5
TABLE #3 - LP GAS
Nominal Input
200,000
175,000
150,000
125,000
Vent Lengths
Vent Lengths
Vent Lengths
Vent Lengths
Altitude
Min.
Max
Min.
Max
Min.
Max
Min.
Max
0
200,000
200,000
175,000
175,000
150,000
150,000
125,000
125,000
1,000
195,900
195,750
171,900
171,200
146,900
146,700
123,050
122,250
2,000
191,800
191,500
168,800
167,400
143,800
143,400
121,100
119,500
3,000
187,700
187,250
165,700
163,600
140,700
140,100
119,150
116,750
4,000
183,600
183,000
162,600
159,800
137,600
136,800
117,200
114,000
5,000
179,500
178,750
159,500
156,000
134,500
133,500
115,250
111,250
6,000
175,400
174,500
156,400
152,200
131,400
130,200
113,300
108,500
7,000
171,300
170,250
153,300
148,400
128,300
126,900
111,350
105,750
8,000
167,200
166,000
150,200
144,600
125,200
123,600
109,400
103,000
9,000
163,100
161,750
147,100
140,800
122,100
120,300
107,450
100,250
10,000
159,000
157,500
144,000
137,000
119,000
117,000
105,500
97,500
These low pressure gas-fi red hot water boilers are design
certifi ed by CSA International, for use with natural
and propane gases. The boilers are constructed and
hydrostatically tested for a maximum working pressure of
50 psig (pounds per square inch gauge) in accordance with
A.S.M.E. (American Society of Mechanical Engineers) Boiler
and Pressure Vessel Code, Section IV Standards for heating
boilers.
Boilers are certifi ed in accordance with ANSI (American
National Standards Institute) Z21.13 standards as gas-
fi red, direct vent, condensing, hot water boilers.
Heating Capacity indicates amount of heat available
after subtracting losses up the stack. Most of this heat is
available to heat water. Small portion is heat loss from
jacket and surfaces of boiler, it is assumed this heat stays
in the structure. Net I=B=R Rating represents portion
of remaining heat applied to heat radiation or terminal
units (i.e. Finned tube baseboard, cast iron radiators,
radiant fl oor, etc.). Difference between Heating Capacity
and Net I=B=R Rating, called piping and pickup allowance,
establishes reserve for heating volume of water in the
system and offsetting heat losses from piping. Net I=B=R
Ratings shown are based on piping and pickup factor of
1.15. Net I=B=R Rating of boiler selected should be greater
than or equal to calculated peak heating load (heat loss)
for building or area(s) served by boiler and associated hot
water heating systems. Manufacturer should be consulted
before selecting boiler for installations having unusual
piping and pickup requirements
.
Complete the following prior to installing boiler.
Codes
This boiler product is a gas-fi red, direct vent, condensing
boiler. Installation must conform to the requirements of
authority having jurisdiction or, in the absence of such
requirements:
United States
•
- National Fuel Gas Code, NFPA 54/
ANSI Z223.1
Canada
•
- Natural Gas Propane Installation Code,
CAN/CSA B149.1
Where required by the authority having jurisdiction,
installation must conform to the Standard for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/ASME
CSD-1
.
BOILER RATINGS & CAPACITIES
BEFORE INSTALLING THE BOILER
Summary of Contents for Q90-125
Page 30: ...30 SERVICE HINTS DETAILED SEQUENCE OF OPERATION...
Page 36: ...36 Troubleshooting Chart 2 TROUBLESHOOTING...
Page 39: ...39 Troubleshooting Chart 5 TROUBLESHOOTING...
Page 42: ...42 This Page Intentionally Left Blank...
Page 44: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...