DUYAR OPUS 0-12 280 V Installation Operation & Maintenance Download Page 12

10

OPUS 

SERIES

INSTALLATION, OPERATION, MAINTENANCE 

AND REPAIR MANUAL

10.2 Terminal Connection Detail Param eter List

Para eter

De

on

Se n

P1

Image Selection

0 - Watts

1 - Meter (Mt)

2 - Current (A)

3 - Speed (Rpm)

P2

P3

Device Max. watts

P4

Target Frequency in

Manual Operation

1500 - 4600 Rpm

P5

Operating Meter Value 2.0 - 15.0 Mt

P6

Operating mode

0 - Automatic Variable Pressure

1 - Automatic Constant Pressure

2 - Manual Operation

3 - Automatic Night Mode

P7

Night mode operating

speed

1700 - 4600 Rpm

P8

Cross-device Master / 

Slave selection

0 - 4

P9

Device BMS

communication

addresses

0 - 255

P14

Factory reset

0 - 1

P15

Relay Mode

0 - Dysfunctional (Does not pull relay)

1 - inverter in fault mode

2 - Inverter running

3 - Inverter in stop state

4 - inverter in variable pressure mode

5 - Inverter in constant pressure mode

6 - Inverter in manual mode

7 - Inverter in night mode

P16

DN1 selection

0 - Dysfunctional device (It works according to its own setting)

1 - The device will start from digital 1. (in mode set in P6)

2 - The device will start-stop from digital 1. It will work according to the

max power

3 - The device will start-stop from digital 1. It will work according to the

max RPM

4 - The device will start-stop from digital 1 and from the buttons on it in

Manual mode

P17

DN2 selection

0 - Dysfunctional device (It works according to its own setting)

1 - The device will start from digital 1. (in mode set in P6)

2 - The device will start-stop from digital 1. It will work according to the

max power

3 - The device will start-stop from digital 1. It will work according to the

max RPM

4 - The device will start-stop from digital 1 and from the buttons on it in

Manual mode

P40

latest error

F1……20 Latest 20 errors

P1

Image Selection

0 - Watts

1 - Meter (Mt)

2 - Current (A)

3 - Speed (Rpm)

P3

Device Max. watts

p

P5

Operating Meter Value 2.0 - 15.0 Mt

P7

Night mode operating

speed

1700 - 4600 Rpm

P9

Device BMS

communication

addresses

0 - 255

P15

Relay Mode

0 - Dysfunctional (Does not pull relay)

1 - inverter in fault mode

2 - Inverter r

r unning

3 - Inverter in stop state

4 - inverter in variable pressure mode

5 - Inverter in constant pressure mode

6 - Inverter in manual mode

7 - Inverter in night mode

0 - Dysfunctional device (It works according to its own setting)

DN2 selection

P17

1 - The device will start from digital 1. (in mode set in P6)

2 - The device will start-stop from digital 1. It will work according to the

max power

3 - The device will start-stop from digital 1. It will work according to the

max RPM

4 - The device will start-stop from digital 1 and from the buttons on it in

Manual mode

Summary of Contents for OPUS 0-12 280 V

Page 1: ...SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL OPUS...

Page 2: ...2 OPUS SERIES INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL www duyarpompa com...

Page 3: ...ng and Air Drain 8 6 4 Cable Fuse Selection and Electrical Installation 8 7 DISPLAY AND SETTINGS 10 7 1 Operating Modes 11 7 1 1 Manual Operating Mode 11 7 1 2 Constant Pressure Operating Mode 11 7 1...

Page 4: ...should be as in Table 3 2 3 4 Operating Conditions OPUS circulation pumps have been developed for the circulation and pressurization of the water circulating in the heating and air conditioning system...

Page 5: ...code Tracking Number 7 Input Voltage Voltage 8 Minimum Power 9 Minimum Current 10 Temperature Class 11 Input Frequency 12 Maximum Power 13 Maximum Current 14 Serial number 15 QR Code 16 Year of produc...

Page 6: ...installation pressure should be between the values in Table 5 1 and Table 5 3 The pump must be operated for a while to drain the air from the installation 6 4 Cable Fuse Selection and Electrical Inst...

Page 7: ...ichever type of pump is to be used it must be selected according to the nominal current and voltage of that pump and a B type relay which can open at DC current and high frequency Grounding current sh...

Page 8: ...conds to set the target speed in night work When the P7 option is reached with the button when the target speed is reached with the keys by pressing the P button again the speed record is made by keep...

Page 9: ...ng remains constant The Hsetting value of the pumps selected in accordance with the operating point is determined as follows The H value at the operating point is marked on the constant pressure opera...

Page 10: ...selected on the screen in 0 5 meter increments 9 4 Operating Mode Selection Criteria The operating mode is selected by considering the criteria in the table below Table 9 1 Operating Mode Selection Cr...

Page 11: ...INSTALLATION OPERATION MAINTENANCE AND REPAIR MANUAL 9 10 TERMINAL CONNECTION DETAIL 10 1 Terminal Connection Detail Table 230 VAC DIN1 Communications BSM RS485 Relay Link DIN2 communication devices...

Page 12: ...will start stop from digital 1 and from the buttons on it in Manual mode P17 DN2 selection 0 Dysfunctional device It works according to its own setting 1 The device will start from digital 1 in mode s...

Page 13: ...tor do notr otate at synchronous speedd ue to the instantaneousc hange in load Checkt he suitabilityo ft he installation water flow direction with the arrowm arko nt he pump body W aitf or thep umpt o...

Page 14: ...2 180 50 182 232 300 8 80 OPUS D 32 12 180 2 180 50 182 232 300 8 80 PUMP TYPE D1 D2 D3 D4 D5 nx m mm L1 H1 H2 H3 H4 Weight PN6 PN10 PN6 PN10 OPUS 40 10 220 C 150 100 110 90 44 130 4x14 4x18 220 65 1...

Page 15: ...e will be filled by the authorized DUYAR POMPA dealer from where the device was purchased and sent to DUYAR POMPA and a copy will be given to the user During the warranty period the warranty certifica...

Page 16: ...equest is not fulfilled the seller the manufacturer and the importer are jointly and severally liable 6 The repair period of the goods cannot exceed 20 working days This period starts from the date of...

Page 17: ...STAINLESS BOOSTER FIRE BOOSTER DNP HORIZONTAL END SUCTION PUMP SINGLE STAGE END SUCTION CLOSED WHEEL ELECTRIC OR DIESEL ENGINE AXIAL TYPE PUMP MoreDetails...

Page 18: ...2021 11 1 WE ARE SENSIBLE TO LIVE...

Reviews: