background image

TYPE 5370 

 I

NSTALLATION, 

O

PERATION

 

AND 

M

AINTENANCE MANUAL

 

TYPE 5320 

Mechanical limit switch with valve and LED 

Summary of Contents for 5370

Page 1: ...TYPE 5370 INSTALLATION OPERATION AND MAINTENANCE MANUAL TYPE 5320 Mechanical limit switch with valve and LED ...

Page 2: ...sonal injury caused by the rotating parts of equipment 电危险 Danger in normal operation of equipment Danger High Voltage The stipulation should be complied with in order to ensure safety production 1 4 General safety instruction Please read the operation manual carefully before installing and operating Type 5370 If any question please contact with DVC During installation The technical specification ...

Page 3: ...air source has been disconnected Do not put the detached scattered parts on the floor All the operation related with electric power shoulded be operated by the authorised professionals C Co on nfo for rm m t to o in ins st tr ru uc ct tion ion Any behaviour not comply with instruction will cause danger to operator environment and machine Meanwhile you perhaps lose the right to claim for your loss ...

Page 4: ... working position of valve It has 2 kinds of sensors Displacement continuous sensor 2 Operating principle Type 5370 is controller including signal transmission and LED position indicating light used for controlling process valve of all kinds Information collection is come from PLC or the signal of other automatic control equipment which could turn the valve on and off and reflect the current posit...

Page 5: ...tion Blue LED light indicating the valve is turned on Red LED light indicating the valve is turned off Bus communication AS I BUS C TOP 1561 33 AS I Bus version is euipped with the following function Signal selection Tacit approval Red LED light flickers indicating it doesn t reach target position or valve position is deviated by pipeline pressure etc 04 15 ...

Page 6: ...on setting and button operation Manual operation LED lights 2 colors BSPT 1 8 Note 1561 control the internal setting of two 3 way solenoid valve 1 When a single acting pneumatic valve with a plug plug one of the working mouth 2 double acting pneumatic valve is no need to plug the working mouth Right key Left key 05 15 ...

Page 7: ...uitable for initial use and also for routine maintenance Manual operation function Triggering the right button will immediately start the solenoid valve valve position The LED lights up when the valve position reaches the target valve position Position feedback signal can be output S1 S2 such as DC 24V PNP 4 20mA analog output signal Green LED lights Green light on mean valve opened or closed Note...

Page 8: ...ng exercise of the actuator Was externally or piped to the valve position 1 loosen the 4 screws until the housing is open 2 the default sensor plug plastic outward as shown in the figure 3 Unplug the plug reinsert it and plug the metal face outwards Note The display light color reset the following steps A 07 15 ...

Page 9: ...the destination is intact So received the Type 5370 and other items must be check If the product is not good or spare parts not neat the consignee should be in the shortest possible time 7 days notify DVC 4 2 Delivery and disassembly 4 2 1 Delivery Check whether all parts in the delivery list is complete 4 2 2 Disassembly Remove possible exit packaging residues Check Type 5370 and accessories to e...

Page 10: ...rotates counterclockwise and remove the transparent cover Remove the four screws with an Allen wrench Rotate counterclockwise by hand and remove the transparent cover Remove the rubber position indicator with the appropriate tool 09 15 ...

Page 11: ... to the actuator 4 Type 5370 is connected to the actuator 5 1 1561 156133 Version is connected to the actuator Note We use a very simple way to connect only in accordance with the standard M6 hex screws can be connected connected 10 15 ...

Page 12: ...ndard configuration AS INTERFACE BUS protocol communication Electronic component All of the electronic components in the control device of Type 5370 are equipped with built in pin connectors which avoid unnecessary wiring and interference According to standard a PCB could be connected with 3 solenoid valves V1 V2 V3 at most and with 4 output of position feedback Input Signal input 24V control pane...

Page 13: ...4 6 1 PCB PCB Terminal Features 1 24V DC 2 24V DC 3 V1 INPUT PNP 24V 4 S1 Output PNP 24V 5 S2 Output PNP 24V 6 A Analog signal output 4 20mA 7 A Analog signal output 4 20mA ...

Page 14: ... be connected with 62 AS I control units at most support model A and B In default situation configuration as follows Programming in default situation the address is 1 And the address could be edited at will by master controller or address editor Before using Type 5370 please note the following matters Type 5370 should be installed on the valve actuator correctly and tightly Otherwise water will be...

Page 15: ... controller Air pressure is not enough To increase supplied air pressure With air but the solenoid doesn t work To inspect if the power is on The interior of actuator is polluted To inspect compressed air pressure and pipeline Without position signal The position of valve shaft hasn t been detected by the detector To adjust the height of detector To inspect if the detector is normally connected wi...

Page 16: ...essure 1 5 to 7 bar 22 to 102 PSI Standard flow 200 l min to 6 bar 20 ºC the pressure difference is 1bar to 87 PSI 74 F the pressure difference is 87 PSI 1 working mouth 2 working mouth 2 working mouth Cable Connector G1 8 The silencer will be supplied together with it Max temperature of air source Transparent lid cover M5 The commonly used plug equipped with 6 4 pipes will be supplied together wi...