de energized Alarm Occurrence A new alarm occurs when there is no previous unackno...

Page 15: ...to return to operation The green power LED will blink quickly to indicate the unit is in the advanced programming mode The unit will automatically leave setup mode if no pushbutton is pressed for 3 minutes Note LED 1 and 2 are used for relay fail safe setup see page 13 and LED 3 is used for silence pushbutton enable disable see page 14 1The unit will automatically leave setup mode if steps 2 and 3...

Page 16: ...input is in alarm state and the channel has not been acknowledged with the ACK pushbutton Acknowledge The alarm state is acknowledged with the ACK pushbutton This will restart the first out indication First Out Reset F3A Only The RESET pushbutton is used to reset the first out indication only Normal Inputs are in the normal state LED Condition Descriptions 1st Pt Indicates the behavior of the firs...

Page 17: ...ady Steady Off Normal Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On Normal Flash Off On ACK Pushbutton Acknowledge Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Condition Normal 1st Pt LED Off Next Pt LED Off Horn Off Condition Alert 1st Pt LED Flash Nex...

Page 18: ... Off Off Alert Intermittent Flash Fast Flash On RESET Pushbutton 1st Out Reset Fast Flash Fast Flash On ACK Pushbutton Acknowledge Steady Steady Off Normal Off Off Off Maintained Alarm ACK before RESET Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Intermittent Flash Fast Flash On ACK Pushbutton Acknowledge Slow Flash Steady Off RESET Pushbutton 1st Out Reset Steady Steady Off Normal O...

Page 19: ...art Condition LED Horn Normal Off Off Alert Steady On Normal Off Off Condition LED Horn Normal Off Off Alert Flash On Normal Flash On ACK Pushbutton Acknowledge Steady Off RESET Pushbutton Reset Off Off Condition LED Horn Normal Off Off Alert Flash On ACK Pushbutton Acknowledge Steady Off Normal Steady Off RESET Pushbutton Normal Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert F...

Page 20: ...teady Steady Off RESET Pushbutton Reset Off Off Off Condition LED Horn 1st Pt Next Pt Normal Off Off Off Alert Flash Steady On ACK Pushbutton Acknowledge Steady Steady Off Normal Steady Steady Off RESET Pushbutton Normal Off Off Off Condition Normal 1st Pt LED Off Next Pt LED Off Horn Off Return to Normal Reset while Normal Condition Alert 1st Pt LED Flash Next Pt LED Steady Horn On Condition Norm...

Page 21: ...DWYER INSTRUMENTS INC Phone 219 879 8000 dwyer inst com P O BOX 373 MICHIGAN CITY IN 46360 U S A Fax 219 872 9057 e mail info dwyermail com LIM158DW_B SFT043 Ver 1 0 up 07 20 ...

Reviews: