Electrical installation
L
N
PE
14
Connecting the whirltub (Diagram 14)
NOTICE
Malfunctions due to incorrect
installation!
> Do not fasten the cables together with cable ties.
> Do not install the supply line parallel to the control
cables.
I
Connect the supply line to the mains supply socket.
II
Connect the potential equalisation cable to the
whirltub.
* or the height
of the highest
shower head /
water outlet that
is permanently
installed,
depending on
which is higher
Pre-Installation
> Installing a permanent power supply line:
λϡ
Install separate circuit breaker and residual-current
circuit breaker (RCCB) upstream
λϡ
Connect all pole disconnector mains switch upstream
located outside specified protection zones (0 - 2)
λϡ
Leave 3000 mm of feed cable exposed
> Laying an equipotential bonding cable:
λϡ
Leave 3000 mm of cable exposed
Safety areas in accordance with DIN VDE 0100-701
600
60
0
2250*
0
1
2
76xxxx xx x xx xx00: 50 Hz, 220 - 240 V AC
76xxxx xx x xx xx06: 60 Hz, 220 - 240 V AC
I
N
= 16 A
I
ΔN
≤ 30 mA
Power supply
Circuit breaker
RCCB
II
I
Summary of Contents for Cape Cod 70362 Series
Page 30: ...ru Duravit 10 www pro duravit com 19 19 10 10 24 24 30 WH_M_DuraSolid_corner_b2w 17 05 6...
Page 44: ...bg Duravit 10 www pro duravit com 19 19 10 10 24 24 44 WH_M_DuraSolid_corner_b2w 17 05 6...
Page 52: ...K XUDYLW ZZZ SUR GXUDYLW FRP B0B XUD6ROLGBFRUQHUBE Z...
Page 53: ...K B0B XUD6ROLGBFRUQHUBE Z L N PE PP 9 P 5 PP 1 PP 1 9 600 600 2250 0 1 2 9 9 1 1 P 5...
Page 54: ...ko Duravit www pro duravit com 19 24 54 WH_M_DuraSolid_corner_b2w 17 05 6...
Page 56: ...ja Duravit www pro duravit com 19 24 56 WH_M_DuraSolid_corner_b2w 17 05 6...
Page 58: ...ar Duravit ZZZ SUR GXUDYLW FRP 19 24 58 WH_M_DuraSolid_corner_b2w 17 05 6...
Page 62: ...kg 62 WH_M_DuraSolid_corner_b2w 17 05 6 19 20 16 17 18 13 14 15 10 12 11...
Page 63: ...1 5 0 WH_M_DuraSolid_corner_b2w 17 05 6 63 21 23 22 25 24...