Electrical installation
Water installation
Position of electrical connection
Pre-Installation
> Lay a permanent power supply line:
λϡ
Please observe the position of the electrical connec-
tion
λϡ
Leave at least 800 mm (31½") of feed cable exposed
> Install circuit breaker
λϡ
Connect a separate upstream circuit breaker
λϡ
Connect an upstream residual current device (RCD)
separating all poles
> Appliances have to be correctly earthed.
13
Connecting the cable (Diagram 13)
> Please observe the L, N and PE conductors.
15
Installing junction box (Diagram 15)
> Fix the junction box in the toilet in the designated
place.
60 mm
60 mm
32
5 mm
IG 1/2”
2
3
/
8
"
2
3
/
8
"
12
13
/
16
"
Pre-Installation
> Install the water connection and water outlet in the
specified areas.
DANGER!
Health risk and potential product damage.
> Supply the Shower WC with cold drinking water from
the main water system.
> Do not connect any waste water, grey water, industrial
water, sea water or other untreated or semi-treated
water.
7
Connecting the water (Diagram 7)
NOTE! Avoiding any malfunctions!
> Only use the water supply hoses provided.
Power supply
# 610... .. 2 .. ....
220 – 240 V ~ 50/60 Hz
Power supply
# 610... .. 1 .. ....
100 - 120 V ~ 50/60 Hz
Max. rated power
1.65 kW
Circuit breaker
I
N
= 16 A
RCCB
I
N
= 30 mA
Protection type
IP X4
Protection class
1
Cold water
DN 15(1/2")
Water pressure
0.07 – 0.75 MPa
(10 – 109 psi)
Water hardness
max. 2.4 mmol/l (240 ppm)
NOTE!
> Install a water softener with water hardness
≥ 2.4 mmol/l (≥ 240 ppm).
5
SensoWash_MAL_1pWC_54040/16.07.6
en