background image

20

Relief Valve
You must have a relief valve on your boiler. Water 

expands as it is heated. If there is no place for the water 

to expand into, water pressure will build up inside the 

boiler and system. Should this happen, the relief valve will 

automatically open at a predetermined pressure. This will 

relieve the strain on the boiler and system. Run a pipe from 

the relief valve outlet (pipe must be same size as outlet 

and the open end must not be threaded) to an open drain, 

tub or sink, or other suitable drainage point not subject 

to freezing. Failure to do so may cause water damage or 

injury should relief valve release. 

Expansion Tank
In a properly assembled system, the expanding water 

fl ows into a expansion tank. This tank should be of the 

correct size. The tank is partially fi lled with air. As the 

water expands it compresses the air in the tank to form 

an air pressure cushion. This “spring-like” cushion serves 

to maintain correct operating water pressure regardless 

of water temperature. This assures a “full measure” of a 

water, even in the highest radiation unit of the system. It 

also prevents blowing off of the relief valve. The air in the 

tank in the beginning (with system fi lled with cold water) 

is suffi cient for proper operation. The tank also serves as 

a trap for excess air in the system. The air would cause 

gurgling in the pipes and ineffi cient circulation in the 

radiators if left in the system . It is possible for a tank 

to become “waterlogged” (fi lled with water). It can also 

become overfi lled with air. This can happen after fi lling the 

system with new water. Fittings provided on the tank and in 

the line to the tank are for bleeding off excess water or air. 

When installing this tank, it is important:

That the tank be higher than the boiler top. 

1. 

That the pipe to the tank continuously rises up to the 

2. 

tank (so that air can “bubble” up to it). 

Diaphragm Type Expansion Tank
The diaphragm type expansion tank (EXTROL) takes the 

place of the conventional expansion tank. Carefully read 

the instructions packed with your EXTROL tank assembly. 
The EXTROL tank comes to you with a 10-12 pounds per 

square inch air charge. This is the same as the pressure 

produced in the system by the automatic fi ll valve. When 

the system is fi rst fi lled, the EXTROL tank will contain little 

or no water. 
As the water is heated its pressure increases. It expands 

into the EXTROL tank, compressing the air in the tank. This 

compressed air cushion permits the water in the system to 

expand as the temperature changes. The diaphragm type 

tank can be mounted on the air purger fi tting or at any 

convenient place in the supply or return line.

Air Eliminating Fitting (Air Purger)
An air purger is used to remove excess air from the 

system. It is installed in the supply line. It will eliminate air 

from the water before it reaches the radiators and bleed off 

this air.
Main Air Vent For Down Flow Systems Or Diaphragm 

Type Expansion Tank
Before a system is fi lled with water, there is air in the 

pipes and radiation units. Some of it will be trapped as the 

system is fi lled . It is possible to eliminate most of this air 

through the air vent on the radiation units. A main air vent 

will speed and simplify this. It should be installed on the 

highest point in the supply main when all radiation is below 

top of boiler. 
Automatic Fill Valve
For safe, effi cient operation, a hot water system must 

be completely fi lled with water. Adding new water, when 

needed can be done manually (by use of a hand valve in 

the water supply line). This requires regular attention to 

the system’s needs. An automatic fi ll valve accomplishes 

this without attention. It is installed in the supply line on 

hot water boilers only. The valve operates through water 

pressure differentials. It does not require an electrical 

connection.
Drain Valve
This manual valve provides a means of draining all water 

from the boiler and system. It is often installed in the 3/4” 

tapping at the bottom of the end boiler section. Or it can be 

installed in a tee where the return line enters the boiler.
Circulating Pump
Every forced hot-water system requires a circulating pump. 

This pump must have the capacity to provide the circulation 

required by your system. The pump is connected into the 

return main just ahead of the boiler. It is also wired to the 

electrical system.
Vent Damper
This product is an automatic, motorized stack damper that 

has been developed to increase the effi ciency of heating 

systems by reducing standby losses from the heating 

apparatus and the conditioned air space. The damper 

closes the chimney vent when the burner is off and fully 

opens it when combustion is required.
Rollout Switch (Flame Rollout Safety Shutoff)
The rollout switch is a temperature-sensitive fuse link 

device. It is located on the boiler base just outside the 

fi re box. In the event of heat exchanger fl ueway blockage 

causing fl ame to roll out of the fi re box, the fuse does not 

change in appearance when blown. If the rollout switch 

blows, it must be replaced with an exact replacement. 

Check heat exchanger fl ueways for blockage when 

restoring system to operating condition. DO NOT operate 
system without a rollout switch. 

EQUIPMENT AND OPTIONAL ACCESSORIES

Summary of Contents for PWXL

Page 1: ...ed Company PWXL Cast Iron Gas Fired Hot Water Boilers INSTALLATION OPERATION MAINTENANCE MANUAL DUNKIRK BOILERS 2210 Dwyer Avenue Utica NY 13504 4729 Phone 315 797 1310 Fax 866 432 7329 e mail info ec...

Page 2: ...e Operation 11 Vent Damper Operation 12 Gas Supply Piping 14 Electrical Wiring 16 Equipment and Optional Accessories 20 Starting the Boiler 21 Initial Operational Boiler Test Check Out Procedure 23 In...

Page 3: ...n monoxide which is odorless and invisible CAUTION Indicates a hazardous situation which if not avoided may result in injury NOTICE Indicates information which should be followed to ensure proper inst...

Page 4: ...by a change in main orifice size For altitudes above 2 000 feet above sea level input ratings should be reduced at the rate of 4 for each 1 000 feet above sea level Consult the latest edition of the N...

Page 5: ...care must be taken to insure a clean combustion air supply during the construction process Airborne particulates such as from drywall dust and from fiberglass insulation can clog the burner ports flu...

Page 6: ...crated boiler at selected location remove crate 2 by pulling crate sides from top and bottom boards This boiler must be set on non combustible floor or 3 optional non combustible Base Plate placed ove...

Page 7: ...not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input Mbh Refer to National Fuel Gas Code for opening C requirements between connected indoor spaces All Outdoor Air Pr...

Page 8: ...o avoid D reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible to E location protecting user from scald...

Page 9: ...or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle Low Design Water Temperature Systems Below 140 If the boiler is to be used in a heating system wher...

Page 10: ...ly Pipe Sealant On Shaft of Gauge Thread the gauge into the supply water tee as shown in 3 Figure 8 To Prevent damage do not overtighten Figure 8 Thread Gauge Into Supply Water Tee NOTICE IMPORTANT DO...

Page 11: ...the 10 chimney height HT for single appliance venting see Figure 11 The sections of vent pipe should be fastened with sheet metal screws to make the piping rigid Horizontal portions of the vent syste...

Page 12: ...damper on pipe curve Do not run wires near high temperature surfaces Use standoff brackets if necessary For safe efficient operation the vent damper and all flue product carrying areas of the applian...

Page 13: ...l control the burner firing as before while the damper will remain open DO NOT turn damper open manually or motor damage will result Set switch to AUTOMATIC OPERATION to close vent damper during burne...

Page 14: ...compound pipe dope suitable for liquefied petroleum gas Provide sediment trap upstream of gas valve See Figure 15 GAS SUPPLY PIPING CAUTION WHAT TO DO IF YOU SMELL GAS Do not try to light any applianc...

Page 15: ...e using gas detector non corrosive detection fluid or other leak detection method acceptable to authority having jurisdiction Do not use matches candles open flames or other methods providing ignition...

Page 16: ...r on a vertically mounted outlet box It should be sensing aver age room temperature THERMOSTAT LOCATIONS TO AVOID DEAD SPOTS HOT SPOTS COLD SPOTS Behind doors Concealed pipes Concealed pipes or ducts...

Page 17: ...NOTES VENT DAMPER SHIPPED LOOSE IN CRATE VENT DAMPER HARNESS MUST BE CONNECTED TO VENT WHEN MOUNTED VENT DAMPER HARNESS Figure 16 1 Field Wiring Connections Circulator Pump Wiring Thermostat TW TR Re...

Page 18: ...2 Wiring Diagram Electronic Ignition NOTICE If any of the original wire as supplied with this appliance must be replaced It must be replaced with type 105 C thermoplastic wire or it s equivalent ELECT...

Page 19: ...16 3 Wiring Diagram Standing Pilot NOTICE If any of the original wire as supplied with this appliance must be replaced It must be replaced with type 105 C thermoplastic wire or it s equivalent ELECTRI...

Page 20: ...re changes The diaphragm type tank can be mounted on the air purger fitting or at any convenient place in the supply or return line Air Eliminating Fitting Air Purger An air purger is used to remove e...

Page 21: ...any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only yo...

Page 22: ...Turn off all electric power to the appliance 3 Remove lower front panel 4 Rotate the gas control knob clockwise 5 to OFF See Figure 18 Wait five 5 minutes to clear out any gas Then smell 6 for gas inc...

Page 23: ...rating and should go off when controls are tested When controls are reset burners should reignite o Test ignition system safety shutoff device after placing boiler in operation See page 25 o For multi...

Page 24: ...er maintenance personnel Installation Location Customer Name __________________________________________________________________________ Address ________________________________________________________...

Page 25: ...e inter mittent pilot control box The gas valve should shut off the main burners TURN OFF ELECTRIC POWER to boiler before reconnecting ignition cable to prevent electric shock Relight The electric and...

Page 26: ...ntact an authorized contractor or qualified service technician to replace the relief valve and inspect the heating system to determine the cause as this may indicate an equipment malfunction This valv...

Page 27: ...hermostat call for heat HIGH LIMIT YELLOW Water temperature at high limit ACTIVE GREEN Active power to unit is on There are four adjustable settings on the control These can be adjusted using a small...

Page 28: ...mit setting For example if the High Temperature Limit is set at 1900 F with the High Temperature Differential at 200 F then the Low Temperature Limit needs to be set at 1700 F or lower If the settings...

Page 29: ...er current protection Check to be sure electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow...

Page 30: ...NOTES...

Page 31: ...Date Service Performed Company Name Tech Initials Company Address Phone...

Page 32: ...DUNKIRK BOILERS 2201 Dwyer Avenue Utica NY 13504 4729 web site www ecrinternational com...

Reviews: