Dust Free Bio-Fighter VersaLight 1SVL14 Installation & Operation Manual Download Page 3

BIO-FIGHTER® VERSALIGHT 1S, 2S INSTALLATION & OPERATION MANUAL

3

UV-C Light May Degrade Plastic and Rubber.

Shield exposed plastic drain pans, wire insula-
tion, flex duct, or other plastic/rubber compo-
nents from UV-C light. 

SELECTING A LOCATION

This device installs in the air handling system
and is best suited for hallway closet upflow
applications or applications where space in
front of the AHU is very limited. Select a
mounting location with enough clearance for
the lamp to be installed and replaced easily.
Allow approximately 14"-20" depending on
lamp length.

A 120V or 240V electrical supply is required.
Any modification to the supplied power cord
will void ETL safety listing and Dust Free®
warranty. Accessory 240V power cord
(#06205) is required for 240V electrical out-
lets. If an electrical outlet is not available,
accessory whip-type power cord (#06303) is
available for hard-wiring the device to power.

CAUTION

UV-C Light Hazard.

UV-C light can cause temporary or permanent loss of
vision, and sunburn. 

To prevent exposure, do not

install device in any applications that allows UV-C
light to be visible after installation. 

WARNING

Special Installation Notes

• Do not install in closet return grille applications.

• Do not install in outdoor applications.

Do not expose wiring or plastic parts to UV-C light.

• Do not install where UV-C light can be seen

after installation.

Do not install beneath a humidifier.

If the UV device is installed on the inlet side

(return air side) of a coil, make sure that the
HVAC system is configured such that the
blower is located between the return air filter
and the inlet side (return air side) of the coil,
such as would be found in a traditional up-
flow, or horizontal furnace with the coil
placed after the heat exchanger.

If the UV device is installed near an air filter,

check with filter manufacturer for UV-C
resistance properties.

If the desired UV installation location is

intended to irradiate an air filter, to neutralize
the microbiological matter on the air filter
surface, such as would be found in the
return air drop of a basement application or
in the return plenum of a horizontal system
in an attic; take precautions as described in
note above, and make sure the UV fixture is
placed on the return side of the filter. DO
NOT INSTALL THE UV FIXTURE ON EITHER
SIDE OF THE FILTER IN HALL / CLOSET
RETURN AIR APPLICATIONS. 

(See ATTEN-

TION! Warning sheet #212

945

-00).

Fig. 1

Use included mounting screws to install device at desired

location.

BASE MOUNTING 

(Fig.1)

Place the base at the desired location and use
the included mounting screws to install the
base to the surface.

FUSE

®

Summary of Contents for Bio-Fighter VersaLight 1SVL14

Page 1: ...This process either destroys the micro organism or neutralizes its ability to reproduce FEATURES Reduces or prevents mold growth on HVAC coils allowing them to operate at peak effi ciency Also significantly reduces bacteria viruses fungi and yeasts in the ductwork High output long life UV C lamps Remote mount lamp configuration Multi input voltage electronic ballast Odor control O3 lamps available...

Page 2: ...achable power cord Listings FIFRA File 73316 Federal Insecticide Fungicide Rodentcide Act ETL Safety Agency File 2002554 U S Patent Nos 5 334 347 5 817 276 6 245 293 6 267 924 6 280 686 6 313 470 6 627 000 6 539 727 6 932 494 6 550 257 Specifications subject to change without notice 13 2 625 3 1 25 3 625 Remote Lamp Housing 4 5 3 437 ETL LISTED CONFORMS TO UL STD 1598 CERTIFIED TO CSA STD C22 2 NO...

Page 3: ...ations Do not install in outdoor applications Do not expose wiring or plastic parts to UV C light Do not install where UV C light can be seen after installation Do not install beneath a humidifier If the UV device is installed on the inlet side return air side of a coil make sure that the HVAC system is configured such that the blower is located between the return air filter and the inlet side ret...

Page 4: ...MOTE LAMP HOUSING Fig 4 After lamp has been installed reinstall the remote lamp housing using the knurled nuts The remote lamp housing must be in place prior to attaching the electrical harness Clean lamp s prior to installation Failure to remove dirt and fingerprints from the lamp s could shorten their lifespan CAUTION UV C Light Hazard UV C light can cause temporary or permanent loss of vision a...

Page 5: ...s does not attach easily rotate 90 degrees and try again After the harness connector is attached slide the protec tive boot over the lamp connector The protec tive boot fits snugly over the lamp and seals the connection from moisture dust etc INSTALLING THE VIEWPORT The VersaLight comes with a UV C safe view port that must be installed separately To install the viewport select a location near the ...

Page 6: ...UV C light can cause temporary or permanent loss of vision and sunburn Take precautions to protect eyes and skin from direct exposure WARNING LAMP REPLACEMENT Annually The lamp should be replaced annually even if it appears to be operating normally UV C energy production diminishes over time 1 Obtain the correct replacement lamp for your model 2 Disconnect power to the equipment 3 Open the cover o...

Page 7: ...VE AND DUST FREE LP EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES WHETHER WRITTEN OR ORAL IMPLIED OR STATUTORY INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY WORKMAN SHIP OR FITNESS FOR A PARTICULAR USE If the limited warranty is void due to failure to use a quali fied contractor all disclaimers of implied warranties shall be effective upon installation How to make a warranty claim or h...

Reviews: