13
RMO600
Getting Started
Seting printer, as well as look of RMO Test Report where given at figures below.
6.8 Duty Cycles
During tests, RMO600 generates a high DC current that heats up the test set.
To prevent RMO600 from overheating, certain duty cycles apply depending on
the used test current.
S i n g l e T e s t
Test current
(A)
Cooling time between
first 4 tests (sec)
Cooling time after
4 tests (sec)
10, 20, 50
100, 200
0 0
300 5 20
400 10 30
500 20 60
600 30 90
C o n t i n u o u s T e s t
Test current
(A)
Maximal test
duration
time (sec)
Cooling time
between tests (sec)
10, 20, 50, 100
300 0
200 150 200
300 90 300
400 50 400
500 30 500
600 20 600
A built-in control prevents these cooling times from being skipped. If you try to
start a test within the cooling period, the display shows "Wait" and a timer
counting down. After the cooling period has elapsed, start the test using the set
test parameters by pressing the
Ω
button. Cooling of RMO600 is supported by
a built-in fan that is automatically activated every time a test is started from the
Test
menu. It continues running 5 minutes after the test is finished.
Table 6-11:
Cooling time
between
single
tests
Table 6-12:
Cooling time
between
continuous
tests