Important:

The installation of the SGF104, commissioning, service and removal must be carried out by 

authorized and/or specialized personnel. During installation the sensor enclosure must not be 

pierced to do so will compromise the protective rating protection.

The installation of the detector does not exempt the user from compliance with all regulations 

concerning the characteristics, installation and use of associated equipment. The ventilation 

of the spaces and, for example, the removal of combustion products are described in the UNI 

norms such as ART. 3 LAW 1083 / 71 and relevant legal provisions.

Do not allow the sensor to become wet.

The probe can be seriously damaged when immersed in water. Remember that the probe has 

an IP64 protection degree.

Handle with care 

Heavy knocks or falls during transportation or installation can damage the sensor.
Avoid abrupt temperature fluctuations. 

Sudden temperature variations can cause condensation and the probe could work poorly. Tem-

perature compenstation is fitted to this sensor but rapid changes will still affect the functionality. 

Cleaning Never clean the device with chemical products. Absolutely avoid using any cloth dip-

ped in thinners, alcohol and chemical detergents. The outer enclosure should only be cleaned 

using a damp cloth.

Power supply ....................................................................................................................... 12÷24 VDC ± 10%

Power demand  ...................................................................................... 110 mA in alarm Max @ 13,8 VDC

Relay switching alarm  ......................................................................................................... 1 A 30VDC SELV

Selection of positive safety........................................................................................ Selectable by switch

Type of gas detected: Oxygen

Integrated sensor according to the type of gas ...........................................................Optical fluorescence

Operating range of the sensing element   ..........................................................................0 - 25 % of O

2

Operating range selectable by switch ....................... 19.5 or 18.5% of O2 (depletion), 22.5, 23.5% 

of O

(Excess) Note

1

Detector accuracy ...............................................................................................................................+/- 1% FS

Long term shift in clean air  ...................................................................................................... < 3% of L.E.L.

Auto zero procedure  .................................................................... Included in the software algorithms

Response Time ............................................................................................................................................... < 10”

Functioning humidity  .............................................................................................. 0-90% not condensed

Functioning temperature  ..................................................................................................... -30°C to +60°C

Control units usable directly.................................................................................................... BX308, BX316

Control units usable with adapter code yy.............. BX444-Mc, BX449F, GS100M, BX180, BX280,   

           BX150, GS300M

Cable diameter for connecting probe - Note

2

............................................................ 1 mm for 100 mt

Section shielded cable transmission distance up to 500 meters .............................x0,75mm2CSA

Installation ................................................................................................................... ceiling or wall mounted

Anti-tamper protection ..................................................................................................................... included

Enclosure.................................................................................................... ABS self-extinguishing VDE0471

External degree of protection........................ IP64

Overall dimensions ...........................................Diameter 90 mm

, Depth 45mm

Electromagnetic compatibility Reference Norms ... EN 50270

Note

1

.

On SGF104 the trigger levels are dependant on the position of the DIP switch 2 selection. 

They are respectively 19.5% (depletion) and 22,5% (excess) - DIP2 in OFF position - or 18.5% 

(depletion) and 23,5% (excess) - DIP2 in ON position.

Note

2

Connection: The sensor cable must not be installed together with the power cables. If this is 

unavoidable it is imperative otherwise, make sure to use a shielded cable.

Technical Specification

Summary of Contents for SGF 104

Page 1: ...des a signal proportional to the levels of oxygen to either a Duomo central control from the GS or BX range or directly to Building Mana gement Systems Operation The self calibration facility allows the probe to adapt in difficult environments and variable temperatures helping to avoid false alarms By connecting a datalogging and diagnostic tool Duomo TS1007 to the sensor It is possible to read ba...

Page 2: ... Power demand 110 mA in alarm Max 13 8VDC Relay switching alarm 1 A 30VDC SELV Selection of positive safety Selectable by switch Type of gas detected Oxygen Integratedsensoraccordingtothetypeofgas Opticalfluorescence Operating range of the sensing element 0 25 of O2 Operating range selectable by switch 19 5 or 18 5 of O2 depletion 22 5 23 5 of O2 Excess Note1 Detector accuracy 1 FS Long term shift...

Page 3: ...of fire and explosion because it enhances the combustion If the concentration of the O2 in air drops below 19 5 it is considered deficient for health of pe ople then if the concentration drops below 16 it causes breathing problems until to cause the asphyixia and below 6 it causes the immediate death Oxygendeficiencycanbecausedbytheincreaseintheairofothergases toxicand or flammable and also from t...

Page 4: ...e percentage of dispersed gas Displays if the probe is in fault Indicates if you want to print the ticket Indicates if you want to reset the probe to the data factory Asks to save the modified data Indicates when the battery is low 1 ADC 80 16 125 145 probe sgF104 sn 24ad12 date 15 2014 DaY 2190 cy 5 al 15 drift 12 range 20 lel 20 fault print tar new save low bat unlock pivot C NC NO R Gas probe S...

Page 5: ...r etc astheycould distort indicated measurements The sensor must be placed away from sources of heat suction fans ventilation fans The general test should be performed by issuing gas from a pre calibrated bottle within the percentages marked on the bottle information label Important This test must be carried out at least once a year or more frequently if required based on a risk assesment of the s...

Page 6: ...een pinched Check the voltage between terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26 4 Vdc Check the voltage between terminals 2 3 It must be a minimum of 0 8 Vdc to a maximum of 1 1 Vdc Important Note These measurement should be perfor med in clean fresh air Moreover this test must be perfor med only with the probe connected to a control unit or with a 220 Ohm resistance instal...

Page 7: ... Pivot Gas probe SGF100 S N ED567D Year 06 2015 Batch SGF104 001 Gas Oxygen Power supply 12 24VDC Absorption 110 mA Relay 1A 30V SELV Signal 4 20 mA USB data detection Operating range 20 Positive safety OFF Positive safety ON Operating range 100 When it is mounted on the wall UP DOWN Power supply Relay Relay max 1A Power supply 30 VDC SELV detection 4 20 mA Note The relay is voltage free Contact c...

Page 8: ...he recycling of electrical and electronic equipment such as for example sales points in case you buy a new and similar product local collection points waste collection center local recycling center etc By ensuring this product is disposed of correctly you will help prevent potential negative consequence for the environment and human health which could otherwise be caused by inappropriate waste han...