4.10.2 Setting PCU Functions
A) Selecting Input Signal
- User can select different types of input signal by adjusting the DIP switches as follows:
4 - 20mA
NOTE: IF NOT SPECIFIED, THE FACTORY SETTING OF THE INPUT SIGNAL IS 4 - 20mA.
1 - 5V DC
2 - 10V DC
0 - 5V DC
0 - 10V DC
60 Hz
50 Hz
B) Selecting Output Signal
- User can select different types of output signal by adjusting the DIP switch as follows:
4 - 20mA
Input Signal
Switch:
Output Signal
Switch:
Input signal
switch 3 “ON”
0 – 10V DC
Input signal
switch 3 “OFF”
2 – 10V DC
Input signal
switch 3 “ON”
0 – 5V DC
Input signal
switch 3 “OFF”
1 – 5V DC
NOTE: IF NOT SPECIFIED, THE FACTORY SETTING OF THE OUTPUT SIGNAL IS 4 - 20mA.
C) Fail Position Setting
- User can select the fail position of the actuator in case of control signal failure by adjusting the DIP switches as follows:
FAIL CLOSE
Fail Position
Setting
Switch
FAIL OPEN
CH 2 Switch
CH 1 Switch
Auto-Full Switch
Fail Open Switch
Fail Close Switch
Fail Last Position