L
N
PE
600
60
0
2250
*
0
1
2
en
10
Connect whirltub
NOTICE
Malfunctions due to incorrect
installation
>
Do not fasten the cables together with cable ties.
>
Do not install the supply line parallel to the control
cables.
I
Connect the supply line to the mains supply socket.
II
Connect the potential equalisation cable to the
whirltub.
*
or the height of
the highest shower
head / water outlet
that is permanently
installed, depending
on which is higher
Safety areas in accordance with DIN VDE 0100-701
Pre-Installation
>
Installing a permanent power supply line:
λϡ
Install separate circuit breaker and residual-current
circuit breaker (RCCB) upstream
λϡ
Connect all pole disconnector mains switches up-
stream located outside specified protection zones (0
- 2)
λϡ
Leave 3 000 mm of feed cable exposed
>
Lay equipotential bonding cables:
λϡ
Leave 3 000 mm of cable exposed
76xxx xx x xx00: 50 Hz, 220 - 240 V AC
76xxx xx x xx06: 60 Hz, 220 - 240 V AC
I
N
= 16 A
I
ΔN
≤ 30 mA
Power supply
Circuit breaker
RCCB
Electrical installation
WH_M_Vero Air_FST/17.05.2
7
II
I