The positioning of the sensor is an important factor for the correct function of  the gas detection 

control unit.

In order to obtain the best results and minimize the probabilities of false alarms, we recommend 

following this diagram and to keep in mind the following general rules.

The probe should be placed at a height of about 1.60 cm from the ground, if the height of the room 

is higher than 2.8m it is recommended to install it at an average height between ceiling and floor.

The sensor should not be fitted where it is likely to be affected by smoke, vapour, etc. as they could 

distort indicated measurements. 

The sensor must be placed away from sources of heat, suction fans, ventilation fans.

The general test should be performed by issuing gas from a pre-calibrated bottle within the 

percentages marked on the bottle information label. Important: This test must be carried out 

at least once a year or more frequently if required based on a risk assesment of the setting.  

Positioning  of the Sensor 

Unlock hole

Note !

When is mounted on the wall, the orientation is obligatory, See pictures below.

Gas Testing

Unlock hole

Test  Gas Concentrations for testing the SGF104 Oxygen sensor:

DEFICIENCY OXYGEN  18% vol

 OXYGEN 

 20,95 vol

EXCESS OXYGEN  24% vol   

Important - Test with calibrated gas only!

Ceiling mounted

X

Summary of Contents for SGF 104

Page 1: ...des a signal proportional to the levels of oxygen to either a Duomo central control from the GS or BX range or directly to Building Mana gement Systems Operation The self calibration facility allows the probe to adapt in difficult environments and variable temperatures helping to avoid false alarms By connecting a datalogging and diagnostic tool Duomo TS1007 to the sensor It is possible to read ba...

Page 2: ... Power demand 110 mA in alarm Max 13 8VDC Relay switching alarm 1 A 30VDC SELV Selection of positive safety Selectable by switch Type of gas detected Oxygen Integratedsensoraccordingtothetypeofgas Opticalfluorescence Operating range of the sensing element 0 25 of O2 Operating range selectable by switch 19 5 or 18 5 of O2 depletion 22 5 23 5 of O2 Excess Note1 Detector accuracy 1 FS Long term shift...

Page 3: ...of fire and explosion because it enhances the combustion If the concentration of the O2 in air drops below 19 5 it is considered deficient for health of pe ople then if the concentration drops below 16 it causes breathing problems until to cause the asphyixia and below 6 it causes the immediate death Oxygendeficiencycanbecausedbytheincreaseintheairofothergases toxicand or flammable and also from t...

Page 4: ...e percentage of dispersed gas Displays if the probe is in fault Indicates if you want to print the ticket Indicates if you want to reset the probe to the data factory Asks to save the modified data Indicates when the battery is low 1 ADC 80 16 125 145 probe sgF104 sn 24ad12 date 15 2014 DaY 2190 cy 5 al 15 drift 12 range 20 lel 20 fault print tar new save low bat unlock pivot C NC NO R Gas probe S...

Page 5: ...r etc astheycould distort indicated measurements The sensor must be placed away from sources of heat suction fans ventilation fans The general test should be performed by issuing gas from a pre calibrated bottle within the percentages marked on the bottle information label Important This test must be carried out at least once a year or more frequently if required based on a risk assesment of the s...

Page 6: ...een pinched Check the voltage between terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check the voltage between terminals 2 3 It must be a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Important Note These measurement should be perfor med in clean fresh air Moreover this test must be perfor med only with the probe connected to a control unit or with a 220 Ohm resistance instal...

Page 7: ... Pivot Gas probe SGF100 S N ED567D Year 06 2015 Batch SGF104 001 Gas Oxygen Power supply 12 24VDC Absorption 110 mA Relay 1A 30V SELV Signal 4 20 mA USB data detection Operating range 20 Positive safety OFF Positive safety ON Operating range 100 When it is mounted on the wall UP DOWN Power supply Relay Relay max 1A Power supply 30 VDC SELV detection 4 20 mA Note The relay is voltage free Contact c...

Page 8: ...he recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste han...

Reviews: