-9-
IV. MINIMUM FIREBOX DIMENSIONS
WARNING: Maintain or exceed the minimum clearances.
V. CLEARANCES (Vent-free operation only)
WARNING: Maintain or exceed the minimum clearances.
VI. INSTALLING DAMPER STOP (Vented operation)
For vented operation of this appliance, a damper stop must be installed in the fireplace to prevent
full closure of the damper blade. The damper stop must be adjusted to provide a minimum flue
opening of 29 square inches. You can obtain a damper stop at your local hearth products dealer
or hardware store.
WARNING: The fireplace and log set function as a system. If the fireplace is spilling
combustion gases into the room (check draft with a match, candle or smoke stick), reposition
the damper clamp to open the damper wider, until a positive draft (i.e. all combustion
emissions go up the chimney) is obtained.
VII. INSTALLATION
1. Carefully remove the contents of the carton. You should find:
• The burner / base (Figure 1)
• Four (4) ceramic fiber artificial logs (Figure 3).
• Two (2) appliance base screws inside a small bag.
• One AA battery.
If components are missing, contact Duraflame Consumer Affairs.
2. Remove all these components from their packaging. When handling the logs, take care not
to damage them. Keep packing materials away from children, as they could be a choking or
suffocation hazard.
Figure 2
Minimum Dimensions of Firebox
Firebox Back
Firebox
Side
19”
18”
31”
15”